You are on page 1of 53

Components

2-5.3.1.8 Second-Shot Delay, P/N 83-132524-000

The Second-Shot Delay is a pneumatic actuation device that prevents pressure from continuing
downstream for approximately 18-21 seconds.

The Second-Shot Delay must only be coupled to a pneumatic actuator via Flex
Hose Kit, P/N 87-120045-001. Failure to do so will result in an incorrect delay
CAUTION time and possible system failure.

2.00 in.
(51 mm)

2.81 in.
(71 mm)
1/8-in. NPT
(Inlet from
Second-Shot
Actuator)

1/4-in.-20 Threaded
1/8-in. NPT
holes for bracket
(Outlet to
attachment
actuation
BACK line) FRONT

Figure 2-33. Second-Shot Delay, P/N 83-132524-000

P/N 83-132550-000 2-31 April 2022


Components

2-5.3.1.9 Second-Shot Delay Bracket

The Second-Shot Delay is mounted on a Second-Shot Delay Bracket, P/N 83-132535-000. This
bracket must NOT be welded to the vehicle. In order to remove or replace the Second-Shot
Delay assembly, the bracket must be removed from the vehicle.

3.52 in.
(89 mm)

1.39 in.
(35 mm)

2.85 in.
(72 mm)

2 x DIA. 0.33 in. (8.4 mm)

Figure 2-34. Second-Shot Delay Bracket, P/N 83-132535-000

2-5.3.1.10 Flex Hose Kit, P/N 87-120045-001

The Flex Hose Kit is a stainless steel hose with a 1/8-in. NPT adapter that is used to transfer
pressure between a pneumatic actuator and the Second-Shot Delay.

7.5 in.
(191 mm)
(End to Seat)

1/8-in. NPT

Figure 2-35. Flex Hose Kit, P/N 87-120045-001

April 2022 2-32 P/N 83-132550-000


Components

2-5.3.2 CHECK VALVE, P/N WK-259404-000

The 1/4-in. Check Valve, P/N WK-259404-000, is used to isolate sections of actuation hose,
when multiple pneumatic actuation sources are connected to a single system.

0.250-18 NPT
0.125-27 NPT 2.440 REF.
(FEMALE)
(MALE)

Figure 2-36. Check Valve, P/N WK-259404-000

Table 2-21. Specifications, 1/4-in. Check Valve, P/N WK-259404-000

Description Specification

Maximum Operating Pressure: 3000 psig


Cracking Pressure: 2 psi
Proof Pressure: 6000 psig
Minimum Burst Pressure: 12,000 psig
Operating Temperature Range: -65ºF to 200ºF

2-5.3.3 VENT CHECK (OPTIONAL), P/N WK-877810-000

The vent check has an aluminum body and a spring-loaded nylon ball to act as the vent check.
It is used as a safety device to relieve pressure in the actuation hose.

0.66 in. 0.5 in.


(17 mm) (13 mm)

0.16 in. DIA.


(4 mm)

45°
APPROX.

0.125-27 NPT

Figure 2-37. Vent Check, P/N WK-877810-000

P/N 83-132550-000 2-33 April 2022


Components

2-5.3.4 ACTUATION MONITOR SWITCH, P/N 42-990132-510

The Actuation Monitor Switch (AMS) is an ingress protected normally open switch assembly,
that provides a signal to the interfacing panel when pneumatically actuating the system. The
AMS provides one male and one female Deutsch DT Series 2-pin connector, which allows
installing the AMS as either first or last device on the manual release circuit.

To re-set the switch, simply vent the corresponding pneumatic actuation line.

End-of-Line Resistor
(see note)
P/N 83-132487-200 24mm 1/8” NPT

Figure 2-38. Actuation Monitor Switch

Note: End of Line (EOL) Resistor provided with the panel. EOL shown as illustrative only. EOL
only affixed to the last device in the manual release circuit.

April 2022 2-34 P/N 83-132550-000


Components

2-6 SUPERVISION COMPONENTS

Supervisory components allow the Envirotech Sentinel SA1 to monitor the state or condition of
system components that are critical to the operation of the system.

2-6.1 Supervisory Pressure Switch, Sentinel System,


P/N 83-131411-200 (Dry Chemical), P/N 83-130411-200 (Wet Chemical)

The Supervisory Pressure Switch is a normally open switch that is mounted on a wet and/or
dry chemical suppression agent cylinder. Under normal conditions, the pressure in the cylinder
maintains the switch in the open position. When the cylinder pressure falls below the minimum
limit, the contacts close to provide an electric signal to the Envirotech Sentinel SA1. The switch
assembly utilizes water-resistant construction with two Deutsch DT Series 2-pin connectors,
and is assembled with one male and one female connector to allow chaining of multiple
switches on a single circuit. The length of the lead wires is sized to allow the switches to be
directly connected when multiple cylinders are close-coupled.

Supervisory Pressure Switches are factory-installed on agent cylinders.

16.00 in.
(406 mm)

1/8-27 NPT
9/16 HEX
Figure 2-39. Supervisory Pressure Switch, Sentinel System, P/N 83-13X411-200

Table 2-22. Supervisory Pressure Switch Part Numbers

Part Number Use

83-131411-200 Dry Chemical


83-130411-200 Wet Chemical

P/N 83-132550-000 2-35 April 2022


Components

2-7 NOTIFICATION COMPONENTS

Notification components alert occupants and bystanders to a fire and provide instruction for
reacting to a fire.

2-7.1 Sign, P/N 83-132470-020

The sign, as shown in Figure 2-40, is 8 in. X 4 in., red on gray.

DIA 0.28 in.


(7 mm) x 4

8.00 in.
(203 mm)

THIS SPACE PROTECTED


4.00 in.
BY ENVIROTECH 3.32 in.
(102 mm)
FIRE SUPPRESSION (84 mm)

SYSTEM
7.32 in.
(186 mm)

Figure 2-40. 8-in. X 4-in. Red on Gray Sign, P/N 83-132470-020

April 2022 2-36 P/N 83-132550-000


Components

2-8 AUXILIARY ACTUATION COMPONENTS

Auxiliary actuation components allow the system to activate or de-activate components or


systems other than the suppression system. Uses typically include shutdown of the vehicle
engine or cooling fans, closure of dampers, or depressurization of hydraulic lines.

2-8.1 Pressure Switch, P/Ns 83-100002-001 and 83-100007-001


Note: Not FM Approved components.

Pressure switches may be installed on the pneumatic actuation line to control auxiliary devices
upon a pneumatic actuation of the suppression system. Each switch has a set of normally open
or normally closed contacts and is provided with a set of flying leads, which may be trimmed
to suit.

Pressure Switches may not be installed on the suppression discharge hose.


CAUTION

Full system operation, including auxiliary devices, must occur upon automatic
detection or when any manual actuator is activated. The use and location of
CAUTION Pressure Switches for auxiliary control must be carefully considered to achieve
this objective.

Figure 2-41. Pressure Switch

Table 2-23. Pressure Switch Contact Types

Part Number Contact Type

83-100002-001 Normally Open


83-100007-001 Normally Closed

P/N 83-132550-000 2-37 April 2022


Components

2-9 TOOLS

2-9.1 IR Detector Test Kit, P/N 83-132016-001

The IR Detector Test Kit provides a test lamp that is used to activate the IR-1A Flame Detector.
This also tests the ability of the system’s detection circuit to receive an activated flame
detector.

2-9.2 Release Circuit Test Kit, P/N 83-132537-000

The Release Circuit Test Kit is designed to test the initiation circuitry and cables of the
Envirotech Sentinel SA1. The circuit tester can be connected in place of an Protractor Assembly
to simulate its operation. The circuit tester has a push button indicator that can be easily reset
for the next test.

Figure 2-42. Release Circuit Test Kit

2-9.3 Detection Circuit Test Kit, P/N 83-132490-100

The Detection Circuit Test Kit is designed to test the detection circuitry and cables of the
Envirotech Sentinel SA1. This tester provides a technician with the ability to test any portion
of the detection circuit by connecting the tester into the initiation circuit.

The Detection Circuit Test Kit includes a built-in end-of-line resistor.

Figure 2-43. Detection Circuit Test Kit

2-9.4 Supervisory Circuit Test Kit, P/N 83-132490-500

The Supervisory Circuit Test Kit is designed to test the supervisory circuitry and cables of the
Envirotech Sentinel SA1. This tester is connected to the plug that connects to the Supervisory
Pressure Switch located on the cylinder valve assembly of the suppression system. This tester
can simulate a low pressure condition of a suppression system cylinder.

The Supervisory Circuit Test Kit includes a built-in end-of-line resistor.

Figure 2-44. Supervisory Circuit Test Kit

April 2022 2-38 P/N 83-132550-000


Components

2-9.5 Actuation Test Adapter, P/N 83-132526-000

The Actuation Test Adapter provides a means to test the Mechanical Actuator, Remote System
Actuator, Second-Shot Actuator, Second-Shot Delay, and actuation hose network for leaks.
The test adapter allows a technician to connect a regulated air or nitrogen source in place of
the 15-in3 Nitrogen Cartridge.

2-9.6 Deutsch Crimp Tool, P/N 83-132027-001

The Deutsch Crimp Tool is a hand tool used to add a Deutsch connector to the end of a cable.

2-9.7 Deutsch Wedge and Contact Removal Tool, P/N 83-132028-001

The Deutsch Wedge and Contact Removal Tool is used for extracting pins and sockets from
connectors.

2-9.8 SA1 Battery Test Cable, P/N 83-132490-400

The Primary Cell By-Pass Cable, P/N 83-132490-400, is a cable with length of 8-1/2 ft.
(2.6 m) which may be used to by-pass the SA1 Primary Cell and connect to a standard lead
acid 12V battery. This allows service personnel to perform Sentinel SA1 maintenance testing
while plugged into a standard battery instead of the Primary Cell.

