Professional Documents
Culture Documents
TABLE OF CONTENTS
1. INTRODUCTION
4.5 Ph MEASUREMENT
4.7 COPPER
1
INTRODUCTION
A chemical cleaning treatment is performed on the boiler water circuits to remove from the
internal surfaces’ impurities such as water hardness scale and treatments, excessive iron oxide
formation, silica compounds, copper-based compounds and other debris, and to establish a
satisfactory magnetite layer.
Such a procedure ensures that optimum boiler water and steam conditions are achieved and
reducing corrosion on heat exchange surfaces.
The method of cleaning on this project is by chemical cleaning and passivation of the
economizer and boiler steam generating sections.
The superheater is excluded from the acid cleaning process and will be protected from chemical
ingress during cleaning by water wedging/plugging.
2
OUTLINE CHEMICAL CLEANING PROCEDURE
Item Operation
4
6.4 Circulate or up to one hour.
6.5 Add further Ammonia solution (approx. 2200 liters 25%) to raise pH to 9.5 to 10.
6.6 Inject chemicals to give the following:
0.5% w/w Sodium Nitrite (500kg)
Circulate for a further 4-6 hours until the dissolved copper concentration is stable.
6.7 Stop pump circulation. Open vents and drain boiler and economizer to effluent
neutralization tank until completely empty.
6.8 Neutralization and treat effluent in the pit until acceptable for discharge, then pump to
effluent point at waste water treatment plant
8 Stage 8- Inspection
8.1 Disconnect temporary connections from boiler pressure parts, open both steam
drum doors and allow internal parts to ventilate and dry out from heat in the
metal.
8.2 Inspect at steam drum, remove sample coupons (if used), and manually remove
and debris lying in low-flow areas. Inspect at other terminal points as agreed. On
acceptance, release boiler for pressure parts reinstatement.
NOTE: In order to conduct these Site Analysis methods, we need the support from
LISCO Chemical Laboratory with LISCO manpower
5
APPENDIX A SAFETY RULES
Storage
All chemical products must be stored and labelled in accordance with the instructions on the
safety sheet.
Chemicals must not be stored together with inflammable material and gas cylinders.
Do not store acids and alkalis together.
Do not store strong acids and organic substances together.
Do not store strongly oxidizing substances together with oxidizable substances.
Eithers and other peroxide-building substances must be stored in the dark and cool, in tightly
sealed containers.
Chemical containers must be stored with closed lids when they are not being used.
Refrigerators and freezers for storage of chemicals must be of such a type that is specially made
for this purpose. Chemicals and similar items must not be stored in refrigerators or freezers that
are intended to store food.
Chemical stores must not have open floor drains. If there is a floor drain, it must be equipped
with protection to prevent leakage. This means for example tight fitting lids, a manual opening
and closing function in the drain or other comparable arrangement.
Equipment for handling and cleaning up spillage must be in readiness and suitable for the
chemicals that are stored. It is suitable to have equipment placed outside the chemical store.
It is important for the fire classification of storage lockers and rooms to match the types and
amounts of chemicals stored therein.
Combustible material must be stored in fireproof cupboards or in separate spaces.
Labelling
Chemicals must normally be stored in their original packaging. If you need smaller amounts
of a chemical, the new packaging must be suitable for the substance. Labelling must be in
accordancewiththeoriginalpackaging.Itmustalwaysbepossibletoknowwhatsubstancethe
packaging contains and what risks there may be.
Handling of chemicals
Always read the safety data sheet and the text on the packaging carefully when you are about
to use a product with which you are not completely familiar with the risks. Contact the
environmental coordinator if you are unsure about handling methods.
Use personal protection equipment (e.g., gloves, face mask) where necessary.
Surplus chemicals and hazardous waste must be dealt with in accordance with the information
in the safety data sheet.
First Aid equipment must be available.
Workplaces must be cleaned regularly. There must not be chemical spills on the floor.
