Professional Documents
Culture Documents
User Manual
Doc. version 2.0
15 October 2019
To program the FC503 and FC506 fire control panels, use 5. Ensure there are no unrelated objects inside the
the software FireClass FC500 (FC501_FC503_FC506) control panel case.
Console release 01.00.01 or control panel FW version 6. Ensure the control panel is capable of processing
1.01 or higher. a fire alarm, and if a siren (sounder) is present in
the system, it is activated in consequence of this
Johnson Controls assumes no responsibility for damage to alarm. If there is a facility for transmission of fire
products arising from improper application or misuse. alarm signals to a central station, it should also be
ensured that the signal is correctly received.
Installation of this control panel must be carried out strictly 7. Verify the functionality of the circuit for the
in accordance with the instructions in the Installation detection of earth fault. The procedure is as
manual, and in compliance with the local laws and by laws follows:
in force. o Connect one of the SH terminals of the loop to
the panel earth.
The FC503 and FC506 fire control panels comply with the o Verify that the fault is reported correctly by the
essential requirements of standards EN54-2, EN54-4, and fire panel.
EN 54-21. o Remove the connection previously made.
Recycling information Note: Points 1 and 2 may be carried out by users. Points
The manufacturer advises that customers dispose of any 3, 4, 5, 6, and 7 must be carried out by qualified persons.
used equipment, such as panels, detectors, sirens, and
other devices, in an environmentally friendly manner.
Potential methods include reuse of parts or whole products
and recycling of products, components, and materials.
Maintenance
To ensure that the system continues to operate normally, it
must be maintained with regular testing by the user and
periodic maintenance by the installer in accordance with
local laws.
Page 2 of 38
8 Key - Fire relay ...........................................................36
Table of Contents 9 Key - Sounder (Disable).............................................37
Introduction ........................................................................ 4
FC500 repeater signaling..............................................37
FC503 and FC506 fire control panels ............................ 4
CPR information ............................................................38
Accessory items ............................................................. 4
User access level ............................................................... 4
Access level 1 (L1) ......................................................... 4
Access level 2 (L2) ......................................................... 5
User interface ..................................................................... 5
Panel command keys ..................................................... 6
VIEW LOG Parameters.................................................... 19
1 Key - View loop data ................................................. 19
2 Key - View devices .................................................... 20
3 Key - View SW zones ................................................ 22
4 Key - View output ...................................................... 22
5 Key – View network devices ..................................... 23
6 Key – View communicators ....................................... 23
7 Key – View system options ....................................... 23
8 Key – View the log..................................................... 24
9 Key – View the FW version ....................................... 25
0 Key – View panel information .................................... 25
View lists....................................................................... 25
MODIFY ........................................................................... 27
1 Key – INIT MSG (Modify panel label) ........................ 27
2 Key - User password ................................................. 27
3 Key - Day and night modes ....................................... 28
4 Key - Time and date .................................................. 28
5 Key - Clear LOG ........................................................ 28
6 Key – Walk Test ........................................................ 29
DISABLE .......................................................................... 30
2 Key – Devices (Disable) ............................................ 31
Select the loop .............................................................. 31
Select the device .......................................................... 31
Disable device on the loop ........................................... 32
3 Key – SW Zone ......................................................... 32
Disable SW zone .......................................................... 33
4 Key - Outputs ............................................................ 33
Select the output .......................................................... 33
Disable Output .............................................................. 33
5 Key - Network ............................................................ 34
6 Key - COMMUNIC. Device ........................................ 34
7 Key - Password disable ............................................. 36
Select the password ..................................................... 36
Disable password ......................................................... 36
Page 3 of 38
Introduction FC500MFI
FC503 and FC506 fire control panels The FC500MFI is a programmable multifunctional module
for connection to a real time event printer. The terminal
blocks also make it possible to connect a standard
The FC503 and FC506 fire control panels follow Johnson interface to remotely control and manage a set of inputs
Controls’ highest standards of quality and performance. and outputs to control the panel.
FC503 FC500IP
FC503 is an analogue addressable fire control panel with This module connects the control panel to a Local Area
one main loop (three sub-loops), that can support up to 250 Network (LAN).
addressable devices and 128 zones. BAQ140T24 switching
power supply powers FC503 at 5.5A @ 27.6 ±1 %V. FC503 and FC506 client
Suitable batteries include two *12 V/ 17Ah or two *12 V/ The FC503/FC506 master control panel can support up to
38Ah. The user interface has LEDs and icons. seven FC503 or FC506 client control panels. These
control panels can be used to expand the FC503/FC506
system in modular way.
The FC503 fire control panel is a modular system. The
configuration of the FC503 system depends on the size
and requirements of the application; therefore, some of the FireClass FC500 (FC501_FC503_FC506) Console
described devices and functions may not be present on This is a software application operating on Microsoft
your system. Windows 7 and higher. The console offers a quick and
The FC503 system consists of the following components: easy way to program the control panel and also provides
• One FC503 control panel event log and printout functions.