To use the cable, remove the SA1 cover and disconnect the Primary Cell connector from the
SA1 Power Supply board. Connect the spade connectors at one end of the cable to the test
battery terminals. Connect the other end of the cable to the SA1 Power Supply board (where
the Primary Cell was just disconnected). There is no need to remove the Primary Cell from the
SA1. Upon completing servicing, disconnect the cable and reconnect the Primary Cell. Re-
attach the SA1 front cover.

P/N 83-132550-000 2-39 April 2022


Components

THIS PAGE INTENTIONALLY LEFT BLANK.

April 2022 2-40 P/N 83-132550-000


System Design

CHAPTER 3
SYSTEM DESIGN

This chapter is intended for system designers and outlines the design of a Envirotech®
Sentinel® SA1 Vehicle Fire Protection System. The information is based on the requirements
of Envirotech Fire Systems, FM Approvals, and the National Fire Protection Association (NFPA)
Standards 17 and 72 (current editions). All installations must meet the requirements of the
applicable regulations and local regulatory requirements.

The design of a Envirotech Sentinel SA1 system may be broken into the following steps:

1. Perform a hazard analysis.


2. Select a suppression solution.
3. Select a detection solution.
4. Select a suppression actuation method.
5. Lay out the suppression, detection, and actuation systems.
6. Determine auxiliary components/systems to be controlled in conjunction with a
suppression release.
7. Determine components/systems to be supervised.
8. Determine the appropriate configuration for the Sentinel SA1.

3-1 PERFORM A HAZARD ANALYSIS

The first step in any fire protection design project is to perform a complete hazard analysis,
which requires the designer to identify and survey the fire hazards that require a fire protection
system.

Note: A general fire protection strategy should be compliant with a recognized standard, such
as NFPA 121 (Standard on Fire Protection for Self-Propelled and Mobile Surface Mining
Equipment) or Australian Standard AS-5062 Fire Protection for Mobile and
Transportable Equipment, that is acceptable to the Authority Having Jurisdiction.

3-1.1 Hazard Identification

A fire hazard exists whenever a fuel, an oxidizer, and an ignition source may interact, such that
there is a probable risk of fire. Upon identifying these locations, a risk assessment is performed
to determine which fire hazards require mitigation in the form of a fire protection system.

This assessment should consider:

• expected emergency response time;


• vehicle operation schedule;
• effect and cost of vehicle downtime;
• vehicle replacement cost; and
• fire history of the vehicle or similar ones used under similar conditions

P/N 83-132550-000 3-1 April 2022


System Design

The following is a list of typical hazard areas for mobile equipment:

• Turbocharger
• Exhaust manifold and pipes
• Starter motor, alternator, battery
• Fuel injectors
• Fuel and hydraulic lines
• Transmission units
• Hydraulic pumps, tanks, and manifolds
• Brakes
• Electrical connections and wiring

Consideration should also be given where liquid fuel may drip, splash, or flow, carrying fire
away from its starting point; or where radiated heat, sparks, or conduction through metal can
carry heat to an area where it would not normally exist.

Always consult the fire history of the vehicle, or similar equipment. This may be available
through company records. The operator of the vehicle may be able to identify the locations of
previous fires and/or special hazards, such as a hydraulic hose that frequently comes loose at
a given point. Fire marshals, insurance companies, or other authorities having jurisdiction are
also likely to provide recommendations and/or requirements, as a result of their experience.

3-1.1.1 FUELS

In accordance with NFPA Standards, fuels are classified as:

• Class A – Solid fuels


• Class B – Flammable and combustible liquids and gases
• Class C – Electrically energized equipment

The primary fuels on a vehicle are typically Class B fuels, such as gasoline, diesel fuel, engine
oil, lubricating oil, hydraulic oil, and propane. In addition, Class A fuels, such as electrical wire
insulation and vehicle components made of rubber or plastic, present a secondary fuel source.
Environmental and conditional fuels such as leaves, brush, garbage, or coal dust, may also be
present.

3-1.1.2 OXIDIZERS

The most common oxidizer is air. However, particular attention should be given when the
hazard area includes oxygen storage tanks or other oxidizers (such as: magnesium, calcium
carbide, potassium, and sodium).

April 2022 3-2 P/N 83-132550-000


System Design

3-1.1.3 SOURCES OF IGNITION

Heat from the engine, transmission, exhaust system, pumps, turbochargers, and electric
motors are the primary sources of ignition for most vehicles. In addition, bearings, brakes,
gears, electrical systems, and environmental conditions provide secondary sources of ignition
heat.

Sparks and embers are intermittent ignition sources, capable of transmitting ignition energy
to an otherwise shielded or distant fuel. Sparks are produced by arcing electrical equipment,
while embers are created by processes such as metalworking or woodcutting, that produce
heated particles.

While pilot flames do not typically exist during the normal operation of most vehicles, they may
be present during maintenance (e.g., a welding torch) or as a condition of the surrounding
environment or the vehicle’s use (e.g., a foundry).

Chemical processes, such as the decomposition of fuel or other debris, may produce adequate
heat to result in the ignition of nearby fuels.

3-1.2 Hazard Survey

Once the areas requiring protection have been identified, additional information is required. As
a minimum, a hazard survey should gather the following information:

• Locations, quantities, and types of the likely fuels


• Locations and types of ignition sources
• Dimensions of the area to be protected, including interconnected spaces, and areas where
fire could spread in the event of a fuel leak
• Locations and dimensions of any un-closeable openings
• Flow rate and wind-down time of forced ventilation that cannot be dampered or shut down
• Minimum and maximum ambient temperatures
• Occupancy status and the path of egress
• Locations of all obstructions
• Acceptable locations for suppression agent storage
• Work processes and vehicle pivots and joints that may affect and/or be affected by the
placement of fire protection components
• Any additional requirements specified by the Authority Having Jurisdiction
• Pressure venting of hydraulic system

3-1.3 Zone Definition

The Sentinel SA1 is designed to provide full fire protection functionality for a single hazard area
or suppression zone; therefore, the identified hazard areas must be grouped and/or
compartmentalized to provide an optimum protection scheme.

In accordance with NFPA 17, any hazard that will allow fire propagation from one area to
another shall constitute a single fire hazard. Where two or more hazards could be
simultaneously involved in fire by reason of their proximity, the hazards shall be protected as
a single suppression zone.

P/N 83-132550-000 3-3 April 2022


System Design

3-1.4 Performance Objectives

In conjunction with the vehicle owner and any authorities having jurisdiction, performance
objectives for the fire protection system should be established through careful analysis of both
economic and safety concerns.

3-2 SELECT A SUPPRESSION SOLUTION

The Envirotech Sentinel SA1 may be used in conjunction with one or more suppression systems
to achieve a complete fire protection solution. A single hazard area may be protected with
either a single-release system or dual-release system, or may be provided with an alarm-only
(i.e., no suppression) system. Of those suppression agents referenced in Chapter 1 of this
manual, the most appropriate should be selected for each hazard, in order to meet the
performance objectives.

3-2.1 Single-Release Systems

A single-release suppression system is comprised of one or more agent cylinders, each


connected to a discharge network and nozzles. The cylinders discharge in concert to provide
suppression coverage throughout the entire hazard. Figure 3-1, Figure 3-2, and Figure 3-3
each show a version of a single-release system:
• Pneumatic/Pneumatic
• Electric/Pneumatic
• Electric/Electric

Cylinder
Actuator (typ)
Maintenance
Into SA1

Bypass Switch
Releasing
MR REL-1 Into NCM
or cable
cct in
AR-1

SUP
DET-1

DOT-E XXXX-XXXX

Mechanical
Actuator
Actuation Monitor Remote System
Switch Actuator
Into NCM
or cable

Figure 3-1. Single-Release System—Pneumatic/Pneumatic

April 2022 3-4 P/N 83-132550-000


System Design

Sentinel SA1
FIRE SYSTEM CONTROL UNIT

SYSTEM
SERVICE
POWER DUE SUERVISORY BATTERY LOW REPLACE

ALARM TROUBLE SILENCE

ALARM
OVERRIDE RESET
RELEASE

Cylinder

Into SA1
Maintenance Actuator (typ)
Bypass Switch Mechanical
Releasing Releasing
Actuator
cct out cct in
Releasing
MR REL-1 Into NCM cct in Releasing Releasing
cct in
In-line Connector, Releasing Into Metron
or cable cct out Release cct out Receptacle

Releasing Releasing
cct in cct out

AR-1

SUP
DET-1
XXXX-XXXX E-TOD

DOT-E XXXX-XXXX

Mechanical Actuation Monitor


Actuator Switch
Into NCM
or cable

Figure 3-2. Single-Release System—Electric/Pneumatic

Maintenance Cylinder
Bypass Switch Actuator (typ)

Releasing Releasing
cct in
Releasing
cct out cct in

In-line Connector, Releasing Into Metron


Release cct out Receptacle

Releasing Releasing
cct in cct out
Into SA1

Electric Manual
Release MR REL-1 Into NCM
or cable
AR-1

SUP
DET-1
Into NCM
or cable

Figure 3-3. Single-Release System—Electric/Electric

P/N 83-132550-000 3-5 April 2022


System Design

3-2.2 Dual-Release Systems

The dual-release system is comprised of two independent suppression systems that each
provide total coverage of the hazard. The systems are actuated sequentially to provide an
extended discharge of the primary agent (i.e., Sentinel DCS-Sentinel DCS or Sentinel LS-
Sentinel LS) or to meet certain performance criteria, such as rapid flame extinguishment
followed by rapid cooling of the fuel (i.e., Sentinel DCS-Sentinel LS). Figure 3-4 shows a
version of a Pneumatic/Pneumatic dual-release system:
Into SA1

Maintenance
Bypass Switch
Releasing
Into NCM cct in
MR REL-1 or cable
AR-1

SUP
DET-1

Actuation
or cable
Into NCM

Monitor
Switch
Cylinder
Actuator (typ)

DOT-E XXXX-XXXX Check Check


Valve Valve
Cylinder
Mechanical DOT-E XXXX-XXXX

Actuator (typ) Remote System


Actuator Second- Second- Actuator
Shot Shot
Actuator Delay

This provides immediate discharge from manual


pressure operated release. It is assumed that the
automatic release will be programmed the same.