Personal hygiene
Smoking is forbidden in the factory area outside specially assigned smoking areas. If you
smoke, remember to wash your hands before lighting up a cigarette. Otherwise, chemical
substances can be transferred by skin contact or breathed in.
Immediately wash off chemical traces from the skin. Read the safety data sheet or ask your
immediate superior if you are not sure what needs to be done.
Food products must not be stored or eaten in premises where chemicals are handled.
Work clothes must be kept clean. If you have been in contact with chemicals, take a shower
before you go home.
6
APPENDIX B ANALYTICAL METHODS
Introduction
Inhibitors are added to acids during chemical cleaning to reduce the rate at which the
acid attacks the metal in the system, normally to negligible levels (say 1-2% of uninhibited
corrosion rate). Normally the only metal normally requiring protection in chemical cleaning is
iron, in the form of carbon steel.
When an acid e.g Hydrochloric Acid, reacts with iron it produces hydrogen gas.
2 HCI+Fe àFE CI₂ + H₂
Thus the production of appreciable amounts of hydrogen indicate that the acid is attacking
the steel in the system.
The inhibitor test consists of the addition of a small ball of clean steel wool to a sample of
the acid solution. If the inhibition is poor then hydrogen will be evolved. The hydrogen
bubbles formed will normally adhere to the surface of the wire or become trapped in the
body of the ball. Since the ball of steel wool has a very large area for its weight, once a few
bubbles have formed it will tend to float to the surface.
Equipment
Steel Wool NOTE: The most suitable grade is 00 (fine). Coarser grades have a lower
surface area to weight ratio and are therefore less sensitive. New steel wool is normally
covered by a protective layer of grease or oil and this must be removed before use. This is
most easily done by washing several times in a volatile solvent. e.g., Acetone or Genklene.
After cleaning the wool is highly susceptible to rust and must be stored in a dry sealed
container with some silica-gel dessicant.
Procedure
Tear off a portion of the clean steel wool and roll into a ball about the size of a small
pea. Drop the ball into a beaker containing 50-100 cm³ of the hot acid solution, ensure the ball
is fully wetted and observe for two minutes. (NOTE: For citric acid solutions, the test
temperature should not be more than 80⁰ C as above this the ball may float even in a fully
inhibited solution.)
Evaluation of Results
In normal conditions if the ball remains submerged then the inhibition is satisfactory.
If it rises to the surface, or refuses to sink, then the inhibition is not satisfactory, the most
frequent causes being-
9.7.1 Poor mixing of inhibitor with the acid solution.
9.7.2 Too high and acid strength due to poor mixing or excessive acid addition
rates.
9.7.3 Wrong inhibitor for the acid being used.
7
9.7.4 Wrong materials being handled, caused normally by using unmarked or
wrongly marked containers.
Procedure
If a colorimeter is to be used switch on and allow to warm up for at least 15 minutes.
Filter the sample if necessary to remove suspended solids and allow to cool.
Take 100 microliter of sample (or other quantity-see Notes below) using micromasterpipette
and transfer to 100 cm³ volumetric flask.
Add 20-30 cm³ water, then 2 drops of Thioglycollic Acid and mix.
Addanexcess(approx.0,5cm³)ofAmmoniasolution,makeuptothe100cm³mark with water and
mix thoroughly. The colour should develop almost immediately.
Transfer sufficient quantity of the colour solution to a 1cm. glass cell. Zero the colorimeter to
0(%absorbance)or100(%transmittance)withasimilarcellcontainingdemineralisedwater, then
measure the transmittance T or absorbance A as per the colorimeter instructions.
At the end of sampling session, switch off the colorimeter.
For the Lovibond Comparator add the colour solution to one glass cell to approx 2/3 full and
add demineralized water to the other cell. Place the cells in the instrument with the
coloured cell in the centre. Holding the device up to the light rotate the disc until the nearest
match is made between the two coloured circles. Read off the absorbance A from the
bottom right- hand number hole.