• Max. 8 FC500 repeaters
• Max. 4 FC500MFI multifunction modules FireClass console multi account engine (FCMAE)
• Max. 7 client panels Max. 250 devices in three different The FCMAE allows you to monitor multiple FireClass
sub-loops or 250 max in a single sub-loop only systems across the world from a single workstation. It
manages up to 32 FC500 series panels (FC501, FC503,
FC506 FC506, FC510, and FC520) connected to Ethernet
FC506 is an analogue addressable fire control panel with two through the FC500IP3 module. It shows the real time
main loops (six sub-loops). The panel can support up to 500 status and alerts the operator when an event occurs in one
addressable devices and a maximum of 250 devices in a of the monitored systems.
single main loop, and 256 zones. BAQ140T24 switching
power supply powers FC506 at 5.5A @ 27.6 ±1 %V. Suitable
batteries include 2 * 12 V/ 17Ah or 2 * 12 V/ 38Ah. The user
User access level
interface has LEDs and icons. Access level 1 (L1)
The FC506 fire control panel is a modular system. The At access level 1 (L1) or viewing level, all users can view
configuration of the FC506 system depends on the size the control panel status. See Table 1 for information about
and requirements of the application; therefore, some of the the control panel operations and statuses available at L1.
described devices and functions may not be present on
Table 1: Access level 1 (L1)
your system.
The FC506 system consists of the following components: Operations Status available
• One FC506 control panel ANALYZE 1. Loop
• Max. 8 FC500 repeaters 2. Device
• Max. 4 FC500MFI multifunction modules 3. SW Zones
• Max. 7 client panels 4. Outputs
• Max. 500 devices in six different sub-loops or two main 5. Network
loops (250 devices max per main loop) 6. Communication
7. Options
The FC503 and FC506 fire control panels allow you to 8. Log
manage the functions of the fire control system up to 9. FW Vers
2000m (loop) with shielded 2 core cable 2x2.5mm². 0. Panel
VIEWLOG Log
VIEWLISTS 1. DIS.ZONES
Accessory items 2. DIS. DEVICES
FC500 repeater 3. DIS. PARTS
Repeaters are peripherals that provide system status 4. WALK TEST
information, emit audible signals, and allow users to 5. FAULTS
control the functions of the FC503 and FC506 system (up 6. WARNINGS
to 1000m, with twisted pair shielded cable). 7. DEV. in TEST
Page 4 of 38
Access level 2 (L2) • HELP button to open the Help screens on the Display.
Access level 2 (L2) is for operating the system, and See Figure 2.
requires an access code. At this level, all the • Command keys
operations at L1 are also available. See Table 2 for
information about the L2 operations and statuses: Note: Use the cursors keys Up, Down, Right, and Left,
and the command keys LAMP TEST and SILENCE
Table 2: Access level 2 (L2) BUZZER, and the alphanumeric keypad to enter the
characters A,B,C,D,E, and F. Use these characters to
Operations Status available enter hexadecimal numbers for planned future use.
MODIFY 1. INIT. MSG
2. USER PASSWORD The function of the cursors keys, the ESC key, the ENTER
3. DAY/NIGHT key, and the command keys, is different in every LCD
4. TIME and DATE display and is fully described in this manual. Also, the
5. Clear log amount of time spent pressing the keys has a different
6. WALK TEST function in the different LCD displays. In future, it will be
7. Options possible to use the HELP key to access more information.
8. Log
9. FW Vers SILENCE / RESOUND / SOUNDERS
0. Panel The control panel can operate in day mode or night mode.
DISABLE 1. Dis. LISTS If the system is silenced during day mode, the silence
3. SW. ZONES status remains until the system is unsilenced (unless new
4. OUTPUTS alarms or faults occur). If the system is silenced during
5. NETWORK night mode, the silence status remains until the night mode
6. COMMUNIC silence time expires. On power up, the system starts in
8. FIRE relay day mode by default. During this operating mode, silenced
alarms/faults will not be unsilenced automatically.
RESET
User interface Reset will stop alarm, delay to alarm, warning, and fault
conditions. Access to this command is limited to
Figure 1: User interface view of FC503 and FC506 authorized personnel using an installer or user access
code. The system reprocesses any alarm, delay to alarm,
warning or fault signal that is not cleared by a reset.
Command keys cannot be used when a reset is running.
The repeaters can be reset by using the user access code.
Description of keys
To manage the panel from the User Interface (UI), use the
following controls:
Page 5 of 38
Panel command keys
Table 3: Description of the control panel and repeater keys
Key Description
SILENCE/ RESOUND Restores the silenceable outputs and the loop devices to standby status
SOUNDERS
Note: The silence status remains until you press the SILENCE key again
in day mode; or until the night mode silence time expires in night mode;
or until the system detects a new alarm condition.
RESET Resets the fire detectors and restores all outputs to standby status
Note: If you press this key when the control panel is functioning as
intended, all LEDs will be on and the buzzer emits a continuous beep.
HELP Explains the information on the LCD display in the different screens
Notes:
• This is an embedded help feature present on the panel LCD
display.