Figure 3-4. Dual-Release System—Pneumatic/Pneumatic

3-2.3 Alarm Only Systems

While such systems are rare in vehicles, the Envirotech Sentinel SA1 may also be configured
to provide an Alarm-Only option (i.e., no suppression). This type of system may be used for
notification and equipment shut-down/control in the event of a fire.

April 2022 3-6 P/N 83-132550-000


System Design

3-3 SELECT A DETECTION SOLUTION

The selected method of detection should be based on the typical fire products (i.e., heat,
radiation, smoke, etc.) for the most likely fuel type in the given hazard and on the performance
objectives of the system.

The Detection circuit of the Sentinel SA1 is designed to allow any combination of the detectors
shown in Chapter 2, up to a maximum total current draw of 180 mA (only when on vehicle
power—NOT if using the Primary Cell Battery). The maximum per-circuit cable length is 300 ft
(90 m).

If using the Primary Cell Battery, powered detectors are not allowed by the
CAUTION Envirotech Sentinel System.

Note: There is no limit on the quantity of non-powered devices that may be used.

3-3.1 Heat Detector Use and Location

At least one heat detector of any type must be installed in each protected compartment. Locate
and mount spot detectors and Linear Heat Sensor detectors in accordance with the following:

• Observe all operating limitations of the selected detector, as described in Chapter 2.


• Mount the thermal spot detector (Detect-A-Fire) close to potential sources of fire. (Since
the detector is only capable of detection at a single point, care must be taken in selecting
the proper mounting locations.)
• Mount the detectors high in the compartment and above potential fire hazards such as
turbos, exhaust components, and alternators. In areas with high airflow, the detectors
should be mounted downwind of the potential fire sources.
• Select the detectors relative to the hazard or ambient compartment temperature, since
they are available with different temperature settings. Proper selection of the temperature
setting will optimize response time to a fire situation and minimize false alarms.
• Locate the detector where it will be protected from mechanical, environmental, or other
conditions that could render it inoperable.
• Locate the detector near and above the hazard where heat from a fire is likely to flow
and/or be trapped.
• Locate the detector where it will be accessible for maintenance and service.
• Select an appropriate temperature setting for the observed maximum normal ambient
temperature at the detector location.
• Do not paint the detector, as this will increase the thermal lag.
• Do not mount the detector on any vehicle component that is likely to be removed during
maintenance or service, such as air cleaner housings, engine carriage brackets, removable
guards or shields, or brackets holding other components.
• Do not locate a detector directly on a “hot” component, such as an exhaust manifold,
turbocharger, engine block, or radiator.

P/N 83-132550-000 3-7 April 2022


System Design

3-3.2 IR-1A Infrared Fire Sensor Use and Location

The Envirotech IR-1A infrared fire sensor can only be used when the Sentinel SA1 is using
vehicle power (i.e., can not be used while on primary cell power).

The Envirotech IR-1A infrared fire sensor has a 100° solid cone field-of-view and should be
positioned to view potential fire hazard areas. With an unobstructed view, the fire sensor can
detect fires in any location of an engine compartment. Since sensor sensitivity is reduced as
the angle from the face of the sensor is increased, the sensor should face towards the area of
most concern. Some engine compartments are very large or have a number of significant
obstructions. In these areas, a fire may develop and propagate for some time before a single
sensor detects and alarms. It is recommended to use more fire sensors in large and/or
congested engine compartments to view all hazard areas.

Table 3-1 shows the IR-1A specifications.

Table 3-1. Infrared Flame Detector Specifications

Description Specification

Operating Temperature Range: -40ºF to 257ºF (-40ºC to 125ºC)


Enclosure Rating: NEMA 4X/IP-66
Weight: 1 lb.

The IR-1A should be mounted high in the engine compartment using the Mounting Bracket Kit,
P/N 83-131060-001, and pointed below the horizontal to minimize contamination of the lens.
It is important to avoid placing fire sensors too close—less than 1.5 ft (458 mm)—to extremely
hot surfaces such as turbochargers, manifolds, or exhaust pipes. Avoid any obstructions such
as hoses or harnesses in the face of the fire sensor that would limit its field-of-view. Mounting
fire sensors so that they do not view brightly illuminated areas will help ensure optimum
performance. The fire sensors should be in an accessible location, with a minimum clearance
of 4 inches from the sensor face, so as to facilitate cleaning and testing efforts.

100°
CONE

½X

DETECTOR

Figure 3-5. IR-1A Sensor Orientation

April 2022 3-8 P/N 83-132550-000


System Design

100°

4 INCHES MINIMUM
CLEARANCE FOR
USE OF TEST
EQUIPMENT

Figure 3-6. IR-1A Fire Sensor Installation Orientation

The IR-1A should not be located where road dust or oils from fan belts or other moving parts
can be deposited. Where more than one sensor is required, overlap their fields-of-view.

Note: For FM Global insured equipment, the Model IR-1A infrared detector must be used in
conjunction with thermal heat detection to comply with FM Global Property Loss
Prevention Data Sheet 7-40, Heavy Duty Mobile Equipment. This is due to no "Through
Lens Supervision" on this infrared detector. Acceptable secondary heat detection
devices are: Detect-A-Fire® Detector, P/N 83-132440-XXX and Linear Heat Sensor
Cable, P/N 83-100003-001.

Table 3-2. Sensor Detection Threshold (Range)

Type of Test Fire Sensor Detection Threshold (Range)

1-ft2 Methanol Pan Fire 36 in.

1-ft2 Gasoline Pan Fire 42 in.

1-ft2 Diesel Pan Fire 42 in.

30-in. Natural Gas Flame, 3/8-in. Orifice 20 in.


30-in. Hydrogen Gas Flame, 3/8-in. Orifice 12 in.

P/N 83-132550-000 3-9 April 2022


System Design

3-4 SELECT A SUPPRESSION ACTUATION SOLUTION

3-4.1 Modes of Operation

A system or its components may be operated without human intervention (i.e., automatic) or
through human action (i.e., manual). The Envirotech Sentinel SA1 system shall be provided
with both automatic and manual means of operation.

Note: “Manual only” systems may be permissible only if acceptable to the authority having
jurisdiction.
Note: FM Global does not allow “manual only” operation.

The manual actuation means of an automatic extinguishing system should be independent of


the automatic means, such that a failure of a system component does not impair both the
automatic and manual means of actuation.

Operation of any automatic or manual actuator shall be all that is required to bring about the
full operation of the system.

3-4.1.1 AUTOMATIC OPERATION

Automatic operation occurs when one or more automatic fire detectors is activated, which
initiates an alarm condition on the control panel, causing the system to notify the operator and
to actuate the suppression and auxiliary systems.

3-4.1.2 MANUAL OPERATION

Manual operation occurs when an individual activates a manual release station, which may
then either initiate an alarm condition to the Sentinel SA1, or actuate the suppression system
directly.

Operation of a single actuator shall cause all functions to operate as intended.

The means for manual actuation shall be mechanical and shall not rely on any of the hardware
components that would be common to the automatic function of the fixed fire-extinguishing
equipment.

In accordance with NFPA 17, the Electric Manual Release, P/N 83-132455-000,
may be used only when a reserve power supply or a secondary mechanical
WARNING means of actuation is also provided.

Note: The Primary Cell Battery, P/N 83-132400-100, satisfies the requirement for a reserve
power supply.
• At least one manual actuator shall be provided for each system.
• At least one easily accessible manual actuator or operating device shall be provided for use
by the equipment operator, and at least one shall be located so that it is in the path of
egress and operable from ground level.
• All operating devices shall be designed, located, installed, or protected so that they are not
subject to mechanical, environmental, or other conditions that could render them
inoperative or cause unintentional operation of the system.
• All manual actuators shall be identified as to the hazard they protect.
• All manual actuators shall be provided with operating instructions.

April 2022 3-10 P/N 83-132550-000


System Design

3-4.2 Actuation Methods

Actuation of a suppression system may be accomplished by either of two methods:


• Electric – The suppression cylinder valve is directly activated by an actuator, which is
activated by a Release circuit on the Sentinel SA1.
• Pneumatic – The suppression cylinder valve is activated by the application of nitrogen
pressure from a cartridge.

3-4.2.1 ELECTRIC ACTUATION SYSTEM

The Release Circuit on the Sentinel SA1 is capable of activating up to 3 Protractors, P/N 83-
132500-500.

3-4.2.2 PNEUMATIC ACTUATION SYSTEM

3-4.2.2.1 Actuation Hose

If the system is pneumatically actuated, 1/4-in. Actuation Hose (hydraulic) must be used.
Hoses for the Envirotech Sentinel System meet SAE 100 R1 AT minimum specifications, USBM
flame resistance requirements as specified in MSHA 2G, and all other SAE requirements,
including an operating range of -65ºF (-54ºC) to +200ºF (+93ºC).
The following SAE standards should be used for reference:
• SAE J516 Hydraulic Hose Fitting Standard
• SAE J517A Hydraulic Hose Standard
• SAE J343 Standard

Fittings shall be used, as necessary, where hose is connected to actuators, pressure switches,
check valves, tees, and distributors. Swivel hose couplings may be used at any location.
Fittings should be the hydraulically crimped type and in accordance with the manufacturer’s
specifications.