Colorimeter Standardization
For the first in a set of readings it is recommended to standardize the colorimeter as follows:
Conduct the above determination but using a suitable volume (often 200ul) of Standard1000
ppm Fe solution to give a midpoint reading. Read the transmittance Ts or absorbance As.
Calculation
9
For 100ul sample taken:
ppm Iron = A x100000
For a volume V ul sample taken:
Ppm Iron = A x 100000000/ V
Chemical Reagents
Cationic exchange resin (in Hydrogen H⁺ form)
e.gZerolit 325, Dowex 50-W-X8(H)
Standard Sodium Hydroxide solution 0.5 molar (0.5N)
Phenolphthalein indicator
Apparatus
250 cm³ & 100 cm³ conical flasks
Reservoir bottle & 10 cm³ auto burette for 0.5M
NaOH. Pipettes 10 & 20cm³ and safety pipette filler
2 x Plastic filter funnel
No. 1 filter papers
25 cm³ plastic measuring cylinder
Glass wool
Wash bottle for demineralized water
Procedure
Filter the sample if necessary, to remove suspended solids and allow to cool.
Add a slurry of resin to the measuring cylinder until, after settling, the resin volume reaches
approximately 10 cm³. Transfer the resin to a clean 100cm³ conical flask, rinsing a few times
10
with demineralized water if necessary. When all the resin has been transferred, decant off
excess water from the resin.
Using a safety pipette filler, pipette 10cm³ (for 2-3% acid cleans) or 20 cm³(for citric rinses
and passivation’s) of the sample on to the resin in the flask. Swirl gently to mix and allow to
stand for 5 minutes, occasionally swirling the flask to thoroughly mix the contents (Flask A.)
Place a small plug of glass wool lightly in the mouth of another clean plastic filter funnel or a
filter paper and place the funnel in a 250 cm³ conical flask(Flask B). Decant the solution from
Flask A through the funnel into Flask B taking care to keep as much resin as possible in Flask
A. Rinse the walls of the funnel with 2-3 cm³ water into Flask B.
Add 10-20 cm³ water to Flask A, swirl briefly and again decant through the plugged funnel as
above info Flask B. Rinse funnel again with 2-3 cm³ water.
Wash the resin twice more as above. If any beads of resin have collected in the funnel , rinse
them thoroughly, allowing the funnel to empty between rinsing’s. Finally place the empty
funnel in Flask A.
Add 3-6 drops phenolphthalein indicator to the solution in Flask B, zero the auto burette and
titrate against the standard sodium hydroxide solution. Allow the solution to just turn pink
andthenstoptitrating.PlacethepluggedfunnelinFlaskB,addafurther10-20cm³waterinto the
resin in Flask A, swirl briefly and again decant through the funnel into Flask B. Continue
titrating dropwise as above until the solution turns pink once more. If three drops or less of
Sodium Hydroxide solution are required the end point has been reached, if not perform
another 10-20 cm³ rinse. Note the final burette reading Vcm³.
Empty Flask B of the solution and rinse out well. Once again rinse the resin in Flask A and
discard the rinse water. Finally discard any resin in the funnel, then place the empty funnelin
Flask B. Drain excess water from the resin. The resin may be used for the next
determination.
Calculation
For a solution containing only citric acid, ammonia and dissolved iron, the cidric acid
concentration is found as follows:
Total Citric Acid (%w/v) = V cm³ x 0,32 (for 10cm³ sample)
Total Citric Acid (%w/v) = V cm³ x 0,16 (for 20cm³ sample)
Free Citric Acid (%w/v) = Total Citric Acid – (3,4 x Iron*)
* See notes below.
TOPIC: pH MEASUREMENTS
REFERENCE: pH/S/01
METHOD: Determination of pH of Chemical Cleaning solutions.