• The Help key is disabled on repeater panels.
System fault In the case of a system fault LED latch, press the system fault
acknowledgement acknowledgement switch to identify the fault and then press RESET.
switch Notes:
• To access the system fault acknowledgement switch, open the
front cover of the panel. The switch is located on the bottom left
of the PCB.
• The system fault acknowledgment switch is not available on
repeater panels.
• The system fault LED latches if one of the following conditions
occur:
o The system resets itself (a watchdog reset) when an
internal logical fault occurs.
o The system is powered ON after a complete panel shut
down.
Note: You can operate only the LAMP TEST, SILENCE Table 4: HELP key functions
BUZZER, and EVAC command keys without the access
Key Help functions
code (access level L1). Entering the access level L2 and
L3 codes allows you to operate all the other command 1 Selects program or analyze mode
keys. 2 Selects disable or view list mode
3 Shows the panel event log or select the
modify mode
HELP key
4 Selects between the function groups
related to the keys 1, 2, and 3
Note: This section describes the functionality of the HELP ENTER No function
key. ESC Exits from the Help to MAIN screen, or
EVENT DRIVEN screen, if any
To explain the information on the LCD display in the
Press the key for more than 3 seconds to
different screens, an embedded help feature is present on
the panel LCD. force the panel to level 1.
See Table 4 for key HELP functions for the MAIN screen. Up and Scrolls through the Help list.
Down
Page 6 of 38
Right No function Table 5: Buzzer signaling
and
Condition Frequency Sound Pause
Left
(Hz)
System Fault 1300 2.5 s 2.8 s
Figure 2: Example of the LCD display after pressing
(main processor
the Help key
fail)
General Fault 660 1s 1s
(Programming
data
corrupted)
Notes:
• During standby status and if the control panel is in day
mode, only the green mains LED and the day mode LED
should be ON.
• The general fault LED and the LED specific to the fault
are ON or blinking during a fault condition.
• To manage the brightness and contrast of the LCD
display, see the MAIN screen.
Page 7 of 38
Figure 3: Event driven screens and MAIN screen basic * Only if the panel is in
interactions normal activity.
** No timeout for ANALYZE
menu, VIEW LOG screen,
VIEW LIST screen. The
timeout can be extended
to four minutes in the
programming menu when
you enter the parameters.
Page 9 of 38
Figure 4: Display MAIN screen access to the warning, delay to alarm,
management of the panel alarm, fault, or walk test
ENTER No function
MAIN screen
The MAIN screen is the first screen displayed by the
panel after it powers up (see Figure 4). This screen
can be replaced by the EVENT DRIVEN screen. After
30 seconds of inactivity, the FRONT screen appears.
Fields
See Figure 4.
1 Access level
2 Control panel status The Access level field shows the current access level
of the panel. 10 seconds before leaving the present
3 Control Panel name
access level this field starts to blink.
(you can modify this)
The Control panel status field displays the current
4 Panel activity/Current
panel status, the possible values include ACTIVE (its
phase
normal state).
A continuous and steady blinking indicates that the
System option control panel is functioning properly.
The Panel activity/current phase field displays the
• Selected language current activity of the panel. For more information,
• Panel identification number see Table 8.
• The panel type (FC503/ FC506)
• The installed battery capacity (17Ah/38Ah) Table 8: Panel activity field values
The selected language is vital for the user interface Value in panel activity Description
(UI) to select between the two available languages in field
the panel. The panel identification number is vital for RESETTING Panel is resetting
the panel to name and manage the files over the LOC. PROG Panel is being
USB memory stick. programmed by a local
access
Note: When the START-UP screen is initialising, the REM.ACCESS Panel is remotely
panel is not fully operative and the control keys are accessed (PC via serial
not working. port, USB or IP)
SYS. INIT Panel is initializing
Front screen
The Front screen is generally displayed when the SYS. VER Panel is verifying itself
panel is in standby status. It can contain an
advertisement message set by the installer. The CLEAR LOG Panel is clearing the
screen content and the enablement to display it are event log
set by the FC500 FC503/FC506 software (SW). For WAITS Panel is waiting to be
information about FRONT screen key functions, see configured
Table 7.
———— No activity
Table 7: Alphanumeric, Cursor, ESC and ENTER
key functions on the FRONT screen SCANNING LOOPS Panel is in its normal
activity
Key Function
Alphanumeric No functions
keypad Note: The date and time field blinks until the date
Cursor keys No function and time is set.
ESC Exits from the FRONT
screen, and moves the UI
to the MAIN or EVENT
DRIVEN screen, activated
directly by events:
Page 10 of 38
Table 9: Alphanumeric keypad, Cursor, ESC and Table 10: Field information on the diagnostic screens
ENTER key functions on the MAIN screen Field Screen display
Key Function v-PSU Displays the output voltage of the
panel power supply
1 Moves to Program or Analyze mode
I-PSU Displays the output current of the
panel power supply
2 Moves to Disable or View lists mode
If I- Displays “LOW”; Vbatt displays
3 Shows the View log or moves to Modify
PSU<150mA the battery voltage
mode
Batt.Res Displays the value of the battery
4 Selects between the function groups internal resistance plus the
related to the keys 1, 2, and 3 battery wiring resistance.
