You are on page 1of 38

Serial Number: _______________

“Translation of original instructions”

Viale Industria 4
12051 Alba (CN) Italy
T +39 0173 31 41 11 F +39 0173 34 872
www.bianco-spa.com

FLUO LM2
OPTICAL CENTRING DEVICE

Use and maintenance manual


Hardware Revision of B016 board B016R1
Revision of the assembly board REL00
Software version V0.4
Release date of the software version 17-06-2014

Draft revision: 0.2


Last change on this manual: 10/06/2015
______________________________________________ Page 1 of 11

Attachment INTRODUCTION
Table of contents
1 TECHNICAL DATA AND EQUIPMENT IDENTIFICATION......................................... 2 
2 DESCRIPTION OF THEEQUIPMENT ......................................................................... 4 
2.1 Main parts .................................................................................................................... 4 
2.2 Compatibility with the previous system, FLUO LM1 .............................................. 5 
3 CONDITIONS OF USE ............................................................................................ 6 
4 OPERATOR WORKSTATION ................................................................................... 6 
5 INSTALLATION AND START-UP .............................................................................. 7 
5.1 Equipment assembly ................................................................................................. 7 
5.1.1 Preliminary check ............................................................................................................ 7 
5.1.2 Anchoring the sensor tube ............................................................................................. 7 
5.1.3 Vibrations .......................................................................................................................... 7 
5.1.4 Installing the control board ............................................................................................ 8 
5.1.5 Accessibility ...................................................................................................................... 8 
5.1.6 Heat sources ..................................................................................................................... 8 
5.1.7 Cleaning the sensor......................................................................................................... 8 
5.2 Electrical system ......................................................................................................... 9 
5.2.1 Line speed reference ...................................................................................................... 9 
5.2.2 Exchange of enabling signals and messages to the outside ................................... 9 
5.3 Machine commissioning. ........................................................................................ 10 
5.3.1 Preliminary checks ......................................................................................................... 10 
5.3.2 System start-up and calibration .................................................................................. 10 
6 DISPOSAL............................................................................................................. 11 
 
______________________________________________ Page 2 of 11

1 Technical data and equipment identification


Supply voltage: See order
Frequency: See order
Power installed: See wiring diagram
Maximum width of fabric: See order

Sensor for maximum ambient temperature: 40°C when using the polycarbonate
cover, upon request we can provide you with different tube covers that can be
used at high temperatures.

Maximum ambient temperature for the control panel: 50°C

Note: for operation at altitudes over 1000 metres a.s.l. it is necessary to reduce the
maximum permitted ambient temperature by 0.5 °C every 100 metres more.

Electric panel level of protection: IP53


Level of protection of the sensor: Depending on the configuration

Applied standards: EN60204-1

The equipment is supplied with an identification plate, affixed on the side of the
panel or on the internal side of the door, reporting the following identification data:

· Manufacturer and its address


· Model and type
· Serial no.
· Year of manufacture
· Maximum speed
______________________________________________ Page 3 of 11

It should be noted that through the declaration of incorporation of the incomplete


machinery, the manufacturer certifies that the same is suitable for being
incorporated into other machinery and that it has been designed and built in
compliance with all the essential safety requirements laid down by Machinery
Directive 2006/42/EC, by low-voltage Directive 2006/95/EC and by Electro-
Magnetic Compatibility 2004/108/EC and subsequent amendments and
integrations.

Indicative picture:

The sensor has an identification label placed on the side of the sensor tube
indicating its serial number and production date, along with some other data.
______________________________________________ Page 4 of 11

2 Description of theequipment
2.1 Main parts

FLUO LM2 has 2 main parts

1- LM2-type TRANSMITTER / RECEIVER SENSOR BAR


2- B016 CONTROL BOARD for FLUO LM2 sensor

FLUO LM2 SENSOR

FLUO LM2 sensor is made of 2 parallel bars between which slides the fabric.
The distance between the bars is fixed, but the mechanical length and the inner
quota that determine the active reading areas are defined based on the final use
of the machine.
One of the two bars is a blinking infra-red light emitter, the other one receives the
light possibly attenuated by the fabric sliding between the tubes.
An automatic system determines the intensity of the light through two appropriate
DARK and LIGHT signals, the self-adapting system is suitable for any type of fabric,
ensuring optimal reading.
The reading tube is divided in 2 parts: RIGHT and LEFT, the electronic system
determines the direction in which the fabric will be moved and triggers an
adjustment signal proportional with the run-out, allowing the actuators connected
to the adjustment outputs to restore the fabric to its appropriate position.

The maximum length of the cables connecting the FLUO LM2 sensor to the B016
control board is of 10 metres, should you require grater connection distances,
please contact Bianco S.p.A.

CAUTION: FLUO LM2 sensor should be connected to PE (GROUND) using the


appropriate copper strips supplied along with the machine.

CAUTION: The cables used for connecting the sensor tube to the control board are
screened cables, please consult the wiring diagram for their connection.

CAUTION: Make sure that the tube configuration is suitable for installation, the
sensor is available in different covers: polycarbonate or coated in silicone for high
temperatures, you can also choose from several types of side plugs, based on the
necessary IP protection level and on the final installation site.
______________________________________________ Page 5 of 11

CONTROL BOARD B016

Control board B016 communicates with FLUO LM2 sensor. with the external
analogue and digital I/O and with the centring adjustment actuators.

