BS5839 A person searching a zone for a fire in a non-addressable fire system should
Section 13.2.3 not have to travel for more than 60m to identify the source of a fire.
BS5839 A person searching a zone for a fire in a non-addressable fire system should
Section 22.3 not have to travel for more than 60m to identify the source of a fire.
BS5839 The sensing element of a heat detection thermistor device should not be less
Section 22.3 than 25mm below ceiling, and not greater than 150mm below ceiling.
2
)Admin: Yousef BelghisAzar( https://telegram.me/PishwaElec
BS5839 The minimum static response to heat devices should not be less than 29°C
Section above the average ambient temperature, or less than 4°C above the highest
35.2.3 temperature the device can expect to experience.
3
)Admin: Yousef BelghisAzar( https://telegram.me/PishwaElec
For ceilings that feature an apex: as long as the height of the apex from the rest
of the ceiling is less than 150mm for heat detectors or less than 600mm for
BS5839
smoke detectors, then these can be treated the same as flat ceilings. For higher
Section
apexes, a device should be installed to the highest point. The distance to adjacent
22.3
devices can be increased by 1% per degree of angle of roof up to a maximum of
25%.
4
)Admin: Yousef BelghisAzar( https://telegram.me/PishwaElec
BS5839 Section Do not put detectors less than 1m from air inlets or air circulating
22.3 units.
Devices should not be mounted within 500mm of any obstruction. If the top of a
BS5839
solid partition is less than 300mm from the ceiling then treat it as a wall.
Section
Similarly, ceiling obstructions such as beams should be treated as walls if deeper
22.3
than 10% of the ceiling height.
5
)Admin: Yousef BelghisAzar( https://telegram.me/PishwaElec
for use in corridors that are escape routes.
BS5839 Section Never mount devices closer than twice the depth of light fittings or other
22.3 obstructions on the ceiling.
BS5839 Voids less than 800mm in height need to have independent coverage, unless fire
Section or smoke is able to spread from one area to another through the void or risk
22.2 assessment shows AFD (Automatic Fire Detection) to be necessary.
6
)Admin: Yousef BelghisAzar( https://telegram.me/PishwaElec
Vertical shafts like lifts and stairways should have a device mounted
BS5839 Section within 1.5m of any opening.
22.2
BS5839 Section Enclosed stairways should have a detector at the top of the stairway and
22.2 on each main landing.
A person should not have to travel more than 45m along an escape route to
BS5839
reach a manual call point (25m if disabled person to operate, or rapid fire
Section
development is likely). Manual call points should be sited at all stairwells and
20.2
exits from the building.
7
)Admin: Yousef BelghisAzar( https://telegram.me/PishwaElec
The centre of the frangible element of the manual call point should be
BS5839
positioned 1.4m (+/-200mm) from floor level (unless a wheelchair user is
Section 20.2
likely to be the first person to raise the alarm).
For areas where people are sleeping, sounder devices should produce a
BS5839
minimum 75dB(A) at the bed-head with all doors shut. in buildings providing
Section
sleeping accommodation for a significant number of people, all bedrooms
16.2.1
should have both audible and visual alarms.
9
)Admin: Yousef BelghisAzar( https://telegram.me/PishwaElec
BS5839 Decibel loss occurs through doors: approximately - 20dB(A) through a normal
Section door and approximately -30dB(A) through a fire door. Unless a sounder is
16.2.1 installed in a bedroom, it is unlikely that 75dB(A) will be achieved.
BS5839 Section Unless MICC cable is used, all cabling should be mechanically protected
26.2 from floor level up to a height of 2m.
11
)Admin: Yousef BelghisAzar( https://telegram.me/PishwaElec
Fire resistant cabling is now required within the whole fire alarm system
BS5839 including the mains supply cables. The use of non-fire resisting cables whether
Section 26 mechanically protected by fire resisting construction or not, will no longer
comply with BS5839 Part 1.
BS5839 Short circuit isolators limit the effect of one fault to a maximum of 2000m2. '2
Section simultaneous faults on a circuit should not disable protection within an area
12.2.2 greater than 10,000m2.
The EURB-4 standard conventional base from Eurotech should be wired as above
11
)Admin: Yousef BelghisAzar( https://telegram.me/PishwaElec
The EURB=4-EV standard intelligent base from Eurotech should be wired as above.
A battery powered, intelligent programming tool is available. The Eurotech EV-AD2 hand
held programmer is light, robust and easy to operate and is used for address programming and
functional testing.
12
)Admin: Yousef BelghisAzar( https://telegram.me/PishwaElec
Intelligent manual call points and modules are generally addressed by the use of a simple 8
bit DIL switch allowing upto a combination of 254 different addresses. The following
diagram indicates an address setting for a manual call point with a device address setting of
90.