44- 1121- 32, Rev .

RF-2000 Round Fire Damper


Installation Instructions
Part No. 44-1121-32, Rev. C
Issued March 2016

Applications
The RF-2000 round fire damper is designed to operate
with blade running horizontally. Dampers can be
vertically or horizontally installed with the leading edge
of the closed blade within the wall or floor.
To ensure optimum operation and performance, the
damper must be installed so it is round and free from
raking. Do not compress or stretch the damper frame
into the duct or opening.
• Mounting - Vertical or Horizontal.
• Minimum UL Classified Size - 6 in. (152 mm)
diameter.
• Maximum UL Classified Size - 24 in. (610 mm)
diameter.
Installation
Notes
Use the following notes as guidelines when installing
this product. Figure 1: Retaining Cinch Plate Dimensions,
in. (mm)
1. Opening Clearance: A square opening in wood or
metal stud walls or masonry walls and floors shall
be a minimum of 1 in. (25 mm) and a maximum of Fasten the cinch plates to the wall or floor
2-1/2 in. (64 mm) larger than the damper diameter. according to the following:
A round opening in masonry walls or floors shall • Masonry Wall – Cinch plate required on only
be a minimum of 1 in. (25 mm) and a maximum of one side of the wall fastened to the wall with a
2-1/2 in. (64 mm) larger than the damper diameter. minimum of 1-1/4 in. (32 mm) #10 masonry
2. Damper Sleeve: The sleeve is integral to the screw.
damper and shall be equal to or heavier than the • Masonry Floor – Cinch plate required on both
gauge of the duct as described in National Fire sides of the floor fastened to the floor with a
Protection Association (NFPA) standard NFPA90A minimum of 1-1/4 in. (32 mm) #10 masonry
and as defined by the appropriate Sheet Metal and screw.
Air Conditioning Contractors’ National Association
(SMACNA) duct construction standard. • Metal Stud Wall – Cinch plate required on only
one side of the wall fastened to the wall by
3. Retaining Cinch Plates: Place retaining cinch engaging the metal stud a minimum of
plates around the damper sleeve and cinch against 1/2 in. (13 mm) with a #10 screw.
the sleeve with the screw provided on the cinching
device (see Figure 1). The plates are designed to
grab and hold the sleeve while mounting flush
against the wall or floor, retaining the damper
securely in the opening. The plates must overlap
the opening a minimum of 1/2 in. (13 mm).

RF-2000 Round Fire Damper Installation Instructions 1


• Wood Stud Wall – Cinch plate required on both • Precision - PA2084T
sides of the wall fastened to the wall by
• ECO Duct Seal 44-52
engaging the wood stud a minimum of
1-1/2 in. (38 mm) with a #10 screw. • Design Polmerics - DP1010