Up Increases the brightness of LCD display If Displays NO BATT
Batt.res>999
Down Decreases the brightness of LCD display mOm or
Vbatt.<19Vdc
Right Increases the contrast of LCD display
Loop diagnostic screen
Left Decreases the contrast of LCD display
This is a general purpose screen used to display
the values of firmware (FW) parameters related to
ESC Exits from the MAIN screen
Changes the UI to the FRONT or EVENT loop management, in real time. The rows labelled
DRIVEN screen. A and B display the average, minimum and
Pressing the key for more than 3 seconds maximum value of the relevant FW parameter. The
forces the panel to access level 1. row labelled C counts the occurrence of events
ENTER No function related to the assigned FW parameter. If you press
the 0 key, all the displayed values reset.
Keyboard test
This screen allows you to test all keys in the panel
Diagnostic screens
UI. If you press any key on the panel UI, the
The following functions are available through the
relevant part of the display goes blank when the
diagnostic screens:
• A display of some electrical parameters inside key press is detected.
the panel (Panel meter screen)
• A display of some functional parameters related Menu screen
to the loops (Loop screen) The MENU screens allow access to the program,
• Execution of the panel keyboard test (Keyboard analyze, disable, and modify features of the panel.
Test screen). For more information on user interaction, see the
To access the diagnostic screens from the MAIN User access level, Disable, and Modify sections of
screen, press and hold the 4 key. this manual. For installation information, refer to the
FC503/FC506 Installation manual.
Figure 5: Interaction between the diagnostic
screens Event driven screens
The event driven screens activate when the system
detects events. When an event activates, it overrides
the screen present on the display at that time. An
event driven screen may be overridden by another
event driven screen that has a higher priority.
Table 11 contains the event driven screen priority
assignment.
Page 11 of 38
If a lower priority event screen is suppressed by a
highest priority event screen, the MORE INFO LED
switches on. Figure 7: Warning status scrolling Right key
Warning status
You can program the FC503/ FC506 fire control
panel to provide warning or delay to alarm status
before alarm status.
Page 12 of 38
Table 13: Cursor key functions
Key Function
Up Shows the next event, other than the
first and the last
Down Shows the previous event, other than
the first and the last
Right Shows the next string of data
Left Shows the previous string of data
Page 13 of 38
To supply the information about the points in delay Figure 9: Delay to Alarm status: Scrolling Right
to alarm, the visualization of the delay to alarm is key
by zones (default) or by points.
Page 16 of 38
3 If the last fault is related to a point, use the 1 Press the Right key to
3 key to jump to the last activated Loop scroll to the second
Device Status Visualization screen. block of fault zone data
2 Press the Right key to
If the last fault is a loop break fault, jump to scroll to the third block
the Locate the Loop Break screen. of fault zone data
3 Press the Right key to
If the last fault is related to an item that can scroll to the fourth block
be disabled, the UI moves to the disabling of fault zone data
screen, in order to allow a fast disablement Note: In the case that a fault is related to a Loop device,
procedure. the faulty point label is swapped with the assigned zone
label every 3 seconds. If the zone has not been
Note: If the access level is less than L2, the associated with the point, only the point label will
password will be required before appear.
proceeding to disablement.
4 Displays further faults. Table 22: Cursor key, ESC and ENTER key
functions in Fault status
When a point information is present in the
Key Function
fourth row, a further 4 key press will cause
the UI to jump to the related Loop Device Up Shows the previously available fault,
Status Visualization screen. other than the first and the last
Down Shows the next available fault, other
When a point fault is present in the fourth than the first and the last
row, a further 4 key press will cause the UI Right Shows the next auxiliary information
jump to the Locate the Loop Break about the point
screen. Left Shows the previous auxiliary
information about the point
If there is a fault related to an item that may ESC Returns to the MAIN screen
be disabled present in the fourth row, the UI ENTER Blocks or reactivates the exchange
moves to the disabling screen to allow a between the labels of the devices and
fast disablement procedure. those of the zones
Page 17 of 38
Note: During the locate loop break procedure all the
detectors power down. At the end of the procedure, a
full loop initialization is executed. The devices not in
the configuration are not found.
Page 18 of 38
Table 24: Cursor, ESC and ENTER key functions
VIEW LOG Parameters Key Function
Up, Down, Right, No functions
This section provides an overview of the Left
programming features on the FC503/FC506 panels. ESC Return to the MAIN
screen.
For information on the parameters of each state, refer
ENTER No function
to the FC503/FC506 Installation Manual.
Table 23: Alphanumeric keypad functions on the 1 Key - View loop data
View Parameters screen Use the 1 key to view the loop data. See Figure 17.
Key Function Table 25: Alphanumeric, Cursor, ESC and ENTER
1 Loop: Starts the procedure to allow key functions to view loop data
you to select and view loop data.