Actuation hose shall not run through protected spaces. Where it is necessary to
route the actuation line through the protected space, tubing or pipe of
WARNING equivalent diameter and pressure rating shall be used.

When pneumatic actuation is utilized, the maximum quantity of agent cylinders that can be
operated and the maximum length of actuation hose that can be used are summarized in
Table 3-3.

Table 3-3. Actuation Limits of Pilot Cylinders

Cartridge Part Maximum Total Length Maximum Length


Maximum Components Operated
Number 1/4-in. Hose Between First and Last

Pneumatic/Elec Second Shot


Control Head Actuator
WK-878508-000 125 ft (38 m) 123 ft (37.5 m) 8 1

When more than one remote actuator is used, the actuators shall be isolated by ¼-in. check
valves (P/N WK-259404-000). Each actuator shall be capable of initiating the entire system.

When multiple actuators are used, the actuators shall not share a common line.
WARNING Tees shall occur at the actuated valve.

P/N 83-132550-000 3-11 April 2022


System Design

3-4.2.2.2 Actuation Monitor Switch, P/N 42-990132-510

The pneumatic actuation hose must be fitted with an Actuation Monitor Switch, connected to
the Manual Release Circuit, to provide a full system response upon manual pneumatic
discharge (See Figure 3-7.)

For configuring information of the Manual Release Circuit, see the following sections in
Chapter 5, “Configuring the Envirotech Sentinel SA1 System”:

• Section 5-1.1, “Configuration Mode”


• Table 5-2, “Sentinel SA1 Configurable Parameters via Programming”

Into SA1
MR

REL-1
AR-1

SUP
DET-1

Figure 3-7. Actuation Monitor Switch Connected to Manual Release Circuit

The switch may be the first or last device on the actuation line and may be threaded directly
into the outlet side of the last control head. The EOL shall only be affixed to the last device in
the manual release circuit. Figure 3-8 shows an Actuation Monitor Switch in a multi-station
system.

April 2022 3-12 P/N 83-132550-000


System Design

Mechanical
Actuator 2
End-of-Line Resistor
To Sentinel
SA1
XXXX-XXXX E-TOD

Actuation Monitor
Switch
1/8 NPT
Mechanical
Actuator 1 Cylinder
Actuator (typ)

DOT-E XXXX-XXXX

Figure 3-8. Actuation Monitor Switch in a Multi-Station System

In systems that utilize multiple actuation stations, the switch must be located downstream of
all check valves, where it may be activated by pressure from any manual actuation station.
Figure 3-9 shows an Actuation Monitor Switch in a single-station system.

Cylinder
Mechanical Actuator (typ)
Actuator
Actuation Monitor
Switch End-of-Line
Resistor
1/8 NPT
DOT-E XXXX-XXXX

Figure 3-9. Actuation Monitor Switch in a Single-Station System

3-5 LAY OUT THE SUPPRESSION, DETECTION, AND ACTUATION SYSTEMS

Referencing the appropriate design manual(s) for the selected suppression system(s) and the
parameters of the selected detection and actuation methods described in this manual,
determine the equipment locations and the required lengths and sizes of the interconnecting
hose and cables.

3-6 AUXILIARY SYSTEMS

The Envirotech Sentinel SA1 can be configured to perform auxiliary functions, such as engine
or fan shutdown, damper closure, or de-pressurization of hydraulic lines.

Electrical devices may be controlled by the Alarm Relay on the Sentinel SA1 or by a Pressure
Switch attached to the pneumatic actuation system.

The Alarm Relay may be configured to operate upon detection alarm or manual release alarm.
See Section 2-2.2.8 for further details.

P/N 83-132550-000 3-13 April 2022


System Design

3-7 SUPERVISION

The Supervisory Circuit on the Sentinel SA1 may be used to monitor any condition or system
component that may impair the effective operation of the system, including loss of pressure in
suppression cylinders.

3-8 DETERMINE THE SENTINEL SA1 CONFIGURATION

The Envirotech Sentinel SA1 system may be configured in accordance with any of the following
options:

1. Electric Automatic/Pneumatic Manual Suppression Actuation w/Single Release Suppression


2. Electric Automatic and Manual Suppression Actuation w/Single Release Suppression
3. Pneumatic Automatic and Manual Suppression Actuation w/Single Release Suppression
4. Pneumatic Automatic and Manual Suppression Actuation w/Dual Release Suppression
5. Automatic Alarm-Only and Pneumatic Manual Suppression Actuation w/Single Release
Suppression
6. Automatic Alarm-Only and Pneumatic Manual Suppression Actuation w/Dual Release
Suppression
7. Alarm Only

Table 3-4. Configuration Drawings

ACTUATION AND ALARM SUPPRESSION

AUTOMATIC MANUAL
RELEASE FIGURE
SUPPRESSION SUPPRESSION
NUMBER
Automatic
Electric Pneumatic Electric Pneumatic Single Dual
Alarm

X X X X Figure 3-10
X X X X Figure 3-11
X X X X Figure 3-12
X X X X Figure 3-13
X X X Figure 3-14
X X X Figure 3-15
X Figure 3-16

April 2022 3-14 P/N 83-132550-000


System Design

Fuse at

Into SA1
Battery
Inline fuse
supplied
by others

~~
Vehicle Power

REL-1
AR-1

SUP
MR
(Battery)

DET-1
To Engine
shutdown,
etc.
AUTOMATIC DETECTION
Maintenance
Bypass Switch
Detect-A-Fire Detector

EOL
Device

IR-1A Detector

MANUAL ACTUATION EOL


Device

1/4-in. Actuation
Hose Control Heads and Valves

SUPPRESSION SYSTEM

NOTES:
SENTINEL SA1 CONFIGURATION 1. AUTOMATIC OPERATION: An alarm signaled by an
automatic fire detector will result in simultaneous, direct,
Feature Setting electrical actuation of each suppression cylinder following a
Manual Release Type Pneumatic programmed delay. The Override function may be used during
the pre-discharge alarm.
Release Delay Time Per requirements
2. MANUAL OPERATION: Operation of a pneumatic
Relay Per requirements manual release station will result in direct, immediate,
pneumatic actuation of each suppression cylinder and the
Discharge Monitor Switch. Upon activation, the Discharge
Monitor Switch will provide a signal to the control panel, which
will activate the relay, but not the release circuit.
3. Individual circuits may remain unused or may include
additional devices, depending on actual requirements. Unused
circuits must be fitted with an End-of-Line Device or Blanking
Plug, as appropriate.

Figure 3-10. Electric Automatic/Pneumatic Manual Suppression Actuation


with Single Release Suppression

P/N 83-132550-000 3-15 April 2022


System Design

Into SA1
Fuse at
Battery
Inline fuse
supplied
by others

~~
Vehicle Power

REL-1
AR-1

SUP
MR
(Battery)

DET-1
To Engine
shutdown,
etc.
AUTOMATIC DETECTION
Maintenance
Bypass Switch
Detect-A-Fire Detector

EOL
Device

IR-1A Detector

MANUAL ACTUATION EOL


Device

EOL
Device

Electric Manual Release Control Heads and Valves

SUPPRESSION SYSTEM
NOTES:
SENTINEL SA1 CONFIGURATION 1. AUTOMATIC OPERATION: An alarm signaled by an
automatic fire detector will result in simultaneous, direct,
Feature Setting electrical actuation of each suppression cylinder following a
Manual Release Type Electric programmed delay. The Override function may be used during
the pre-discharge alarm.
Release Delay Time Per requirements
2. MANUAL OPERATION: An alarm signaled by an electric
Relay Per requirements manual release station will result in simultaneous, direct,
electrical actuation of each suppression cylinder following a
programmed delay. The Override function will be disabled
during the pre-discharge alarm.
3. Individual circuits may remain unused or may include
additional devices, depending on actual requirements. Unused
circuits must be fitted with an End-of-Line Device or Blanking
Plug, as appropriate.

Figure 3-11. Electric Automatic/Manual Suppression Actuation


with Single Release Suppression

April 2022 3-16 P/N 83-132550-000


System Design

Fuse at

Into SA1
Battery
Inline fuse
supplied
by others

~~
Vehicle Power
(Battery)

REL-1
AR-1

SUP
MR
DET-1
To Engine
shutdown,
etc.
AUTOMATIC DETECTION
Maintenance
Bypass Switch
Detect-A-Fire Detector

EOL
Device

IR-1A Detector EOL


Device

Control Heads and Valves

SUPPRESSION SYSTEM
1/4-in. Actuation
Hose

NOTES:
SENTINEL SA1 CONFIGURATION 1. AUTOMATIC OPERATION: An alarm signaled by an
automatic fire detector will result in electrical actuation of a
Feature Setting Remote System Actuator following a programmed delay. The
Manual Release Type Pneumatic actuator will provide immediate pneumatic actuation of each
suppression cylinder. The Override function may be used
Release Delay Time Per requirements during the pre-discharge alarm.
Relays Per requirements 2. MANUAL OPERATION: Operation of a pneumatic
manual release station will result in direct, immediate,
pneumatic actuation of each suppression cylinder and the
Discharge Monitor Switch. Upon activation, the Discharge
Monitor Switch will provide a signal to the control panel, which
will activate the relay, but not the release circuit.
3. Individual circuits may remain unused or may include
additional devices, depending on actual requirements.