WARNING: Risk of Personal Injury. Note: Install the damper so that it is square and free
Do not place cinch plates in the groove. If from raking. Compressing or stretching the damper
! the cinch plates are in the groove, the frame into the duct or opening may result in failed
operation and will void the warranty.
damper is not properly secured. An
insecure damper may dislodge and fall,
IMPORTANT: Do not lift the damper using the
which may result in severe personal
blades or actuators. Lift or handle the damper using
injury or death.
the frame or sleeve. Handling or lifting the damper
AVERTISSEMENT : Risque de by the blades or actuator may damage the damper
blessure. and will void the warranty. Do not compress or
Ne pas placer les plaques de retenue stretch the damper frame into the duct or opening.
dans la rainure. Si les plaques de retenue
se trouvent dans la rainure, le registre IMPORTANT: Examine each smoke damper on a
coupe-feu n'est pas correctement fixé. regular basis to ensure it is not rusted or blocked. In
Il pourrait alors sortir de son logement et addition, test each smoke damper annually or semi-
de tomber, ce qui risque de provoquer annually, depending on the application, and
des blessures graves, voire mortelles. according to the National Fire Protection Association
(NFPA) standards, to ensure it will perform as
4. Damper Orientation: The leading edge of the intended. Exercise care to ensure that such tests
blade in the closed position must be within the are performed safely and do not cause system
plane of the wall. Vertical installation is illustrated damage.
and horizontal is similar. (See Figure 3 through
Figure 6.) The damper may be installed with up to 6. Optional Sealant of Dampers in Fire Rated Wall
a 30 degree variance of the axle being horizontal. or Floor Openings: Following the sealant
The damper is approved with airflow in any manufacturer's directions, remove dirt, grease, and
direction. moisture from the surface to be sealed. Apply a
continuous bead of sealant to the location
applicable to your specific installation.
Approved sealant or fire stop materials:
• Dow Corning® - 999A, Silastic 732RTV
• GE® - RTV 108
Figure 2: Blade Orientation
• Hilti Corporation - FS-One
5. Duct/Sleeve Connections: Round breakaway • 3M® - #M-CP 25WB+
connections must be used. Either a 4 in. (102 mm)
• Specified Technologies, Inc. - SpecSeal®
wide draw band or #10 sheet metal screws spaced
Series SSS or LCI
equally around the circumference of the ducts as
follows: • John Manville International, Inc. - Firetemp™
• duct diameters of 22 in. (559 mm) and smaller CI
– three screws • Rectorseal - Metacaulk 1000, Metacaulk 350i,
• duct diameters over 22 in. (559 mm) to 24 in. Biostop 500+ or Biostop 350i
(610 mm) – five screws Do not apply sealant within the required expansion
Note: When optional sealing of these joints is gap between the damper and the fire rated wall or
desired, the following sealants may be applied in floor.
accordance with the sealant manufacturer's Press the surface of the sealant in place to dispel
instructions: any air. Allow sealant to set up and become tack-
• Hardcast, Inc. – Iron-Grip™ 601 sealant free before operating the damper.

2 RF-2000 Round Fire Damper Installation Instructions


Note: If opening size allows for angle on one side
only, then sealant shall be applied on only angle side.
Nothing is required on non-angle side.
Installation Diagrams
Figure 3 and Figure 4 illustrate installation in
1 and 2 hour rated masonry floors and ceilings or walls.

Figure 4: Masonry Installation, Side View

Note: Masonry walls require retaining cinch plates on


only one side of the wall, as shown. Floors require
retaining cinch plates on both sides of the floor.
Figure 5 and Figure 6 illustrate installation within
Figure 3: Masonry Installation, 3 Dimensional square openings in metal or wood stud framing
(3D) view incorporating 1 and 2 hour rated drywall partitions.

Figure 5: Metal Stud Installation, 3D view

RF-2000 Round Fire Damper Installation Instructions 3


Figure 6: Wood & Metal Stud Walls, Side View
Figure 7: Wooden Stud Wall Framing
Dimensions, in. (mm)
Screws must penetrate wood or metal studs.
Metal stud walls require retaining cinch plates on only 4. Consult the authority having jurisdiction for other
one side of the wall. Wood stud walls require retaining acceptable framing methods.
cinch plates on both sides of the wall.
Recommended Framing for Openings in Wood
and Metal Stud Walls
1. Frame wall openings as shown in Figure 7 and
Figure 9.
2. Double vertical studs are not required for openings
36 in. wide x 36 in. high (914 mm x 914 mm) or
smaller.
3. All construction and fasteners must meet the
requirements of the appropriate wall design for Figure 8: Wood Stud Construction
local, regional, and national codes.

4 RF-2000 Round Fire Damper Installation Instructions


Figure 9: Metal Stud Wall Framing Dimension,
in. (mm)

Figure 10: Metal Stud Construction

European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
WESTENDHOF 3 507 E MICHIGAN ST C/O CONTROLS PRODUCT MANAGEMENT
45143 ESSEN MILWAUKEE WI 53202 NO. 22 BLOCK D NEW DISTRICT
GERMANY USA WUXI JIANGSU PROVINCE 214142
CHINA

Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.

RF-2000 Round Fire Damper Installation Instructions 5

Published in U.S.A. www.johnsoncontrols.com