CAUTION: Board B016 should be supplied using +24VDC and not 24VAC as for the
previous C212 control board of FLUO LM1 system

2.2 Compatibility with the previous system, FLUO LM1


B016 is an update to the previous C212 board, the analogue functions available on
C212 are now digitally controlled, the new board s more versatile and its
parameters can be customised by the operator.
The best features in C212 can still be found in B016, such as options C366
(advanced adjustment controls) and C216 (board RESET).
B016 also features additional options that help: customising the settings, simplifying
the calibration procedure, connecting to other devices using suitable serial
protocols.
The two boards are not interchangeable as their wirings, supply (C212=24Vac,
B016=+24Vdc) and mechanical fasteners differ completely.
______________________________________________ Page 6 of 11

3 Conditions of Use
Make sure that the ambient temperature does not exceed the operating limits set
for the sensor and control panel, make sure that there are no vapours, as they may
affect the measuring or the system performance. If using the machine in humid
environments or if the temperatures do not match the ones intended, please make
sure to use a suitable configuration of FLUO LM2 tube sensor.

4 Operator workstation
Under normal conditions of use, the only task of the operator is to decide whether
to operate the centring system in AUTOMATIC mode or in MANUAL mode using the
keys MAN+/MAN-, and to define the central position of the fabric by setting it using
the BALANCING potentiometer connected to B016 control board.
______________________________________________ Page 7 of 11

5 Installation and start-up


CAUTION: Installation operations must be carried out by qualified staff.

5.1 Equipment assembly


5.1.1 Preliminary check

Remove the packaging from the equipment and make sure all parts are intact.
Check if the power supply is suitable.

CAUTION: Board B016 should be supplied using +24VDC and not 24VAC as for the
previous C212 control board of FLUO LM1 system

CAUTION: Make sure that the tube configuration is suitable for installation, the
sensor is available in different covers: polycarbonate or coated in silicone for high
temperatures, you can also choose from several types of side plugs, based on the
necessary IP protection level and on the final installation site.

5.1.2 Anchoring the sensor tube

Fasten FLUO LM2 sensor tube to the machine structure, making sure that the fabric
passes between the tubes without touching them.
If possible, avoid installing the system in places with strong lighting or heating
sources, as they might affect the system performance.

Fasten the pair of sensor tubes using the suitable side brackets and connect the
grounding strips.

5.1.3 Vibrations

Avoid the transmission of harmful vibrations caused by installing incorrectly levelled


devices or by connecting it to other machines using brackets. The vibrations might
harm the measuring and electronic equipment.
______________________________________________ Page 8 of 11

5.1.4 Installing the control board

Fasten the control board B016 or the electric panel in which it is placed, connect
the sensor tube, the supplies, and the auxiliary accessories such as potentiometers,
buttons, limit switches, actuators, reference or exchange signals.

CAUTION: Carefully follow the wiring diagram supplied with the machine.

5.1.5 Accessibility

You should be able to open completely the access doors to the control panel in
order to carry out the maintenance operations. You should be able to reach the
sensor upper cover in order to remove it if necessary and access the internal
boards.
The bulbs installed in the control panel should be visible.

5.1.6 Heat sources

Avoid placing the electric cabinet near direct heat sources or vapour jets. Avoid
direct exposure to sunlight.

5.1.7 Cleaning the sensor

Do not use water jets to clean the sensor, unless the tube configuration allows it.

Clean using a wet cloth, do not use solvents as they may dull the protective
covering of the tube.
______________________________________________ Page 9 of 11

5.2 Electrical system

5.2.1 Line speed reference

In order to enable some advanced features (RESET and adjustment proportional


with line speed) you should connect the system to a “proximity” PNP-type inductive
sensor in order to detect the belt speed.
Then you should set the suitable parameters in order for B016 control board to
correctly detect the speed, consulting the appropriate sections, that refer to
software use, in this instructions manual.

CAUTION: Place the speed sensor near a drive roller or an idle roller in order to
ensure correct belt speed detection. Do not use the rollers placed in sections with
speed boost settings as the detected data will be distorted.

5.2.2 Exchange of enabling signals and messages to the outside

See the wiring diagram provided with the machine and


the wiring diagrams of the equipment connected to the line in order to plan
and coordinate a correct use of the enabling signals, paying particular
attention to the safety circuits

FLUO LM2 system can communicate with the line on which it is installed,
sharing the adjustment signals, measuring signals, contacts for exceeding set
tolerance thresholds, enabling signals or any other type of signals.
______________________________________________ Page 10 of 11

5.3 Machine commissioning.


5.3.1 Preliminary checks

CAUTION: Check all wirings, overall power supply from control panel, proper
connection of sensor tubes and all other connections related to B016 board.

CAUTION: Board B016 should be supplied using +24VDC and not 24VAC as for the
previous C212 control board of FLUO LM1 system

5.3.2 System start-up and calibration

Power board B016 and make sure that it starts up, on the 3-digit display should
appear the following message (scrolling):

“dd-mm-yyyy FLUOrx Vz.z”

Where:
dd-mm-yyyy represents the issue date for the software version installed on the B016
board

x represents the hardware revision of the B016 board

z.z represents the software version currently installed on B016 board

Proceed with the calibration of FLUO LM2 sensor tube, only after carefully reading
the next paragraphs in this manual in order to understand the operating mode of
the B016 board and how to set the software functions or check and set the
configuration parameters.
______________________________________________ Page 11 of 11

6 Disposal
DECOMMISSIONING
If the equipment becomes inactive, it is recommended that you remove it from
service or to affix to the same a warning note, clearly visible.

The machine is built with steel, aluminium and plastic


components: therefore, much of the material can be recycled.

When dismantling the equipment, we recommend you separate the different


materials for subsequent recycling or dispose them of separately.
No materials used to construct the control panel and user interface are toxic or
dangerous to operators' health, therefore they can be handled without taking
special precautions.