2 Device: Activates the selection and Key Function
visualization sequence of real time Alphanumeric No functions
loop device data. keypad
3 SW zone: Activates the selection and Up Selects the next loop
display procedure for the data Down Selects the previous
corresponding to all SW zones. loop
4 Output: Activates the selection and Right, Left No functions
viewing procedure for the data ESC Returns to the
corresponding to an output. previous screen
5 Network: Starts the procedure to view ENTER No function.
all devices (repeaters and MFI
modules) on the RS485 Network. Fields
6 Communic.: Activates the viewing The Loop field shows the current loop on display.
sequence for the main data on all See Figure 18.
communication units.
7 Option: Activates the viewing The Detectors field displays the number of detectors
sequence for all locally programmed sensed on the relevant loop.
system options.
8 Log: Starts the procedure to allow you The Modules field displays the number of modules
to view logged events. detected on the relevant loop.
9 FW ver.: Starts the procedure to view
the firmware versions of all of the The Status field displays the status of the selected
panel’s processors. loop. The following are the possible values:
0 Panel: Starts the procedure to allow
• Working
you to view the panel information.
• Fault
• Standby
• Disabled
Page 19 of 38
The Loop field displays the total current supplied to 3 If blinking, the control
all three loops in real time. This field has a 5 second panel is operating
refresh rate. normally
4 Module number
2 Key - View devices 5 Overcurrent that powers
Use the 2 key to view the loop device data (select the OFF the loop
loop and then the device). See Figure 17. 6 Current value in the 3
loops
Table 26: Alphanumeric, Cursor, ESC and ENTER 7 Current status of the
key functions to select a loop loop
Key Function
Alphanumeric Use the 1, 2 or 3 key to Selecting the device
keypad view the loop (see Figure
After selecting the loop, the loop details are shown.
18)
Note: Use the 1, 2, 3, 4, 5, See Figure 19.
and 6 keys to select up to 6 Use the Alphanumeric keypad to insert the device
loops on the FC506 panel address. If the address does not exist, the next
Up, Down No functions
available device is selected.
Right Selects the next available
loop Note: If the device is in the system, square brackets
Left Selects the previously are present near the address. If the address does not
available loop exist, or is different from that selected in the
ESC Cancels the operation underlying bar, arrows are shown.
Returns to the previous
screen Table 27: Cursor, ESC and ENTER key functions
ENTER Confirms and displays the to select a device
screen of the selected loop
Key Function
Up, Down No functions
Figure 17: Viewing loop choice and loop details Right Selects the next available
device
Left Selects the previously
available device
ESC Cancels the operation
Returns to the previous
screen
ENTER Confirms and displays the
information for the selected
device
1 Access level
2 If blinking, the control
panel is operating Viewing device data on the loop
normally Select the loop and then the device. See Figure 19.
3 Control panel name
4 Selected loop Table 28: Alphanumeric keypad, Cursor, ESC and
ENTER key functions to view device data
Key Function
Figure 18: Viewing loop details 0 Disables the device (detectors only)
Note: Access level 2 or above is
required
Up Scrolls through modules with several
inputs or outputs
Down Scrolls through modules with several
inputs or outputs
Right Displays the status of the next device
on the same loop
Left Displays the status of the previous
1 Loop number device on the same loop
2 Detector number ESC Cancels the operation
Returns to the previous screen
ENTER No function
Page 20 of 38
Fields Figure 19: Viewing devices on the loop (detectors
and modules)
The Device Status field displays the current status of
the detector or module. The possible values are as
follows:
• WORKING
• ACTIVE
• WARNING
• FAULT
• ZONE DIS.
• WALK TEST
• STAND-BY
• The loop ID
• The device address
• The device type
• The channel ID (for the modules)
• The zone number
Page 21 of 38
3 Key - View SW zones
Use the 3 key (SW Zone) option in the Analyze menu
to view software zones (maximum 128 zones for
Figure 20: Viewing SW zones
FC503 and 256 zones for FC506). The status of all
the SW zones in the system is displayed in compact
format, see Figure 20. The status of the SW zones is
displayed using the abbreviations in Table 29.
1 SC output
Page 22 of 38
2 Standby status
3 Open collector output
5 Key – View network devices
Figure 23: Viewing the communicator
Use the 5 key to view network devices such as MFI
modules (maximum 4), client panels (maximum 7)
and repeaters (maximum 8). See Figure 22.
Fields
The Network devices field status displays the related
output status using abbreviations. For more
information, see Table 33.
1 Link status Table 36: Alphanumeric, Cursor, ESC and ENTER key
2 Network type devices functions to view system options
Key Function
6 Key – View communicators Alphanumeric No functions
Use the 6 key to view the communicator connected to keypad
the control panel, see Figure 23. The FW version, the Up, Down, Right, No functions
FC500IP module status, and the IP address is Left
displayed. ESC Cancels the operation
Returns to the previous
screen
Table 34: Cursor, ESC and ENTER key functions ENTER No function
to view the communicator
Key Function Figure 24: Viewing options
Alphanumeric No functions
keypad
Up, Down, Right, No functions
Left
ESC Cancels the operation
Returns to the previous
screen
ENTER No function
1 Access level
2 Control panel status
Page 23 of 38
3 If blinking, the control Up Selects the previously
panel is operating available event
normally Down Selects the next available
4 Mode type event
8 Key – View the log Right Displays the next available
data (see Figure 27)
Use the 8 key to select View Log or select it directly
Left Displays the previous
from STANDBY status. You can view the log from the
available data
MAIN screen without a password. See Figure 25.