Figure 3-12. Pneumatic Automatic and Manual Suppression Actuation


with Single Release Suppression

P/N 83-132550-000 3-17 April 2022


System Design

Fuse at

Into SA1
Battery
Inline fuse
supplied
by others

~~
Vehicle Power

REL-1
AR-1

SUP
MR
(Battery)

DET-1
To Engine
shutdown,
etc.
AUTOMATIC DETECTION
Maintenance
Bypass Switch
Detect-A-Fire Detector

EOL
Device

IR-1A Detector

EOL
Device

SECOND SHOT Second-Shot Second-Shot FIRST SHOT


Delay Actuator
SUPPRESSION SUPPRESSION
1/4-in. Actuation
Hose

pneumatic actuation of the secondary suppression cylinders.


SENTINEL SA1 CONFIGURATION The Override function may be used during the pre-discharge
alarm.
Feature Setting 2. MANUAL OPERATION: Operation of a pneumatic
Manual Release Type Pneumatic manual release station will result in direct, immediate,
pneumatic actuation of the primary suppression cylinders, the
Release Delay Time Per requirements Discharge Monitor Switch, and the Second-Shot Actuator.
Relay Per requirements Upon activation, the Discharge Monitor Switch will provide a
signal to the control panel, which will activate the relay, but
NOTES: not the release circuit. After a delay, the Second-Shot Actuator
1. AUTOMATIC OPERATION: An alarm signaled by an will provide direct, pneumatic actuation of the secondary
automatic fire detector will result in electrical actuation of a suppression cylinders.
Remote System Actuator following a programmed delay. The 3. Individual circuits may remain unused or may include
actuator will provide immediate pneumatic actuation of the additional devices, depending on actual requirements. Unused
primary suppression cylinders and the Second-Shot Actuator. circuits must be fitted with an End-of-Line Device or Blanking
After a delay, the Second-Shot Actuator will provide direct, Plug, as appropriate.

Figure 3-13. Pneumatic Automatic and Manual Suppression Actuation


with Dual Release Suppression

April 2022 3-18 P/N 83-132550-000


System Design

Into SA1
Fuse at
Battery
Inline fuse
supplied
by others

~~
Vehicle Power
(Battery)

REL-1
AR-1

SUP
MR
DET-1
To Engine
shutdown, Not Used. (Plug)
etc.
AUTOMATIC DETECTION

Detect-A-Fire Detector

EOL
Device

IR-1A Detector

MANUAL ACTUATION EOL


Device

1/4-in. Actuation
Hose Control Heads and Valves

SUPPRESSION SYSTEM

NOTES:
SENTINEL SA1 CONFIGURATION 1. AUTOMATIC OPERATION: An alarm signaled by an
automatic fire detector will activate the relay, but will not
Feature Setting result in actuation of the suppression system.
Manual Release Type Pneumatic 2. MANUAL OPERATION: Operation of a pneumatic
Release Delay Time N/A manual release station will result in direct, immediate,
pneumatic actuation of each suppression cylinder and the
Relay Per requirements Discharge Monitor Switch. Upon activation, the Discharge
Monitor Switch will provide a signal to the control panel, which
will activate the relay, but not the release circuit.
3. Individual circuits may remain unused or may include
additional devices, depending on actual requirements. Unused
circuits must be fitted with an End-of-Line Device or Blanking
Plug, as appropriate.

Figure 3-14. Automatic Alarm-Only and Pneumatic Manual Suppression Actuation


with Single Release Suppression

P/N 83-132550-000 3-19 April 2022


System Design

Into SA1
Fuse at
Battery
Inline fuse
supplied
by others

~~
Vehicle Power
(Battery)

REL-1
SUP
MR
AR-1

DET-1
To Engine
shutdown, Not Used. (Plug)
etc.
AUTOMATIC DETECTION

Detect-A-Fire Detector

EOL
Device
MANUAL
IR-1A Detector ACTUATION

EOL
Device

SECOND SHOT Second-Shot Second-Shot FIRST SHOT


Delay Actuator
SUPPRESSION SUPPRESSION
1/4-in. Actuation
Hose

NOTES:
SENTINEL SA1 CONFIGURATION 1. AUTOMATIC OPERATION: An alarm signaled by an
automatic fire detector will activate the relay, but will not
Feature Setting result in actuation of the suppression system.
Manual Release Type Pneumatic 2. MANUAL OPERATION: Operation of a pneumatic
Release Delay Time N/A manual release station will result in direct, immediate,
pneumatic actuation of the primary suppression cylinders, the
Relay Per requirements Discharge Monitor Switch, and the Second-Shot Actuator.
Upon activation, the Discharge monitor Switch will provide a
signal to the control panel, which will activate the relay, but
not the release circuit. After a delay, the Second-Shot
Actuator will provide direct, pneumatic actuation of the
secondary suppression cylinders.
3. Individual circuits may remain unused or may include
additional devices, depending on actual requirements. Unused
circuits must be fitted with an End-of-Line Device or Blanking
Plug, as appropriate.

Figure 3-15. Automatic Alarm-Only and Pneumatic Manual Suppression Actuation

April 2022 3-20 P/N 83-132550-000


Installation

CHAPTER 4
INSTALLATION

4-1 INTRODUCTION

This chapter is intended for system installers and outlines the installation of the Envirotech®
Sentinel® SA1 System.

4-2 GENERAL ORDER OF INSTALLATION

The following order of installation is recommended, and detailed instructions for each of the
following sections is provided in this chapter:

1. Mount the Envirotech Sentinel SA1 Control (Sentinel SA1).


2. Mount all detectors.
3. Mount all other ancillary devices.
4. Run all cables.
5. Mount all cables.
6. Power up the system to verify that it’s working properly, then power it down.

4-3 GENERAL INSTALLATION REQUIREMENTS

All Envirotech Sentinel SA1 System equipment must be installed to facilitate proper inspection,
testing, manual operation, recharging and any other required maintenance as may be
necessary. Equipment must not be subject to severe weather conditions beyond its ratings or
mechanical, chemical, or other damage, which could render the equipment inoperative.
Equipment must be installed in accordance with applicable NFPA Standards and vehicle
regulations.

4-4 SUPPRESSION SYSTEM INSTALLATION

The suppression system installation is covered in the applicable suppression system manual
listed in the following table:

Table 4-1. Envirotech Sentinel System Manuals

Component Names Manual Names

Envirotech Sentinel LS Envirotech Sentinel LS Fire Suppression System DIOM


(P/N 83-130550-000)
Envirotech Sentinel DCS Envirotech Sentinel DCS Fire Suppression System
DIOM (P/N 83-131550-000)

Ensure that all cylinders have their control heads removed while installing the
CAUTION Envirotech Sentinel SA1 system.

P/N 83-132550-000 4-1 April 2022


Installation

4-5 MOUNT THE ENVIROTECH SENTINEL SA1 ELECTRONIC MODULE

The Sentinel SA1 should be mounted in or near the vehicle’s control cabin, to provide direct
access to the user interface. The LEDs should be visible to the vehicle operator.

4-5.1 Installation of the Sentinel SA1

To install the Sentinel SA1:


1. Mark the location on the mounting surface, and position the template onto the appropriate
mounting location. Ensure that the mounting hole locations on the template are level.
Note: Mounting hardware is not included.
2. Select mounting hardware that is suitable for the application, based on the weight of the
unit and the environment.
3. Drill the appropriate-sized holes required for the chosen mounting hardware.
4. Remove the front cover of the module:
a. Loosen the four (4) captive cover screws, using a Phillips head screwdriver and
Remove the cover.
b. Disconnect the front cover cable from the main board (see Figure 4-1).
5. Place the unit onto the prepared mounting area. Ensure that the top of the module is in the
correct orientation.
6. Using the mounting hardware, fasten the module to the mounting surface of the vehicle.
7. Install the Primary Cell or Power Supply Board.
a. If the Primary Cell is used:
i. Mark the installation date onto the label provided on the Primary Cell.
ii. Mount the Primary Cell on the four standoffs, using the supplied 6-32 screws.
iii. Connect the battery cable to the main board.
b. If the Power Supply Board is used:
i. Mount the Power Supply Board on the four standoffs, using the 6-32 screws.
ii. Connect the power supply cable to the main board.
iii. If the Rechargeable Battery is used, mount the battery on the Power Supply
Board using the supplied 6-32 screws and connect the battery cable to the
Power Supply Board.
8. Replace the front cover of the module:
a. Reconnect the front cover cable to the main board.
b. Place the cover onto the module. Using a Phillips-head screwdriver, tighten the four
(4) front captive cover screws, making sure that the screws are fully fastened down.

April 2022 4-2 P/N 83-132550-000


Installation

Figure 4-1. Sentinel SA1 Installation

4-5.2 Installing the Mounting Bracket for SA1 Control Module with RSA, P/N 83-130034-
400

The bracket is formed from a rugged 3/16” plate with a durable powder coat finish. By using the 3/8” diameter
mounting holes, the bracket may be supported either from the top, bottom or side. When side mounted, the
bracket can be oriented for either left or right-hand operation of the RSA. The bracket includes four fasteners
to ensure properly affixing the SA1 to it.

1.88 in.
(3.02 cm)
9.188 in. (23.39 cm)

Three (3)
mounting
holes for P/N
83-132530-000.
Use when
mounting lip
is on the 7.750 in.
right of the Four (4) x 8-32 standoffs
(19.69 cm) Mounting lip
SA1 unit. with three (3)
(Four (4) x 8-32 x 1 in. screws
0.281 diameter
are included for mounting SA1)
holes
Same as
above, but
when
mounting
lip is on the
left of the
SA1 unit.