The sensor and the electronic boards should be disposed of in compliance with the
relevant national laws in force.

WARNING! The electronic boards should be disposed of in


compliance with the relevant national laws in force

WARNING! The equipment should be dismantled at the end of its


service life by qualified personnel who is trained and knows how
to correctly handle - and possibly disassemble - the machine.
Only use equipment and lifting apparatus that is appropriate
and complies with the standards and laws in force.
______________________________________________ Page 1 of 13

Attachment B016 CONTROL BOARD FOR FLUO LM2


- Description of the Hardware functions -

Table of contents
1 FLUO LM2: CONTROL BOARD B016 ...................................................................... 2 
1.1 General description ................................................................................................... 2 
1.2 Compatibility with the previous system, FLUO LM1 .............................................. 2 
1.3 Functional limitations for B016 board...................................................................... 3 
1.4 Terminals description ................................................................................................. 3 
1.4.1 Terminal M1 – Solenoid valves – .................................................................................... 5 
1.4.2 Terminal M2 – Power supplies –...................................................................................... 5 
1.4.3 Terminal M3 – Sensor tubes FLUO LM2 TX and RX – .................................................... 5 
1.4.4 Terminal M4 – analogue inputs and outputs – ............................................................ 6 
1.4.5 Terminal M5 – relay auxiliary functions –....................................................................... 6 
1.4.6 Terminal M6 – opto-insulated digital inputs – .............................................................. 7 
1.4.7 Terminal M7 – auxiliary serial lines .................................................................................. 7 
1.5 Fuses installed on board B016 .................................................................................. 8 
1.6 Wire bridges, Switches, Buttons and Jumper for Board B016 ............................. 9 
1.7 LED Board B016 ......................................................................................................... 11 
1.8 Trimmer and Test Point Board B016 ....................................................................... 13 
 
______________________________________________ Page 2 of 13

1 FLUO LM2: control board B016


1.1 General description

Control board B016 communicates with FLUO LM2 sensor. with the external
analogue and digital I/O and with the centring adjustment actuators.

CAUTION: Board B016 should be supplied using +24VDC and not 24VAC as for the
previous C212 control board of FLUO LM1 system

1.2 Compatibility with the previous system, FLUO LM1


B016 is an update to the previous C212 board, the analogue functions available on
C212 are now digitally controlled, the new board s more versatile and its
parameters can be customised by the operator.
The best features in C212 can still be found in B016, such as options C366
(advanced adjustment controls) and C216 (board RESET).
B016 also features additional options that help: customising the settings, simplifying
the calibration procedure, connecting to other devices using suitable serial
protocols.
The two boards are not interchangeable as their wirings, supply (C212=24Vac,
B016=+24Vdc) and mechanical fasteners differ completely.
The sensor tubes FLUO LM1 and FLUO LM2 are not compatible:
FLUO LM1 sensor can communicate with C212 board and if appropriate measures
are taken, it can also communicate with B016 board while the new FLUO LM2
sensor can communicate only with B016 board and should never be connected to
C212 board. For optimal performance, please use sensor FLUO LM2 with control
board B016.
______________________________________________ Page 3 of 13

1.3 Functional limitations for B016 board


Description Value Notes
Supply voltage +24Vdc (+/-10%) Do not use 24Vac
Consumption 1.5 - Amperes
Operating temperature 0-60°C
Maximum environment 0-90% Non-condensing
humidity
Cables length 10 metres For any other information please
B016 board–LM2 sensor contact Bianco S.p.A.
Maximum allowed 24Vdc + 10%
voltage on digital inputs
Maximum allowed 10Vdc + 10%
voltage on analog inputs

1.4 Terminals description

Please refer to the image on the next page.


There are 7 removable terminals, each of them having a different number of
positions in order to clearly identify them.

Terminals use:

M1 (Removable terminal with 3 positions):


Connection of the pneumatic centring system solenoid valves

M2 (Removable terminal with 6 positions):


Power supply connection +24Vdc input and +24Vdc utilities power supply

M3 (Removable terminal with 10 positions):


Sensor tubes connection FLUO LM2 TX and RX

M4 (Removable terminal with 12 positions):


Analogue inputs and outputs connection

M5 (Removable terminal with 8 positions):


Connection of the relay for auxiliary functions

M6 (Removable terminal with 16 positions):


Connection of opto-insulated digital inputs

M7 (Removable terminal with 7 positions):


Connection of auxiliary serial lines

CAUTION: Please connect / disconnect the terminals only after cutting off the
machine power supply, in order to avoid damaging the board or any other
equipment connected to it.
______________________________________________ Page 4 of 13

3 x PROG push buttons


3 x 7 segments
______________________________________________ Page 5 of 13

1.4.1 Terminal M1 – Solenoid valves –


Connection of the pneumatic centring system solenoid valves
Item Name Description Notes
1 RELREG-COM Common static relays solenoid valves Maximum load voltage 24Vdc or
24Vac
2 RELREG-NO+ Cont. N.O Static relay adjustment + The solenoid valves common is
3 RELREG-NO- Cont. N.O Static relay adjustment - protected by fuse F1

1.4.2 Terminal M2 – Power supplies –


Power supply connection +24Vdc input and +24Vdc utilities power supply
Item Name Description Notes
1 +24VDCIN +24VDC supply input “+” +24Vdc +/-10%
2 0VPOT 0VPOT supply input “0V”
3 GROUND Connection to machine GROUND
system
4 +24VAUX +24Vdc output protected by fuse Do not exceed an absorption of
0.5Ampere for external utilities
5 0VPOT Connection 0V external utilities
6 0VPOT Connection 0V external utilities

CAUTION: Board B016 should be supplied using +24VDC and not 24VAC as for the previous
C212 control board of FLUO LM1 system

NOTE: The wire bridge that connects 0V and PE (GROUND) should be performed in a single
point of the machine, usually inside the main panel, near the +24Vdc power supply of the
board B016.
Avoid such a connection by maintaining the 0V suspended only if noticing that the overall PE
connection is poor and that the disturbances caused to the PE by the motors, inverter or
screened cables, affect system performance, in such conditions, please keep the 2 potentials
PE and 0V separate in order to avoid affecting the measuring accuracy and in extreme cases,
damaging the devices.

