Professional Documents
Culture Documents
5 Closed Loop Control
5 Closed Loop Control
Page 1 of 3
Figure 5.2: PLC for closed-loop control
Modes of control
With proportional control the controller gives an output to the
actuator which is proportional to the difference between the
actual value and the set value of the variable, i.e. the error
(Figure 5.3(a)). Such a form of control can be given by a PLC
with basic arithmetic facilities. The set value and the actual
values are likely to be analogue and so are converted to digital
and then the actual value is subtracted from the set value and
the difference multiplied by some constant, the proportional
constant KP, to give the output, which after conversion to
analogue is the correction signal applied to the actuator:
controller output=K p x error
Page 2 of 3
Proportional control has a disadvantage in that, because of
time lags inherent in the system, the correcting signal applied
to the actuator tends to cause the variable to oscillate about
the set value. What is needed is a correcting signal which is
reduced as the variable gets close to the set value. This is
obtained by PID control, the controller giving a correction signal
which is computed from a proportional element, the P term, an
element which is related to previous values of the variable, the
integral I term, and an element related to the rate at which the
variable is changing, the derivative D term. With integral
control the controller output is proportional to the integral of
the error with time, i.e. the area under the error-time graph
(Figure 5.3(b)).
controller output=k I x integral of error withtime
Page 3 of 3