ESC Cancels the operation
To see the stored events in the fire control panel log, Returns to the previous
use the View Log option in the View Parameters screen
menu. The log stores the most recent 4000 events. ENTER No function
When the log is full, the oldest event is deleted, so
the newest can be stored. Notes:
Note: Use the CLEAR LOG option in the MODIFY • If the events are linked to the devices, the
menu to delete the log events. zone label alternates with the point label
The following data is stored in the log: every 3 seconds. If the zone is not
associated with the point, only the point label
• Event description appears.
• Event number • If the displayed events are filtered by type, an
• Description of the device (panel or repeater) asterisk symbol (*) immediately begins to
in the event blink to the right of the event number.
• Description of the event item
Figure 25: Viewing the log
• Time and date of the event
• Address of the event item
Fields
See Figure 25.
Key Function
Page 24 of 38
• Version of the PCB
• Type of power supply on board
• Type of batteries on board
Figure 26: Scrolling with the Right key to view log
• Presence of the auxiliary controller, see
events
Figure 27
View lists
Press = View List on the MAIN screen.
1 Press the Right key to scroll to the
The View List option allows you to view the lists
second block of data about zones in
described in Table 41.
the log
2 Press the Right key to scroll to the Table 41: Alphanumeric keypad, Cursor, ESC and
third block of data about zones in the ENTER key functions to select and view list types
log
Key Description
1 Dis. Zone: A list of disabled
9 Key – View the FW version zones
2 Dis. Device: A list of disabled
In the View Parameters menu, use the Ver. FW devices
option to view the fire control panel’s FW version. 3 Dis. Part: A list of disabled parts
Use the 9 key to view the FW version. See Figure 27. 4 Walk Test: A list of walk test
zones
Table 39: Alphanumeric, Cursor, ESC and ENTER 5 Faults: A list of faults
key functions to view firmware information 6 Warnings: A list of warnings
7 Dev. In Test: A list of devices
Key Function
actively in test mode
Alphanumeric No functions
Up, Down, No functions
keypad
Right, Left
Up, Down, Right, No functions
ESC Cancel the operation
Left
Returns to the previous screen
ESC Cancels the operation
ENTER No function
Returns to the MAIN screen.
Note: A blinking list number indicates that the
ENTER No function
corresponding list contains data.
• Fire panel ID The Item Info field displays information about the
• Electronic board serial number of the fire currently selected item. It shows the location of
panel (eight hexadecimal digits)
Page 25 of 38
the SW zone and loop device or the description of
a system part and the related label.
1 Access level
2 Control panel status
3 If blinking, the control
panel is operating
normally
4 List type
5 List item information
6 Current item ID
7 Total number of items in
the list
8 Options
Note: For the Dis.
Zone, Dis. Dev, Dis.
Part and Walk Test, a
common visualization
list screen appears.
Page 26 of 38
Table 44: Key functions on the modify panel label
MODIFY Key Function
Alphanumeric Enter or update the panel label
To access the MODIFY menu, enter the user access keypad
code (11111 at default), each digit will be masked by Cursor keys • Up: changes the selected
* (asterisk). For the MODIFY option, on the MAIN letter from lower case to
upper case
screen, press the 3 key. The options available from
• Down: changes the
the MODIFY menu are described in Table 43.
selected letter from upper
Figure 29 shows the options for the MODIFY menu case to lower case
after inserting or modifying the password. • Right: selects the next
character to be modified
• Left: selects the previous
Figure 29: Display MODIFY menu character to be modified
Page 28 of 38
Note: During the clear log activity the MAIN screen seconds. This zone setting is programmable
displays with the panel activity field loaded with the using the PC software. The default value is NO.
clear log string (see Figure 35). Once the log has
been cleared, the panel resets. The presence of a zone in the walk test mode is
signaled by the test yellow LED on the UI. More than
Figure 33: Display Clear log one zone can be put in walk test mode at the same
time.
Page 29 of 38
3 If blinking, the control
DISABLE panel is operating
To access the DISABLE menu from the MAIN normally
screen, enter a user PIN password (the default PIN is 4 Options
11111): each entered digit will be hidden with the *
symbol. This activates the procedure used to enable
Table 48: Keypad and key functions in the
and disable each of the following: Disable state
• Display list of disabled devices Key Function
• Loop devices (input or output devices) Alphanumeric Selects the disable and enable
• SW zones keypad options
• Outputs of the control panel Cursor keys No function
• Network devices ESC Cancels the operation
• Communic. Returns to the previous screen
ENTER No function
• FIRE Relay
Note: When a device is disabled, the disable LED is To select the various disable and enable options, use
on, and any alarm or fault related to the disabled the keys described in Table 49.
device is ignored.
