Fan Coil Units Penthouse A 10/10/2023

Supply air Entering Entering Total Entering Leaving Water


Specification
Description Flow air Temp Temp Capacity Water Water Flow Qty
Type
(L/S) DB‐⁰C WB‐⁰C (KW) Temp‐⁰C Temp‐⁰C (L/S
FCU‐1.5TR Concealed 265 23 16.2 5.3 7 15 0.16 3
FCU‐2TR Concealed 350 23 16.2 7.0 7 15 0.21 4
FCU‐2.5TR Concealed 440 23 16.2 8.8 7 15 0.26 1
FCU‐3TR Concealed 530 23 16.2 10.6 7 15 0.32 2
FCU‐4TR Concealed 700 23 16.2 14.1 7 15 0.42 2
FCU‐5TR Concealed 880 23 16.2 17.6 7 15 0.53 3