1.4.3 Terminal M3 – Sensor tubes FLUO LM2 TX and RX –


Sensor tubes connection FLUO LM2 TX and RX
Item Name Description Notes
1 +TRM Conn. Sensor tube TX supply +
2 -TRM Conn. Sensor tube TX supply -
3 GROUND GROUND connection tube TX
4 +RCV Conn. Sensor tube RX supply +
5 -RCV Conn. Sensor tube RX supply -
6 DARK-IN Input DARK signal
7 LIGHT-IN Input LIGHT signal
8 LEFT-IN Input LEFT signal
9 RIGHT-IN Input RIGHT signal
10 GROUND GROUND connection tube RX

Connect the screen of the GROUND cables.


______________________________________________ Page 6 of 13

1.4.4 Terminal M4 – analogue inputs and outputs –


Analogue inputs and outputs connection
Item Name Description Notes
1 +10VREF Potentiometers power supply Max 5mA summing up M4.1 + M4.5
2 SENS-AN Input SENSITIVITY Level (0/10Vdc) Enable inp. From parameter “S.n.S”
3 BILC-AN Input BALANCING Level (0/10Vdc) Enable inp. From parameter “B.I.L”
4 0VANEXT 0V / Potentiometers power supply
5 +10VREF Potentiometers power supply Max 5mA summing up M4.1 + M4.5
6 ALARM-AN Input ALARM THRESHOLD Level Enable inp. From parameter “A.L.L”
(0/10Vdc)
7 AZGAIN-AN Input HOMING DEVICE GAIN In the current software version, the
input is used to connect the
Level(0/10Vdc)
temperature sensor of the receiver
tube, if provided.
8 0VANEXT 0V / Potentiometers power supply
9 REF+ Output +/-10V for adjustment + Differential output, RIF- represents the
RIF+ differential (Eg.: If REF+=+6.5V REF-
10 REF- Output +/-10V for adjustment - =-6.5V and vice versa).
11 0VANEXT 0V reference signals
12 GROUND Connection SCH of the screened
cables

1.4.5 Terminal M5 – relay auxiliary functions –


Connection of the relay for auxiliary functions
Item Name Description Notes
1 +24VOUTREL: Output +24VOUT for external utilities Max 0.5Ampere
2 RELAUX-COM Common static relays for Inverter
unlocking or lamp control
3 RELAUX-NO1 Contact static relay or lamp “-“ Max 0.3Ampere
4 RELAUX-NO2 Contact static relay or lamp “+“ Max 0.3Ampere
5 0VRELE 0V connection for external utilities
6 RELALARM- Common alarm Relay
COM
7 RELALARM-NO Alarm relay N.O. contact Max 0.3Ampere
8 RELALARM-NC Alarm relay N.C. contact Max 0.3Ampere
______________________________________________ Page 7 of 13

1.4.6 Terminal M6 – opto-insulated digital inputs –


Connection of opto-insulated digital inputs
Item Name Description Notes
1 +24VOUTDIGIN Common +24V digital inputs Max Absorption 200mA
2 AUTO_OC AUTO / MAN Input AUTO = 1, MAN = 0
3 MAN_OC+ Input Button MANUAL + If both keys are pressed, the machine
does not perform any action
4 MAN_OC- Input Button MANUAL -
5 VMIN-AUTO-EN Input MINIMUM SPEED If VMIN-AUTO-EN = 0 prevents AUTO
6 SPEED1_OC-PNP Inp. sens. Speed Proximity or Line speed sensors
SPEED NOTE
Encoder
7 SPEED2_OC-PNP Inp. sens. Speed Proximity or
Encoder
8 +24VOUTDIGIN Max Absorption 200mA
9 LIMITSW_OC+ Inp. limit switch direction “+” If 0 prevents the “+” adjustment
10 LIMITSW_OC- Inp. limit switch direction “-” If 0 prevents the “-” adjustment
11 LIMITSW_ZERO Input ZERO position of the limit ZERO NOTE:
switch
12 GEN-MOVE-EN Input Enable movement If 0 prevents the outputs adjustment in
AUTO and MAN.
13 HOM-EN Input Enable HOMING
14 AUX-IN Input Free for future use
15 0V-OPTO 0V opto-insulated for reference OPTO NOTE
16 GROUND Connection SCH of the screened
cables

GENERAL NOTE: Each of the 12 opto-insulated inputs requires an input current of


about 8mA.
OPTO NOTE: All 12 opto-insulated inputs refer to 0V-OPTO M6.15 that is shorted on
board B016 in a single point with 0VPOT, therefore 0V-OPTO has the same power of
0V of input supply voltage.
SPEED NOTE: The speed sensors operation depends on board B016 parameters
setting. You can connect either a Proximity PNP using only one input or an encoder
using both inputs.
ZERO NOTE: Used to park the centring actuator in neutral position during certain
operations, compatible with the Software version installed on board B016

