RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 576 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 17 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 750 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 400 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 1 UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
576 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 388 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 628 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 16 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 750 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 500 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 1 & 3 UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
628 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 414 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 502 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 20 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 750 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 400 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 2 UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
502 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 351 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 501 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 20 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 750 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 400 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 3 UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
501 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 351 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 534 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 19 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 750 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 400 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 4A UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
534 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 367 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 631 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 16 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 750 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 500 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 4B UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
631 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 416 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 569 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 18 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 750 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 400 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 5A UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
569 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 385 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 604 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 17 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 750 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 500 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 5B UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
604 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 402 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 595 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 17 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 750 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 400 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 6A UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
595 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 398 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 385 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 26 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 500 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 300 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 6B UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
385 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 293 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 529 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 19 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 750 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 400 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 7A UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
529 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 365 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 459 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 22 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 500 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 400 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 7B UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
459 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 330 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 525 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 19 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 750 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 400 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: METERING ROOM
TO: BLOCK 8A UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
525 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 363 mm
2 LAYERS
RESULTS:
TRAY SPACE REQUIRED FOR 1 LAYER OF CABLES : = 455 mm
PLUS TRAY SPACE RESERVED FOR FUTURE : = 100 mm ( 22 %)
------------
RECOMMENDED TRAY SIZE FOR 1 LAYER OF CABLES: = 500 mm
------------
------------
RECOMMENDED TRAY SIZE FOR 2 LAYERS OF CABLES: = 400 mm
------------
NOTE: THE RECOMMENDED TRAY SIZES ARE BASED ON THE OVERALL DIAMETERS
OF TYPICAL XLPE/PVC COPPER CABLES ASSUMED LAID TOUCHING. THE SINGLE OR MULTI CORE
CABLES FROM 1.5mm2 THROUGH 630mm2 ARE BASED ON SAUDI CABLE OR RIYADH CABLE
CABLE TRAY SIZING CALCULATION FOR TRAY RUN:
FROM: BLOCK 8A UNITS
TO: BLOCK 8B UNITS
CALCULATION:
ACTUAL SIZE OF CABLE TRAY = TOTAL DIA. OF CABLES + TOTAL DIA. OF CONDUIT + FUTURE SPACE
455 + 0
ACTUAL SIZE OF CABLE TRAY = + 100 = 328 mm
2 LAYERS