Table 49: Alphanumeric keypad, Cursor, ESC and
The disabled and enabled modes are as follows: ENTER key functions for the disable and enable
options
• Input devices
Key Function
A disabled input device (detector, input
1 Selects the Disab. List
module, conventional zone module,
2 Selects the Disable option of the
addressable call points) will not generate an Loop devices
alarm or fault status. 3 Selects the Disable option of SW
o To clear an alarm status generated zones
by an input device, reset the fire 4 Selects the Disable option of
control panel. Outputs
• Output devices 5 Selects the Disable option of
An alarm or fault status will not activate Device in the Network
disabled output devices (output modules, 6 Selects the Disable option of
addressable sirens). Comunic. devices
o To stop the output devices 7 Selects the Disable option of the
activated by the fault status, user password #2… #8 and
disable the devices concerned. installer #2
o To stop the output devices 8 Selects the Disable option of the
fire relay output
activated by an alarm status,
9 Selects the Disable option of the
reset the fire control panel.
sounders
Note: Output devices enabled during alarm or fault Cursor keys No function
status (programmed), will be activated immediately. ESC Cancels the operation
Returns to the previous screen.
The display (see Figure 35) shows how to select the ENTER No function
options to disable and enable.
Note: The 2, 7 and 9 key options can only be
Figure 35: Display Disable menu enabled by the installer #1 password. The default
user password is 00000.
Page 30 of 38
1 Access level
2 Panel status
Table 50: Alphanumeric keypad to select a list to 3 If blinking, the panel is
analyze operating normally
Key Function 4 Options to choose
1 Shows the list of disabled zones 5 List type
2 Shows the list of disabled loop devices 6 List item information
3 Shows the list of disabled system 7 Current item ID
parts (Outputs, Communicator) 8 Number of items in the
list
Table 51: 1 Key Disable list key and function 2 Key – Devices (Disable)
Key Function This option is only enabled if you enter the Control
Cursor No function Panel using a Master Installer PIN. The default PIN is
keys 00000. Use the 2 key to select “Device” Disable. The
ESC Cancels the operation. Loop can be selected (see Figure 36).
Returns to the previous screen.
ENTER No function
Select the loop
Note: For more information, see the View lists Table 54: Alphanumeric keypad in the select the
paragraph in the VIEW LOG Parameters chapter. loop state
Key Function
For disabled zones, loop devices and system parts,
1, 2, and 3 Selects loop
see the second display in Figure 38.
Table 52: Alphanumeric keypad for disabled Note: To select up to 6 loops in the FC506, use the
zones, loop devices and system parts 1, 2, 3, 4, 5 and 6 keys.
Key Function Table 55: Cursor, ESC and ENTER key functions
1 Calls the enablement screen to to select the loop
enable the displayed entity
Key Function
Table 53: Disabled zones, loop devices and Cursor • Up and Down keys: No functions
system parts keys and functions keys • Right key: Selects the next loop
• Left key: Selects the previous
Key Function loop
Cursor • Up key: Selects the previous item ESC Cancels the operation
keys • Down key: Selects the next item Returns to the previous screen
• Right and Left keys: No functions ENTER Confirms and displays the
ESC Cancels the operation information screen for the selected
Returns to the MAIN screen. loop.
ENTER No function
Page 31 of 38
• Right key: Selects the next Figure 37: Displays of disable devices
loop
• Left key: Selects the
previous loop
ESC Cancels the operation
Returns to the previous screen
ENTER Confirms and displays the
screen of the selected loop.
3 Key – SW Zone
Use the 3 key to select SW zone; after the zone has
been selected the zone can be Disabled/Enabled.
See Figure 38.
Select SW zone
Use the Alphanumeric keypad to select the zone
identification number.
Page 32 of 38
Table 60: Cursor, ESC and ENTER key Table 61: Keypad and key functions in the display
functions to disable a device on the loop SW zone state
Key Function
Cursor keys • Up and Down keys: No Key Function
functions. Alphanumeric No function
• Right key: Selects the keypad
next SW zone Cursor keys No functions
• Left key: Selects the ESC Cancels the operation
previous SW zone Returns to previous screen
ESC Cancels the operation ENTER Confirms and disables the SW
Returns to the MAIN screen. Zone. The User Interface moves to
ENTER Accepts the selection and the MAIN screen, signaling a local
displays the next screen, if programming activity followed by a
the zone exists panel reset.
Key Function
Alphanumeric Selects the output identification
keypad number.
Cursor keys Up key: Shows the next type of
outputs
Down key: Shows the previous
type of outputs
The type of outputs are as follows:
• SC1 Output (NACFIRE)
• SC2
• OC Output 1-2
Right and Left key: No function
ESC Cancels the operation.