1.4.7 Terminal M7 – auxiliary serial lines


Connection of auxiliary serial lines
Item Name Description Notes
1 RS485+ Serial connection RS485+ Preset for future expansion of MODMUS
line towards PLC
2 RS485- Serial connection RS485-
3 0VSER 0V reference serial lines
4 CAN+ Serial connection CAN+ Line CAN BUS connection lines
property of BIANCO
5 CAN- Serial connection CAN-
6 0VSER 0V reference serial lines
7 GROUND Connection SCH of the screened
cables
______________________________________________ Page 8 of 13

1.5 Fuses installed on board B016

F2 F4

F1 F3

Item Description Notes


F1 Common relay output for valves control If necessary, replace any burnt
fuses using spare parts with similar
Glass fuse 5x20mm
values to the ones installed on the
F2 Common outputs ALARM relay board.
SMD fuse
F3 Overall protect.+24Vdc power supply
Glass fuse 5x20mm
F4 Common outputs RELAUX-NO1, NO2
SMD fuse
______________________________________________ Page 9 of 13

1.6 Wire bridges, Switches, Buttons and Jumper for Board B016

B8 B9 SW1 SW2

PB1 PB2 PB3

Item Description Notes


B8 RESET: By closing this wire bridge you will During normal operation, please
keep opened B8 and B9.
(OFF) RESET the system
B9 BOOT: This wire bridge should be closed
(OFF) when performing the software update
using the USB connected to the PC
SW1 1 Termination serial CANBUS Follow the indications in the
machine wiring diagram with
(NOTE1) 2 Pull-dw serial line RS485- respect to the default
3 Termination serial RS485 configuration.
4 Pull-up serial line RS485+
SW2 1 Address station MODBUS LSB Not used if MODBUS
communication not provided.
(NOTE1) 2 Address station MODBUS MSB
3 Enable impulse adjustment NOTE2
4 Enable parameters editing NOTE3
5 Doubling the sensitivity NOTE4
6 Default parameters initialization NOTE5
7 Enable calibration mode NOTE6
8 HW Test Mode NOTE7
______________________________________________ Page 10 of 13

NOTA1: To view the default configuration of these switches, please follow the
machine wiring diagram.

NOTE2: When impulse adjustment mode is enabled, the valves output is enabled
by impulses, allowing small movements.

NOTE3: If SW2.4 is OFF parameters display and editing mode is not accessible, After
installing and commissioning the machine, set SW2.4 to OFF to make sure that no
parameters can be accidentally changed.

NOTE4 : If the switch is ON the sensitivity value is doubled for parameters or for
analogue input.

NOTE5: If the switch is ON during board start-up or RESET the parameters are
restored to their default values, after performing this operation you cannot return to
the previously set values. After resetting the parameters, always set SW.6 to OFF
otherwise the parameters will be reset each time you start the device.

NOTE6: By setting SW2.7 to ON you can perform the system calibration. please
consult the relative paragraph in the user manual.

NOTE7: By setting SW2.7 to ON you will enable the board's functional testing mode.
This procedure should not be performed by the end user, it should be performed
only at BIANCO S.p.A. headquarters and it requires particular skills and devices.
Proceeding with this procedure at the end user's site can be dangerous because
the board I/O do not follow the machine's operating logic and may damage the
board or the machine.
Always leave SW2.8 set to OFF.
______________________________________________ Page 11 of 13

1.7 LED Board B016


LD14
LD12
LD5 LD4 LD2 LD9 LD10 LD13 LD15
LD11

LD1

LD3

LD6 LD7 LD8 LD16 LD17 LD18

Item Color Description


LD1 RED ON when contact RELREG-NO+ on M1.2 is closed
LD2 RED ON when contact RELAUX-NO1 on M5.3 is closed
LD3 RED ON when contact RELREG-NO- on M1.3 is closed
LD4 RED ON when contact RELAUX-NO1 on M5.4 is closed
LD5 RED ON when contact RELALARM-NO on M5.7 is closed
LD6 GREEN Always ON, presence of internally generated voltage +12/-12V
LD7 GREEN The intensity of the light indicates the amount of power generated by TX tubes
LD8 GREEN Always ON, presence of supply voltage for RX tubes
LD9 GREEN Always ON, presence of internally generated voltage +5V
LD10 GREEN Always ON, presence of internally generated voltage +3.3V
LD11 RED Blinks when serial RS485 transmits data
LD12 GREEN Blinks when serial CANBUS receives data
LD13 GREEN Blinks when serial RS485 receives data
LD14 RED Blinks when serial CANBUS transmits data
LD15 RED Blinks if there is data on the USB line
LD16 GREEN Blinks whenever an input or a button changes its state NOTE 1
LD17 YELLOW Blinks when light adjustment is not performed NOTE2
LD18 RED Blinks if a system error occurred NOTA3
______________________________________________ Page 12 of 13

NOTE1: This LED blinks whenever a digital input, a dip-switch or a button changes
state, it can be used to make sure that the accessories work properly, if this LED
does not signal the state change (for example when a button is pressed), there
might be a connection error or the control board might be damaged.

NOTE2: This LED blinks when there is no fabric between the TX and RX sensor tubes.
It also blinks during the sensor tubes calibration procedure.