Theoretical Considerations
The pH of a solution is a measure of its acidity or alkalinity. The pH scale runs from O (very
acidic) to 14 (very alkaline). At pH 7 acidity is equal to alkalinity, i.e. the solution is neutral.
TechnicallypHisdefinedasminusonemultipliedbythelogarithmtobase10oftheHydrogen ion
concentration, i.e.:-
11
The precise measurement of pH is conveniently carried out electrically and many commercial
electronic pH meters are available. The method used relies on placing two different electrodes
in the solution to be measured and measuring the voltage produced between them. One
electrode is known as a "reference" electrode while the other is a "glass" electrode. The glass
electrode is the one which produces a varying output, depending on the pH of the solution. In
most modern meters the two electrodes are combined in a single unit often referred to as a
"combination pH electrode". This is the type used with the WPA E1 Suitcase Laboratory kit.
Due to ageing effects in the electrode(s) it is essential to set up a pH meter to read correctly by
using solutions whose pH is accurately known. Such solutions are known as buffer solutions.
Once set up, the calibration will last for about 24 hours, but less if the instrument is repeatedly
switched on or off.
Accuracy
When ammonium bifluoride has been added to cleaning solution, there in will convert it to
HF acid which contributes towards the total titration value.
The correction is 2,244 x (%w/w Bifluoride added.) The correction is as % Citric Acid and is
to be subtracted from the Total Citric Acid as calculated above.
For 10 cm³ sample containing 0.5% w/w Ammonium Bifluoride
Total Citric Acid (%w/v) = (V cm³ x 0,32)- 1,122
Notes
The calculation for free citric acid is based on the reaction between iron scale and citric acid
producing Ferrous Hydrogen Citrate (monoammonium Fe II citrate):
CH₂---------COO⁻
HO --------C ------- COO⁻ Fe²⁺
CH₂--------COO⁻ NH₄⁺
This is certainly what is formed with an excess of citric acid. Calculations based on forming
thisproductshowanIronsaturationlevelof8820ppm(0.87%w/w)for3%citricacidsolution.
However,thisisnotthesaturationlimitforcitricacidasfurtherreactioncantakeplaceleading to the tri
ferrous dicitrate salt. This gives a true saturation level of 13000 ppm Fe (1.3% w/w) for a 3%
citric acid solution.
In addition to the above in the presence of oxidizing conditions a corrosive reaction known as
‘’ferric ion corrosion’’ can occur. This is particulary severe in solutions of high Iron
concentrations, say above 6000-7000 ppm (0,6-0,7 % w/w) when it tends to become self-
supporting.
Fe(III) citrate + 0₂ àFe(III) citrate
2(Fe(III) citrate) + Fe à3(Fe(II) citrate)
The first reaction above occurs more easily the higher the pH of the solution becomes. The
overall reaction is unaffected by the presence of inhibitors and in fact as it is a metal surface
reaction it can, in some cases, interfere with normal ‘’surface coating’’ action of the inhibitor
giving the appearance of inhibitor breakdown.
For the above reasons it is not good practice to exceed 7000 ppm Fe during a 3% w/w citric
acid clean, nor to allow the free citric acid level to fall below 0.5% w/w. It is neither good
practicetosupplementthestrengthof‘’dirty’’acidsolutionsbyadditionoffurthercitricacid, as has
been common practice in the past. The solution should be drained and the acid stage
repeated, if agreed with the client.
12
SYSTEM: Site Analysis Method
13
SYSTEM: Site Analysis Method
TOPIC: Copper
REFERENCE: Cu/S/01
METHOD: Colorimetric determination of Copper in process solutions using
Biscyclo hexanone Oxaldi hydrazone Reagent
Theoretical Considerations
BiscyclohexanoneOxaldihydrazone(BCHorBCODH:C₁₄H₂₂N₄O₂)reactswithcopperionsin
ammonical solution to give a blue coloured complex. The intensity (depth) of colour is
proportional to the amount of copper ions in solution(i.e. the copper concentration). High iron
contentinthesamplewillpreventtheformationofthecoppercomplex,henceafluoridebuffer is
added to overcome this.