Six (6) x 0.281 diameter


FRONT VIEW holes for mounting SIDE VIEW

Figure 4-2. Mounting Bracket, P/N 83-130034-400

P/N 83-132550-000 4-3 April 2022


Installation

3.60 in.
(9.14 cm)

13.25 in.
(33.65 cm)

FRONT VIEW - oriented with lip on left FRONT VIEW - oriented with lip on right SIDE VIEW

Figure 4-3. 83-130034-400 Clearance Requirements

4-6 MOUNT ALL DETECTION COMPONENTS

4-6.1 Install the Detect-A-Fire®, P/N 83-132440-XXX

4-6.1.1 BEFORE BEGINNING

Detect-A-Fire (DAF) units can be mounted either horizontally or vertically, depending on the
application and installation requirements. If mounted horizontally, the DAF is position-
sensitive. The DAF uses the Fenwal logo stamped on the hex head as an “indicator” of the
internal contact orientation.

When mounted in any position other than vertical, the “FENWAL” logo must
CAUTION face directly up or down. Otherwise, the unit may not function properly.

Note:
1. Do not install the unit where the shell would be physically damaged
by debris, rocks, etc.
2. Detectors mounted in an area subject to physical abuse must be
suitably protected without obstructing the thermal air path to the
unit.

There is risk of damage to the unit if it is over-tightened.


CAUTION

3. In order to function properly, the sensing shell of the unit must remain free from paint,
grease, oil, etc. Should such a buildup occur, do not—under any circumstances—
attempt to remove the buildup. Replace the unit.
4. Any detector that has been abused or damaged must be replaced.

April 2022 4-4 P/N 83-132550-000


Installation

Any of the above could change the factory temperature setting, which may
result in property damage, serious personal injury, or death. It is possible for a
unit to have been abused or damaged without displaying any outward
WARNING indications. All units should be tested periodically with NFPA (72) and/or
Authority Having Jurisdiction (AHJ).

4-6.1.2 INSTALLATION PROCEDURE


1. Select the area to mount the bracket.
2. Clean the area and mount the bracket. The bracket may be welded into place.
Note: Do not weld, braze, or apply heat to the mounting bracket while
the DAF is connected to the bracket.
3. Loosely affix the DAF unit to the clamp using the retaining nut.

If horizontally mounted, the Fenwal logo stamped on the hex head must face
CAUTION directly up or down. Otherwise, the unit will not function properly.

Note: If horizontally mounted, ensure that the Fenwal logo stamped on


the hex head is facing upwards.
4. Tighten the locking nut.

4-6.2 Install the Linear Heat Sensing Cable, P/N 83-100003-001

The LHS is a fusible cable and should be installed close to potential sources of fire. The cable
is capable of sensing a fire at any point along its length.

The system is usually configured with one cable of the appropriate length installed within the
concerned risk area. An additional LHS may be added in series for added protection. The length
of the cable should be long enough to cover the hazard area but not excessively long to reduce
its susceptibility to damage. The cable should be mounted high in the protected area above
potential fire sources. Physical contact with heat absorbent surfaces and mounting in an area
of high airflow should be avoided as much as possible. The detection wire should not be
installed within 12 inches of engine exhaust components and should not be pinched, crimped
or kinked during the installation process.

In an engine compartment, the cable should be mounted on the compartment roof around the
perimeter or in a sine wave pattern--whichever allows for greater coverage and ease of
installation. In other areas such as roof mounted fuel tanks where the cable cannot be mounted
to the roof, it should be mounted above the tank valves using appropriate bracketry. Care
should be taken to avoid installing near moving parts or in the way of maintenance personnel.
In areas where maintenance work is regularly performed or more support is required,
mounting clip spacing should be reduced.

The LHS should be mounted using rubber insulated mounting clips at approximately 2-foot
intervals (see Figure 4-4) and the wire should not be allowed to droop between mounting
points. The clips should be able to hold a wire 3/16-inch diameter without pinching and hold
the wire away from heat-absorbing surfaces.

LHS CABLE

Figure 4-4. LHS Mounting Clips

P/N 83-132550-000 4-5 April 2022


Installation

4-6.2.1 INSTALL THE LHS BASE, P/N 83-132454-000

To install the LHS Base:

1. Locate a suitable mounting location for the LHS Base.


2. Remove the cover of the LHS Base:
a. Loosen the four (4) captive cover screws, using a Phillips head screwdriver.
b. Remove the cover.
3. Mark the location of the four (4) mounting holes.
Note: Mounting hardware is not included.
4. Select mounting hardware that is suitable for the application, based on the weight of the
LHS Base and the environment.
5. Drill the appropriate-sized holes required for the chosen mounting hardware.
6. Place the LHS Base onto the prepared mounting area. Ensure that the top of the LHS Base
is in the correct orientation.
7. Using the mounting hardware, fasten the LHS Base to the mounting surface.
8. Loosen the outer nut of the waterproof seal on both sides of the LHS Base.
9. Insert the LHS Cable through the two seals.
10. Attach each end of the LHS Cable to a terminal.
Leave alone the two pre-wired connectors on either side of the LHS Base.
11. Tighten the outer nuts of the two seals.
12. Replace the front cover of the LHS Base by tightening the four (4) cover screws, making
sure that the screws are fully fastened down.

Figure 4-5. LHS Base

April 2022 4-6 P/N 83-132550-000


Installation

4-6.3 Install the IR-1A Flame Detector, P/N 83-132450-000, 83-132700-000 and
Infrared Flame Detector Bracket, P/N 83-131060-001

To install the IR-1A Flame Detector and Bracket:

1. Locate a suitable mounting location for the IR-1 Flame Detector Bracket.
2. Refer to Figure 4-6 and Figure 4-9 for locating the mounting holes and assembling the
bracket and detector.
3. Refer to Figure 4-7 and Table 4-2 to determine the sensor orientation.

2-53/64 in.
(72 mm)
11/64 in.
(4 mm) TYP

11/64 in. +.010


TYP
(4 mm) -.000
2-1/2 in.
(64 mm)
1-1/4 in.
(32 mm)

25/32 in. Ø 3/8 in. HOLE


(18 mm)
TYP

1-13/32 in.
1-11/32 in. (35 mm)
(34 mm)

Figure 4-6. Mounting Holes for the IR-1 Mounting Bracket, P/N 83-132060-001

100°
CONE

½X

DETECTOR

Figure 4-7. IR-1A Sensor Orientation

P/N 83-132550-000 4-7 April 2022


Installation

Table 4-2. IR-1A Sensor Orientation (Reference Figure 4-7)

Fuel X (in.)

Methanol 36
Gasoline 42
Diesel 42
Methane 20
Hydrogen 12

3.50 in. 4-29/32


(89 mm) (125 mm)
3.00 in. 1-11/64
(76 mm) (30 mm)

1.3 in.
(33 mm)
2.50 in. 2-1/2 in.
(64 mm) (64 mm)
DIA .2 in x 2

5.50 in.
(140 mm)

Figure 4-8. IR-1A Optical Flame Detector with Mounting Bracket Attached

{
5/16-18
LOCKNUT

}
2 SETS 5/16 WASHER BOTTOM MOUNTING BRACKET
OF
HARDWARE
7/8 x 5/16-18
BOLT 1-1/4 x 8-32
SCREW

#8 FENDER
WASHER

2 SETS
OF
TOP MOUNTING BRACKET HARDWARE

#8 WASHER
IR-1 DETECTOR
P/N 83-132001-001 8-32 LOCKNUT

Figure 4-9. Assembly of the IR-1 Mounting Bracket, P/N 83-131060-001

April 2022 4-8 P/N 83-132550-000


Installation

4-7 INSTALL PNEUMATIC ACTUATION COMPONENTS

4-7.1 Equipment Location

4-7.1.1 ACTUATORS

The mechanical actuator can be located either inside or outside the vehicle in any accessible,
convenient location away from hazards. The remote system actuator must be located inside
the vehicle in a protected location.

4-7.2 Pneumatic Actuation Components

The pneumatic actuation components include:

1. 15-in3 Nitrogen Cartridge, P/N WK-878508-000


2. Mechanical Actuator, P/N 83-897392-000
3. Mechanical Actuator Brackets:
a. Indoor Bracket (Short), P/N 83-844726-000
b. Outdoor Bracket (Long), P/N 83-844725-000
4. Remote System Actuator, P/N 83-132514-000
5. Remote System Actuator Bracket, P/N 83-132530-000
6. Second-Shot Hardware
a. Second-Shot Actuator, P/N 83-132520-000
b. Second-Shot Actuator Bracket, P/N 83-132531-000
c. Second-Shot Delay, P/N 83-132524-000
d. Second-Shot Delay Bracket, P/N 83-132535-000
e. Flex Hose Assembly, P/N 87-120045-001
7. Check Valve, P/N WK-259404-000
8. Vent Check (Optional), P/N WK-877810-000
9. Actuation Monitor Switch (i.e., Pressure Switch), P/N 42-990132-510

4-7.3 Install the Mechanical Actuator, P/N 83-897392-000

Make sure actuator knobs are in set position with safety pin installed and seal
CAUTION wire intact.

Do not remove cartridge from the actuator. Bodily injury may result if the
WARNING actuator is energized without the cartridge in place.

Do not install the nitrogen cartridge at this time. Doing so could cause
WARNING equipment damage, personal injury, or unwanted discharge.

1. Install the appropriate brackets to mount the mechanical actuator: either the Indoor
Nitrogen Bracket (Short), P/N 83-844726-000 or the Outdoor Nitrogen Bracket (Long), P/N
83-844725-000. These brackets are provided with mounting holes. Bolt or weld brackets
in place. Paint bare metal as required.
2. Assemble actuator assembly to bracket.