NOTE3: It turns on if there is a system error such as: board B016 overheating, wrong
level of supply voltage, loss of already set parameter values, other system errors. If
an error is detected the LED blinks and the error description scrolls on board B016
display, the system continues to display the error message even if the cause of the
error was removed, in order to make it disappear you have to RESET the board.
______________________________________________ Page 13 of 13

1.8 Trimmer and Test Point Board B016

TP2 TP3 TP4 TP5 TP7 TP6

TP1

P1 P2 P3 P4 TP8 TP9 TP10

Trimmer
Pos. Description Notes
P1 Trimmer DARK sensor channel calibration Channels “DARK”, “LIGHT”, “LEFT”,
“RIGHT” should be calibrated in
order to adapt or compensate the
P2 Trimmer LIGHT sensor channel calibration reading sensitivity features of each
P3 Trimmer LEFT sensor channel calibration sensor tube.
P4 Trimmer RIGHT sensor channel calibration
Test Point
Item Description Notes
TP1 Test point 0VPOT

TP2 Test point for “DARK” signal These test points are used
when the calibration procedure is
TP3 Test point for “LIGHT” signal performed using an external
TP4 Test point for “LEFT” signal multimeter, referred to as 0V-ADJ
TP5 Test point for “RIGHT” signal (please consult the calibration
TP6 Test point 0V-ADJ procedure).

TP7 Test point 0VDG


TP8 Test point 0VAN
TP9 Test point 0VAN
TP10 Test point 0VDG
______________________________________________ Page 1 of 13

Attachment B016 CONTROL BOARD FOR FLUO LM2


- Description of the Software functions -

Table of contents
1 FLUO LM2: SOFTWARE BOARD B016 .................................................................... 2 
1.1 General description ................................................................................................... 2 
1.2 Software Functions not implemented yet ............................................................. 3 
1.3 Main display ................................................................................................................ 4 
1.4 Secondary parameters display ............................................................................... 5 
1.5 Parameters menu display and editing ................................................................... 6 
1.6 Description of the machine parameters ............................................................... 7 
1.7 Sensor tube calibration procedure ......................................................................... 9 
1.7.1 Calibration using an external multimeter .................................................................. 10 
1.7.2 Calibration using the function “Sensor tube calibration parameters display” .... 12 
 
______________________________________________ Page 2 of 13

1 FLUO LM2: Software board B016


1.1 General description

You can perform any control or setting function using the 3 buttons “-“, “+”, “P”
and the 3-digit red display.

The system offers 4 different display levels:

1) MAIN DISPLAY
2) SECONDARY PARAMETERS DISPLAY
3) PARAMETERS MENU DISPLAY AND EDITING
4) SENSOR TUBE CALIBRATION PARAMETERS DISPLAY

This chapter contains detailed descriptions of all software functions that refer to:

Hardware Revision of B016 board B016R1


Revision of the assembly board REL00
Software version V0.4
Release date of the software version 11-05-2015

Any other Hardware or software versions than the ones indicated in the table might
affect the machine operation mode, please contact Bianco S.p.A. technical
support service if in possession of such versions.
______________________________________________ Page 3 of 13

1.2 Software Functions not implemented yet


The software version described in this manual does not include the following
functions:

 RESET Control
 Control of the meter counter and Speed SENSOR
 MODBUS serial protocol
 CANBUS serial protocol
 Advanced control of the process regulator
 Advanced control of the system errors
 Zero limit switch control for parking in neutral position

These functions will be gradually integrated in future software versions.


______________________________________________ Page 4 of 13

1.3 Main display


By closing the wire bridge B8 RESET while the board is being power supplied or after
performing a RESET, on the display appears a scrolling message featuring the
information below:
The name of the device, the board hardware revision, the software revision, the
date of creation of the software revision.

dd-mm-yyyy FLUOrx
Vz.z
Where:
String Description
represents the issue date for the software version installed on
dd-mm-yyyy
the B016 board
dd=day, mm=month, yyyy=year
represents the hardware revision of the B016 board
x
represents the software version currently installed on B016
z.z
board

This message appears only if no system errors are present, otherwise, it is replaced
by the error description

ErruCC 18.9

For example, string “ErrUCC” indicates that the supply voltage exceeds the limits
24V+/-10%, being of 18.9Vdc.

If an error is detected, besides the error message, LED LD18 (red coloured) will also
switch on

The system continues to display the error message even if the cause of the error
was removed, in order to make it disappear you have to RESET the board.

The system errors that are taken into consideration are indicated below:

1) Supply voltage out of allowed range (< 21.5V and >26.0V)


2) Board B016 temperature out of allowed range (>70°C)
3) The memory where the machine parameters are saved is damaged
4) The memory where the board software is saved is damaged
5) Damage of the system memory

The errors are only displayed, they do not block the machine operation.
______________________________________________ Page 5 of 13

1.4 Secondary parameters display

Starting from the main display, you can view certain operation parameters.

By pressing keys“+” or “-“ you can view and scroll through the following
parameters:

rFb 0.83

P
rFa -9.6

+ - -9.6

UPS 24.2
+ -

S°C 45.9

t°C 35.7

Each parameter is alternately displayed, the value of each parameter appears on


the display (blinking).
By pressing key “P” you can keep that specific value steadily lit, to go back to
scrolling display mode, press once again “+” or “-“.

To exit secondary parameters display press at the same time keys “+” and “-“.

Meaning of the secondary data:

Data Description
It represents the difference between the 2 measuring sections
rFb
of the LEFT and RIGHT sensors, when there is no fabric in the
device, a value closer to zero indicates a more accurate
calibration.
It represents the output voltage on RIF+ measuring analogue
rFA
signals, this value takes intro account the set SENSITIVITY level
and the balancing level
It represents the supply voltage of the board B016, expressed
UPS
in volts.
Represents the temperature inside the sensor tube on receiver
S°C
side expressed in °C. The temperature sensor is connected
only in FLUO modules suitable for use at high temperatures; in
standard FLUO the input of the B016 is unused and the data
has no meaning.
It represents the temperature of the environment in which the
t°C
B016 board is installed, expressed in °C
______________________________________________ Page 6 of 13

1.5 Parameters menu display and editing

In order to access the parameters menu make sure that the dip-switch SW2.4 is ON,
otherwise you will not be able to perform any operation.