Chemical Reagents
BiscyclohexanoneOxaldihydrazone. Dissolve 0.25g BCH in 100 cm³ of 50%w/w Ethanol
(Ethyl Alcohol C₂H₅OH) - water solution. Allow to cool.
Buffer solution. Dissolve 50g Citric Acid (A.R. Grade) in 200cm³ distilled water. Solution
(Solution A). Dissolve 25g ammonium fluoride, NH4F (A.R. Grade) in 100cm3 in a plastic
beaker(Solution8).AddsolutionAandBto150cm³0.880Ammonia(A.R.Grade-35%w/w); mix,
cool and dilute to 500cm³ with distilled water.
Caution: Ammonia is Toxic, Fluorides are toxic and corrosive.
Standard Copper Solution (1000 ppm Cu)
15
Apparatus
Spectrophotometer capable of measuring at approx. 595nm (595 x 10⁻⁹₅ m) e.g:-
E1 colorimeter fitted with No. 7 filter at Lo-intensity
100cm³ volumetric flasks
Micromaster or Eppendorf pipettes and disposable tips
Plastic filter funnel
No. 1 filter papers
Wash bottle for demineralised water
Procedure
If a colorimeter is to be used switch on and allow to warm up for at least 15 minutes.
Filter the sample if necessary to remove suspended solids and allow to cool.
Take 100 microlitres (µI) of sample (or other quantity - see Notes below) using micromaster
pipette and transfer to 100cm³ volumetric flask.
Colorimeter Standardization
For the first in a set of readings it is recommended to standardize the colorimeter as follows:-
Conduct steps to 4.7 above but using 100µ1 of Standard
1000 ppm Copper solution. Read the transmittance Ts or absorbance As.
Calculations
Calculate the Standardization Factor Q by the formula:-
Q = 1000 or 1000
--------- ----------
(2 - log Ts) As
From the standardization factor the Copper concentration of the sample may be calculated as:-
For 100µl sample taken:-ppm
Copper = (2 - log T) x Q or:
ppm Copper = A x Q
For a volume V µI of sample taken:-
ppm Copper = (2 - log T) x Q x 100/V
or: ppm Copper = A x Q x 100/V
Notes
For initial Copper removal stage (500-2000ppm) take 100µl sample
For Second Copper removal stage (20-400ppm) take 500µl-5c
16
CHEMICAL CLEANING PROCEDURE / Operational Log
Time/Date
Sign of
Stage Activity Comments/ Deviations
Start Finish Initials
2 Initial Filling
Set up valves for filling boiler. Fill boiler tonormal
2.1 working level (monitor at steam drum temporary
gaugeglass).
17
Start up 1x temporary Chemical cleaning pump and
2.6
commence pumping into system.
18
4. Citric Acid Rinse
19
5.5 (repeat) Draining boiler.
6 Copper Removal
6.6
Inject chemicals to give: 10g/l (1.0%w/w) Citric Acid
(1000 kg anhydrous), Ammonia to achieve pH 3.5-
Take samples every
4.0 (approx.200 20check
litres, minutes and monitor.
by sampling)
Continue circulation depending on analysis for at
6.7 least 1 hour, but no more than 2 hours.
7. Ammonia Rinse
Start pumps and commence filling economiser and
7.1
boiler. Commence backflush the superheater into
8. Inspection
Disconnect temporary connections from boiler
pressure parts. Open steam drum door and allow
8.1 internal parts to ventilate and dry out from residual
heat in the metal.
20
Inspect at drum, manually remove any debris
lying in low-lying areas. Inspect at other terminal
8.2 points as required by client. On acceptance
release boiler for pressure parts reinstatement.
The List of Chemicals required for Boiler Chemical cleaning according to the above procedure is given below:
21