P/N 83-132550-000 4-9 April 2022


Installation

Figure 4-10. Nitrogen Cartridge and Mechanical Actuator Shown in Indoor Bracket

Figure 4-11. Nitrogen Cartridge and Mechanical Actuator Shown in Outdoor Bracket

April 2022 4-10 P/N 83-132550-000


Installation

4-7.4 Install the Remote System Actuator Bracket, P/N 83-132530-000

To install the Remote System Actuator (RSA) Bracket:

1. Locate a suitable mounting location for the RSA Bracket.


Note: The RSA Bracket can be installed with either a left or right outlet.
2. Mark the location of the three (3) mounting holes.
Note: Mounting hardware is not included.
3. Select mounting hardware that is suitable for the application, based on the weight of the
Remote System Actuator and the environment.
4. Drill the appropriate-sized holes required for the chosen mounting hardware.
5. Using the mounting hardware, fasten the RSA bracket to the mounting surface.

4-7.5 Install the Remote System Actuator, P/N 83-132514-000

To install the Remote System Actuator (RSA):

1. Use three (3) 10-32 screws to mount the RSA to the RSA Bracket.
2. Fasten the Protractor’s cable clip to the single-screw side of the RSA Bracket, using the
longest screw.

Figure 4-12. Remote System Actuator, Remote System Actuator Bracket,


and Cartridge

Note: Use lock washers on the double-screw side of the RSA Bracket,
and a standard flat washer on the single-screw side.

P/N 83-132550-000 4-11 April 2022


Installation

4-7.6 Install the Second-Shot Actuator Bracket, P/N 83-132531-000

To install the Second-Shot Actuator Bracket:

1. Locate a suitable mounting location for the Second-Shot Actuator Bracket.


2. Refer to Figure 2-32 in Chapter 2 (Second-Shot Actuator Bracket, P/N 83-132531-000) for
mounting hole locations.
3. Mark the location of the four (4) Bracket mounting holes.
Notes:
a. Mounting hardware is not included.
b. Be sure that mounting location can accommodate Second-Shot
Actuator and Second-Shot Delay.
4. Select mounting hardware that is suitable for the application, based on the weight of the
Second-Shot Actuator and the environment.
5. Drill the appropriate-sized holes required for the chosen mounting hardware.
6. Using the mounting hardware, fasten the Second-Shot Actuator Bracket to the mounting
surface.

4-7.7 Install the Second-Shot Actuator, P/N 83-132520-000

To install the Second-Shot Actuator:

1. Mount the Second-Shot Actuator to its Bracket, using two (2) pan-head screws.
2. Tighten the nut on the actuation hose adapter, located at the top of the Second-Shot
Actuator.
3. Mount the cover using four (4) pan-head screws with lock washers. Refer to Figure 2-32 in
Chapter 2 (Second-Shot Actuator Bracket, P/N 83-132531-000) for mounting hole
locations.

Figure 4-13. Second-Shot Actuator, Second-Shot Actuator Bracket,


and Cartridge

April 2022 4-12 P/N 83-132550-000


Installation

4-7.8 Install the Second-Shot Delay, P/N 83-132524-000 and Second-Shot Delay Bracket,
P/N 83-132535-000

To install the Second-Shot Delay and Second-Shot Delay Bracket:

1. Mount the Bracket to the body of the Delay with the two (2) socket-head cap screws.
2. Torque the screws to 144 in-lbs.
3. Locate a suitable mounting location for the Second-Shot Delay Bracket. Ensure that the
Flex Hose, P/N 87-120045-001, can be installed from the actuator outlet to the Second-
Shot Delay inlet.
4. Mark the location of the two (2) mounting holes.
Note: Mounting hardware is not included.
5. Select mounting hardware that is suitable for the application, based on the weight of the
Second-Shot Delay and the environment.
6. Drill the appropriate-sized holes required for the chosen mounting hardware.
7. Using the mounting hardware, fasten the Second-Shot Delay Bracket, attached to the
Second-Shot Delay, to the mounting surface.
8. Install the Flex Hose, P/N 87-120045-001, from the actuator outlet to the Second-Shot
Delay inlet.

Figure 4-14. Second-Shot Delay, Second-Shot Delay Bracket, and Cartridge

4-7.9 Install the 1/4-Inch Actuation Hose

To install the 1/4-inch Actuation Hose:

1. Utilize the hose as specified in Section 3-4.2.2, Pneumatic Actuation System.


2. Ensure that all adapters and fittings are accounted for, where connections are necessary.
Ensure that all connections are wrench-tight and free of leaks.
3. Ensure that the hose is properly secured to the vehicle using clamps, to limit unnecessary
movement or vibrations in the hose.
4. Install the hose according to the limits specified in Section 3-4.2.2, Pneumatic Actuation
System.

Actuation hose shall not run through protected spaces. Where it is necessary to
route the actuation line through the protected space, tubing or pipe of
WARNING equivalent diameter and pressure rating shall be used.

When multiple actuators are used, the actuators shall not share a common line.
WARNING Tees shall occur at the actuated valve.

5. After installing the hose, the actuation system must be pressure tested to ensure that the
system is free of leaks.

P/N 83-132550-000 4-13 April 2022


Installation

4-7.10 Install the Check Valve, P/N WK-259404-000

To install the Check Valve:

1. Mate the threaded connections and ensure that the arrow points in the direction of flow.
2. Ensure that the Check Valve is secure.

4-7.11 Install the Vent Check, P/N WK-877810-000

To install the Vent Check:

Attach the Vent Check anywhere on the pneumatic line. If several pneumatic system valve
actuators are used, connect with 1/4-inch hose and install the vent check in the last actuator
in the series, or located downstream of all check valves.

1/8 NPT

Figure 4-15. Vent Check

4-7.12 Install the Actuation Monitor Switch (i.e., Pressure Switch), P/N 42-990132-510

To install the Actuation Monitor Switch:

1. Install the Actuation Monitor Switch anywhere on the pneumatic line that meets the
following two conditions for location:
– in a location where the Actuation Monitor Switch may be affected by the actuator(s)
– in a location where the Actuation Monitor Switch may be as remote as possible from
the actuator(s)

April 2022 4-14 P/N 83-132550-000


Installation

4-8 INSTALL ELECTRIC ACTUATION COMPONENTS

4-8.1 Mount the Maintenance Bypass Switch, P/N 83-132483-500

The Maintenance Bypass Switch is designed to bypass two release circuits and shall be located
electrically between the control panel and the first Protractor.

Install the Maintenance Bypass Switch as follows:

1. Select a suitable location.


2. Install the Maintenance Bypass Switch, using four (4) #8 screws of suitable length and
type. Refer to Figure 4-18 for dimension details.
3. Ensure that the Maintenance Bypass Switch is in the Bypass state.
4. Connect the Maintenance Bypass Switch to the control panel, and then to the release
circuit.
5. Place the Maintenance Bypass Switch in the Active state.
Notes:
1. The Maintenance Bypass Switch key may be removed in either
position: Active (armed) or Bypass (off-line).
2. The maximum total length of the Releasing Loop through the
Maintenance Bypass Switch is 500 ft.
3. The Maintenance Switch is not supervised for shorts. It is
supervised for opens.

4-8.2 Install the Protractor Assembly to the Control Head, P/N 83-132500-500

To install the Protractor on the control head:

1. Remove the top plug on the control head.


2. Apply RTV silicon sealant to the new Protractor threads, and hand tighten into control head.
3. Insert the Protractor through the grommet at the top of the gauge shield and thread into
the pneumatic/electric control head (P/N 83-132500-500). Hand tighten.
4. Place a cable clamp on the Protractor cable. The clamp will be fastened to the control head
using the control head mounting bolts.
Note: If connecting to one cylinder only, connect the Release I/O cable
to the connector of the Protractor assembly. For connecting
multiple cylinders, see Section 4-8.3 (next paragraph).

P/N 83-132550-000 4-15 April 2022


Installation

Figure 4-16. Protractor Assembly with Control Head

Last Electric
Into SA1

Release Actuator
Cable Assembly

REL-1
AR-1

SUP
MR

DET-1

Figure 4-17. Protractor with Control Head

April 2022 4-16 P/N 83-132550-000


Installation

4-8.3 Install the Release In-Line Connector, P/N 83-132487-300

The Release In-Line Connector is needed for the use of two (2) or more suppression cylinders.
No EOL device is required at the end of the circuit. The Release In-Line Connector connects
directly to the Protractor or next Release In-Line Connector.

Note: The maximum number of Protractors that can be connected per


Sentinel SA1 is three (3).

Last Electric
Release In-Line In-Line Actuator
Into SA1

Cable Connector Connector Assembly

REL-1
AR-1
MR

SUP
DET-1

Electric Electric
Actuator Actuator
Assembly Assembly

Figure 4-18. Release In-Line Connector—Usage

4-8.4 Install the Black Release Circuit Shorting Plug, P/N 83-132487-500

If the Black Release Circuit on the Sentinel SA1 is not used, a shorting plug must be installed
in the unused Release receptacle.

4-8.5 Install the Electric Manual Release, P/N 83-132455-000

To install the Electric Manual Release (EMR):

1. Locate a suitable mounting location for the EMR.


2. Mark the location of the two (2) mounting holes.
Note: Mounting hardware is not included. Suggested hardware is #10
screws.
3. Select mounting hardware that is suitable for the application, based on the weight of the
EMR and the environment.
4. Drill the appropriate-sized holes required for the chosen mounting hardware.
5. Place the EMR onto the prepared mounting area. Ensure that the top of the EMR is in the
correct orientation.
6. Using the mounting hardware, fasten the EMR to the mounting surface.
7. Tighten the two (2) screws, making sure that the screws are fully fastened down.