You can access this menu only from “Main display”, therefore if you are in
“Secondary parameters display” exit this page following the instructions in the
previous paragraphs.

You can access the menu by holding key “P” for 5 seconds.

P P +
InS S.n.S. 27.6 32.0
b.I.L. 27.6
0
-
A.L.L.
C.E.n. 7.5
PId C.t.P. 0
C.A.P. 0.0 P
+ - E.n.C. 0.0
E.C.I. 0
ALL S.F.I. 0
S.E.t. 11
-.-.-. 2.0
-.-.-.
---

1. You can scroll through the desired table using buttons “+” and “-“
2. You can access the desired table by pressing button “P”
3. Each parameter in the table is displayed along with its value, that flashes
alternately with the set value
4. By pressing button “P” once again you can access the parameter editing
menu
5. You can change the parameter value using keys “+” or “-“
6. Press button “P” once again to confirm the parameter set and to return to
table mode view.
7. To exit a table, scroll down until reaching the exit cell, marked with “-.-.-.”,
and press “P” to confirm the action
8. To exit the menu, scroll down through the table list until reaching the exit
cell, marked with “-.-.-.”, and press “P” to confirm the action

If after changing a parameter's value you do not perform the proper table exiting
procedure, as described at points 7, and 8, The new value will not be saved and
will be lost at the next machine restart.
______________________________________________ Page 7 of 13

1.6 Description of the machine parameters

There are 3 tables with parameters: “Ins”, “PId” and “ALL”, in the current software
version you can manage only some parameters in the table “Ins”

Parameters in Table “Ins”


Parameter Default Min Max U.f.m. Description
S.n.S. 27,6 0 100 % Reading sensitivity
b.I.L. 0 -99 99 % Balancing
A.L.L. 0,75 0 10 V Alarm threshold
C.E.n. 0 0 2 n Enable reset (*)
C.t.P. 0,0 0 100 n Reset pitch (*)
C.A.P. 0,0 0 100 % Reset layer width (*)
E.n.C. 0 0 999 n Number of impulses of the encoder or of
the phonic wheel (*)
E.C.I. 0 0 999 mm Circ. encoder or impulses frequency (*)
S.F.I. 11 1 999 n Number of signal averages
S.E.t. 2,0 0.1 9.9 V Setpoint for light adjustment (*)
F.r.q. 150 40 400 mS Impulse regulation period
-.-.-.

(*) = parameter that cannot be managed in the current software version, the
modification of these parameters does not affect the machine operation.

Below are described only the parameters that can be changed:

S.n.S. Reading sensitivity


By increasing the sensitivity you increase the responsiveness of the machine, the
default value of 27.6% represents the standard calibration performed on the
previous version of the sensor, FLUO LM1, based on board C212.

By setting this parameter to 0 the sensitivity data will be diverted to SENS-AN


analogue input, on terminal M4.2, where 0V at input represents 0% and 10.0Vdc at
input represents 100%.

If setting the dip-switch SW2.5 to ON, the sensitivity set for that parameter or for the
external potentiometer will be doubled.

B.I.L. Balancing
The balancing represents the centring offset, if set to 0 the fabric will be kept in the
centre, if set to a different value, the fabric will be kept on a side, at a distance
proportional to the BALANCING value set, the sign of the parameter indicates the
side on which the fabric will be moved.

By setting this parameter to 0 the balancing data will be diverted to BILC-AN


analogue input, on terminal M4.3, where 5.0Vdc at input represents 0%, 0Vdc at
input represents -99% and 10.0Vdc represents +99%.
______________________________________________ Page 8 of 13

A.L.L. Alarm threshold


This data represents a threshold beyond which the alarm relay having the output
contacts on terminal M5 will be closed. The value is expressed in millimetres.

The value set is compared to the run-out value indicated by the position of the
“rfB” sensor that can be viewed in “Secondary Parameters” page, this value is not
affected by the values set in parameters SENSITIVITY and BALANCING.

By setting this parameter to 0 the alarm threshold data will be diverted to analogue
input ALARM-AN on terminal M4.6.

The alarm relay will be enabled if the set threshold is exceeded for 1.4 seconds and
disabled if the value falls back within the set range for at least 0.14 seconds.

S.F.I. Number of signal averages


The higher this number, the greater the period of time for which the sampled
signals are averaged in order to detect the run-out data.

The default value 11 copies the reading speed set for the previous sensor, model
FLUO LM1 based on board C212.

It may be useful to increase the number of signal averages when the fabric is not
homogenous, but pay attention, because this modification also decreases the
reading speed and in some cases it might cause oscillations during adjustment.

F.r.q. Impulse regulation period


When switch SW2.3 is set to ON, impulse regulation is activated; this parameter
determines the regulation period for the relative operating mode. The value is
expressed in milliseconds.
When impulse regulation is deactivated, SW2.3 set to OFF, this parameter has no
meaning.

“PID” and “ALL” Tables


In this software version, the tables “PID” and “ALL” do not contain any parameters.
______________________________________________ Page 9 of 13

1.7 Sensor tube calibration procedure


The calibration procedure can be enabled by setting the dip-switch SW2.7 to ON,
activating the functions below:

1) The adjustment of the reading contrast is omitted and the power on the
transmitter tubes is forced to maximum.
2) The yellow LED LD17 blinks signalling the absence of the light contrast
adjustment (this LED can blink even before setting switch SW2.7 to ON if no
fabric is being processed)
3) The calibration data display window is enabled.