1 Index of the zone Returns to the previous screen.
2 Access level ENTER Confirms the operation.
3 Control panel status
4 If blinking, the
control panel is Disable Output
operating normally
5 Enable/Disable In Figure 40, the display shows the current
request status of the output, the possible actions are
6 Current status enable or disable.
7 SW zone dis./enable
Disable SW zone
The display shows the current status of the SW
zone, the possible actions are enable or disable.
Page 33 of 38
Figure 39: Display Dis. Outputs network device.
Note: If the number is
incorrect, an error message
will be shown:
WRONG VALUE
PLEASE ENTER NEW
PARAMETER.
Cursor keys Use the Up Key to show the
next type of network device.
Use the Down Key to show
the previous type of
network device. The type of
devices are as follows:
• Repeater 1-8
• MFI 1-4
• Client panel 1-7
• RS485NET:
1 Identification number
local network
2 Access level
interface
3 Control panel status
No function is related to the
4 If blinking, the
Right or left key.
control panel is
operating normally ESC Cancels the operation.
Returns to the previous
5 Enable/Disable
screen.
request
ENTER Confirms and displays the
6 Current status
next screen.
7 Output Dis./Enable
Table 63: Keypad and key functions in the Disable the network device
disable output state The display shows the current status of the network
device, the possible actions are enable or disable.
Key Function
Alphanumeric No function Table 65: Keypad and key functions in the disable
keypad the network state
Cursor keys No function
Key Function
Alphanumeric No function
ESC Cancels the operation keypad
Returns to the previous
Up, Down, No functions
screen
Right, Left
ENTER Confirms and the UI moves Cursor keys
to the MAIN screen
ESC Cancels the operation and returns
followed by a panel reset to the previous screen.
ENTER Confirms and the UI moves to the
MAIN screen followed by a panel
5 Key - Network reset.
The 5 Key is used to select the Disable
Network devices option. After the network
device has been selected, it will be 6 Key - COMMUNIC. Device
disabled/enabled accordingly (see Figure 41). The 6 Key is used to select the disable Communic.
devices option; after Communic. device has been
Select the network device selected, you will be able to disable or enable it. The
corresponding Telecom module will then be
disabled/enabled accordingly (see Figure 42).
Table 64: Alphanumeric keypad, Cursor, ESC
and ENTER key functions in the select the
network device state Disable the COMMUNIC. device
Key Function
Alphanumeri Use the Alphanumeric
c keypad keypad to select the
identification number of the
Page 34 of 38
Table 66: Alphanumeric keypad, Cursor, Table 67: Alphanumeric keypad, Cursor, ESC and
ESC and ENTER key functions to select the ENTER key functions in the disable the
COMMUNIC. device COMMUNIC. device state
1 Identification number
1 Access level
2 Access level
2 Control panel status
3 Control panel status
3 If blinking, the
4 If blinking, the control panel is
control panel is operating normally
operating normally
4 Communicator type
5 Enable/Disable
5 Enable/Disable
request
request
6 Current status
6 Current status
7 Device Dis./Enable
7 Communicator
Dis./Enable
Page 35 of 38
Figure 42: Display enabled/disabled password
7 Key - Password disable
This option is only enabled if you enter the
control panel using a Master Installer PIN
(Default 00000).
Use the 7 Key to select the disable password
option; after the option has been selected the
corresponding password will be
disabled/enabled (see Figure 43).
• Enabled
Disable password • Disabled
In this state, the display shows the current The item “Action to do” contains the following actions:
status of the selected password (user or
installer). The possible actions are: enable or • ENABLE IT?
disable. • DISABLE IT?
Table 69: Keypad and key functions in the Table 70: Alphanumeric keypad, Cursor, ESC and
disable password state ENTER key functions in the fire relay state
Key Function Key Function
Alphanumeric No functions Alphanumeric No function
keypad keypad
Up, Down, No functions Up, Down, No function
Right, Left Right, Left
cursor keys cursor keys
ESC Cancels the operation ESC Cancels the operation and returns
Returns to the previous to the previous screen.
screen ENTER Confirms and the UI moves to the
ENTER Confirms and the UI moves MAIN screen followed by a panel
to the MAIN screen reset.
followed by a panel reset.
Page 36 of 38
activated with an access level 2 or 3 pass code. For more
Figure 43: Display enabled/disabled fire information, see Table 3.
relay
LCD display description
The information on the LCD display is organized as
screens. There are two screen types:
• MAIN screen
• Event driven screens
The MAIN screen allows access to the panel
information. It also shows the status of the panel.
1 FIRE relay The FC500 MAIN screen replicates the panel MAIN
Dis/Enable screen with the following limitations:
2 Access level • Will never be overwritten by the panel Front screen
3 Control panel status • Only the View list and View Log screens may be
4 If blinking, the called.
control panel is • The ESC long press to return to level 1 is not
operating normally operative.
5 Enable/Disable • View log screen description acts as in the panel.
request • View list screen description acts as in the panel.
6 Current status
0051
EXPECTED OPTIONS
Fault signals from points
Dependencies on more than one alarm signal: type A and B
Delays to outputs
Disablement of addressable
point Test condition
Output to fire alarm device
Page 38 of 38