P/N 83-132550-000 4-17 April 2022


Installation

4-9 MOUNT ALL CABLES

Careful measurements of the distances between the module, detectors, and all
ancillary devices must be taken, so that accurate lengths of cables and splitters
CAUTION may be incorporated into the system.

Note: The only cables whose lengths are modifiable are:


• Power (P/N 83-132481-XXX)
• Relay (P/N 83-132485-0XX)

4-9.1 Cable Connections

For ease of installation, the Envirotech Sentinel SA1 system has been designed with a number
of plug-in cables, splitters, and end-of-line devices.

Note:
1. The Sentinel SA1 must be powered by a dedicated circuit that is
typically energized with the vehicle’s ignition (except when powered
by the Primary Cell Battery).
2. A variety of custom cable lengths can be daisy-chained, using the
referenced table (see Table 4-3) for each cable.
3. Identification labels are provided for troubleshooting and
maintenance. They wrap around the outside diameter of the cable
near both ends of the connectors.

4-9.2 Required Splitters and End-of-Line Devices

Table 4-3 shows the splitters and end-of-line devices required for use with each cable.

Ensure that the I/O cables are labeled with the correct labels.
CAUTION

4-9.3 Connect the Envirotech Sentinel SA1 System


Note: See Appendix B for a specific example of how to connect the
system.
Note: The cable that connects the Supervisory, Manual Release
(Activation), and Agent Release circuit from the Sentinel SA1 to
its respective switch, release, or actuator is called the Two-Wire
I/O Cable. It is P/N 83-132483-0XX. See Table 4-3, which shows
which cables to use to connect the Sentinel SA1 circuits.

April 2022 4-18 P/N 83-132550-000


Installation

Table 4-3. Circuit and Cable Identification

Cable End-of-Line Device


Circuit
(Part Number) (Part Number)

Sentinel SA1
VEHICLE POWER Vehicle Power Cable (used with vehicle Power Circuit Blanking Plug (used with
power) the Primary Cell Battery)
(P/N 83-132481-XXX) (P/N 83-132487-800)
See Table 2-9

Distribution Cable (optional) N/A


(P/N 83-132486-0XX)

SA1 Splitter
P/N 83-132486-500
REL-1

SUP

Into SA1 MR

DET-1

AR-1

SUPERVISORY Two-Wire I/O Cable Grey Two-Wire I/O End-Of-Line Device


(P/N 83-132483-0XX) (P/N 83-132487-200) onto the last pressure
See Table 2-11 switch
of the circuit

MANUAL RELEASE Two-Wire I/O Cable Grey Two-Wire I/O End-Of-Line Device
(P/N 83-132483-0XX) (P/N 83-132487-200) onto the last device
See Table 2-11 (electric manual release or AMS) of the
circuit

DETECTION Detection Cable Detection End-Of-Line Device


(P/N 83-132482-0XX) (P/N 83-132487-100)
See Table 2-10

P/N 83-132550-000 4-19 April 2022


Installation

Table 4-3. Circuit and Cable Identification (Continued)

Cable End-of-Line Device


Circuit
(Part Number) (Part Number)

RELEASE Two-Wire I/O Cable Black Releasing Circuit Shorting Plug


(P/N 83-132483-0XX) (Connect to Protractor (P/N 83-132487-500) onto the last
on cylinder valve, using In-Line Connector Protractor of the circuit
Release,
P/N 83-132487-300)
See Table 2-11

ALARM RELAY Relay Cable Relay Circuit Blanking Plug (if the circuit is
(P/N 83-132485-0XX) not used)
See Table 2-13 (P/N 83-132487-600)

Note: No connector on the Envirotech Sentinel SA1 system should be


left open. Use the appropriate plug or EOL Device, as shown in
Table 4-3. The End-of-Line Devices and Plugs shown in Table 4-3
are part of the SA1 Kit, P/N 06-236947-001.

4-9.3.1 CONNECTING THE ENVIROTECH SENTINEL SA1 SYSTEM

To connect the Envirotech Sentinel SA1 system:

1. Connect the Vehicle Power Cable to the Sentinel SA1, with the following steps:
a. Connect the Vehicle Power Cable (P/N 83-132481-0XX) into the Vehicle Power
connection of the Sentinel SA1.
Note: The other end of the Vehicle Power Cable connects to
the ignition through an in-line, slow-blow fuse, not
supplied or installed at this time.
2. Connect the SA1 Splitter, P/N 83-132486-500, to the Sentinel SA1.
3. Connect the Two-Wire I/O Cable (P/N 83-132483-0XX) from the Supervisory Circuit
on the SA1 Splitter:
a. Connect the Two-Wire I/O Cable from the Sentinel SA1 Splitter to the pressure
switch located on the cylinder valve.
Note: Additional cables are not required to daisy-chain
between adjacent cylinders, provided the cylinders
are located next to each other.
b. Install an End-of-Line (EOL) resistor (P/N 83-132487-200) onto the last pressure
switch of the circuit.
4. Connect the Two-Wire I/O Cable (P/N 83-132483-0XX) from the Manual Release
(Activation) Circuit on the SA1 Splitter:
a. Connect the Two-Wire I/O Cable from the Sentinel SA1 Splitter to the Electric
Manual Release.
b. Install an End-of-Line (EOL) resistor (P/N 83-132487-200) onto the last Electric
Manual Release of the circuit.
5. Connect the Detection Cable (P/N 83-132482-0XX) from the Detection Circuit on the
SA1 Splitter:

April 2022 4-20 P/N 83-132550-000


Installation

a. Connect the Detection Cable (P/N 83-132482-0XX) from the Sentinel SA1 Splitter
to the Detection device(s).
b. Install an End-of-Line (EOL) resistor (P/N 83-132487-100) onto the last detection
device of the circuit.
6. Connect the Two-Wire I/O Cable (P/N 83-132483-0XX) from the Agent Release
Circuit on the SA1 Splitter:
a. Connect the Two-Wire I/O Cable from the Sentinel SA1 Splitter to the Protractor
located on the cylinder valve, using the In-Line Connector Release, P/N 83-132487-
300.
b. Install a Black Release Circuit Shorting Plug (P/N 83-132487-500) onto the last
Protractor of the circuit.
Note: Additional cables are not required to daisy-chain
between adjacent cylinders, provided the cylinders
are located next to each other.
7. Connect the Alarm Relay Cable (P/N 83-132485-0XX) from the Alarm Relay Circuit on
the SA1 Splitter:
a. Connect the Alarm Relay Cable from the Sentinel SA1 Splitter to the Engine
Shutdown and other equipment, such as fans or hydraulic pumps, that are
determined to be de-energized when a fire condition is detected.
Note: Plug the Relay Circuit on the SA1 Splitter with the
Relay Circuit Blanking Plug (P/N 83-132487-600) if
not using the Relay Circuit.

4-9.4 Before Powering Up

Before powering up:

1. Install the fuse holder for the slow blow 10 Amp, 250V In-line fuse to the positive lead of
the power cable.
Note: This fuse holder should be at the power source, and be positioned
between the vehicle and the equipment, in order to protect the
wiring.
2. Place a slow blow 10 Amp, 250V in-line fuse (provided by installer) into the fuse holder.

4-9.5 Powering Up

Verify that the system powers up. Depending on the configuration, the system could take up
to two minutes to initialize.

Once initialized, the Sentinel SA1 will display “Normal,” and the power LEDs (green lights) will
be steadily-lit. All other LEDs will be OFF.

P/N 83-132550-000 4-21 April 2022


Installation

4-10 COMMISSIONING AND TESTING THE ENVIROTECH SENTINEL SA1 SYSTEM

The Envirotech Sentinel SA1 System must be commissioned and tested prior to being put into
service. Refer to Section 7-5.2, Commissioning and Testing the Envirotech Sentinel SA1
System.

4-10.1 Personnel Training

All persons who could be expected to inspect, maintain or operate the system shall be
thoroughly trained in the functions they are expected to perform. All personnel working in the
protected space shall receive training regarding agent safety issues.

4-10.2 Arming the System

Upon completion of the Discharge Network Testing, Actuation Testing, Sentinel SA1 Testing
and Personnel Training, the following procedure shall be performed to arm the system.
1. Verify that the Electric and Pressure Control Head is in the set position.
2. Install the Electric and Pressure Control Head on the Cylinder Valve Assembly.
3. Install a nitrogen cartridge on each actuator.

Securing the Electric and Pressure Control head on the Cylinder will complete
the system setup. System discharge could occur if the system has not been
CAUTION properly installed or configured.

4-10.3 System Documentation

Prior to acceptance of the system, technical documentation shall be supplied to the vehicle
owner and authority having jurisdiction. This documentation shall include the following:
• System owner’s manual (P/N 83-132551-000)
• Written and signed report of the system commissioning

The authority having jurisdiction may also require a copy of this manual,
(P/N 83-132550-000).

April 2022 4-22 P/N 83-132550-000


Configuring the Envirotech Sentinel SA1 System

CHAPTER 5
CONFIGURING THE ENVIROTECH SENTINEL SA1
SYSTEM
5-1 INTRODUCTION

This chapter describes how to configure the Envirotech® Sentinel® SA1 System. The
Envirotech Sentinel SA1 System (“Sentinel SA1”) is configured through the user interface.

As shown in the following illustration and table, the Sentinel SA1 User Interface Buttons are
referred to in this chapter as B1, B2, and B3.

B2
B3

B1 Increment
(Scroll up)

<Enter> or cycle
Decrement through parameters
(Scroll down)

Figure 5-1. Sentinel SA1 User Interface Buttons Nomenclature

P/N 83-132550-000 5-1 April 2022

You might also like