CAUTION: Before proceeding with the calibration of the sensor tube make sure
that:

A) At least 15 minutes passed from machine start-up in order for the sensors to
reach the operating temperature
B) The tubes are free from any fabric or other objects
C) Both tubes are cleaned

The calibration of the 4 signals (DARK, LIGHT, LEFT, RIGHT) coming from the sensor
tubes can be performed in 2 ways:

1) Using an external multimeter


2) Using the function “Sensor tube calibration parameters display”

We recommend you to perform the calibration using the function “Sensor tube
calibration parameters display” because no external instruments are used (their
accuracy is not known) and the sensor is calibrated taking into consideration the
data detected by the board, compensating for any measuring error.

CAUTION: However, never perform a mixed calibration, in other words never


calibrate some of the channels using an external multimeter and the rest of the
channels using the “Sensor tube calibration parameters display” function.
When performing the calibration using an external multimeter, do not take into
consideration the data indicated on the display of the B016 board, as they may
differ from the ones detected by the multimeter.
______________________________________________ Page 10 of 13

1.7.1 Calibration using an external multimeter

TP2 TP3 TP4 TP5 TP6

P1 P2 P3 P4

CAUTION: Before proceeding, carefully read the previous paragraph “Sensor tube
calibration procedure”.

1) For all measures, please keep the BLACK tip of the multimeter on TP6 “0V-
ADJ” and set the multimeter in Volt DC with 20Vdc full scale

2) By keeping the RED tip on TP2 “DARK” carefully adjust the trimmer P1 until
obtaining 9.00Vdc (+/- 0.01Vdc)

3) By keeping the RED tip on TP3 “LIGHT” carefully adjust the trimmer P2 until
obtaining 9.00Vdc (+/- 0.01Vdc)

4) By keeping the RED tip on TP4 “LEFT” carefully adjust the trimmer P3 until
obtaining 9.00Vdc (+/- 0.01Vdc)

5) By keeping the RED tip on TP5 “RIGHT” carefully adjust the trimmer P4 until
obtaining 9.00Vdc (+/- 0.01Vdc)

After adjusting the 4 trimmers make sure once again that the voltages on the 4
relative test points are 9.00Vdc (+/- 0.01Vdc), otherwise adjust them once again.

After completing the calibration:


______________________________________________ Page 11 of 13

1) set switch SW2.7 to OFF

2) Insert the fabric between the sensor tubes, the width of the fabric should
exceed by at least 50cm the central part of the tube, not covered by sensors.

3) Make sure that when the fabric is present, the yellow LED LD17 remains off and
does not blink indicating that the light contrast adjustment is properly
performed, suitable for the type of fabric being processed.

4) Start the machine and check the operation of the centring device, if the result
of the adjustment is not appropriate, use the parameters or the external
potentiometers to adapt the SENSITIVITY and BALANCING.
______________________________________________ Page 12 of 13

1.7.2 Calibration using the function “Sensor tube calibration


parameters display”

CAUTION: Before proceeding, carefully read the previous paragraph “Sensor tube
calibration procedure”.

After setting the dip-switch SW2.7 to ON the system switches to “Sensor tube
calibration parameters display” function

By pressing keys“+” or “-“ you can view and scroll through the 4 calibration data
“DARK”, “LIGHT”, “LEFT”, “RIGHT”

d8.9 8.99

P
h9.0 9.00

+ - 9.00

L8.9 8.99
+ -

r9.0 9.00

The name of the channel along with the calibration data (displayed with only one
decimal) and the calibration data at maximum resolution (with two decimals) will
be alternately displayed, blinking.

The channels can be identified as follows:

1) “dx.x” alternated with value “x.xx” represents the calibration value of the
channel “DARK”, press“P” to keep the data display steadily lit (with two
decimals) and use trimmer P1 to adjust 9.00 (+/-0.01)

2) After calibrating the trimmer, press button “+” to start the calibration of the next
channel.

3) “hx.x” alternated with value “x.xx” represents the calibration value of the
channel “LIGHT”, press“P” to keep the data display steadily lit (with two
decimals) and use trimmer P2 to adjust 9.00 (+/-0.01)

4) After calibrating the trimmer, press button “+” to start the calibration of the next
channel.
______________________________________________ Page 13 of 13

5) “Lx.x” alternated with value “x.xx” represents the calibration value of the
channel “LEFT”, press“P” to keep the data display steadily lit (with two
decimals) and use trimmer P3 to adjust 9.00 (+/-0.01)

6) After calibrating the trimmer, press button “+” to start the calibration of the next
channel.

7) “rx.x” alternated with value “x.xx” represents the calibration value of the
channel “RIGHT”, press“P” to keep the data display steadily lit (with two
decimals) and use trimmer P4 to adjust 9.00 (+/-0.01)

8) Use keys “+” and “-“ to make sure that all 4 channels were calibrated,
otherwise proceed with their calibration using a data less accurate than 9.00
(+/-0.01).

After completing the calibration:

5) set switch SW2.7 to OFF and make sure that the display returns to “Main display”
page

6) Insert the fabric between the sensor tubes, the width of the fabric should
exceed by at least 50cm the central part of the tube, not covered by sensors.

7) Make sure that when the fabric is present, the yellow LED LD17 remains off and
does not blink indicating that the light contrast adjustment is properly
performed, suitable for the type of fabric being processed.

8) Start the machine and check the operation of the centring device, if the result
of the adjustment is not appropriate, use the parameters or the external
potentiometers to adapt the SENSITIVITY and BALANCING.

You might also like