Professional Documents
Culture Documents
Application Note
The arcing contact is the first to make a contact during a close operation and the last
to break contact during an open operation. Circuit breaker will have the arcing contact wear
under normal operation as well as when breaking circuit under a short-circuit current. If the
arcing contact is too short or in a poor condition, then the breaker soon becomes unreliable.
It should be remembered that excessive arcing-contact wear and/or misalignment
might result in decreasing the CB’s breaking capacity because of changing the arcing contact
surface that cause reducing dielectric strength. Main contact surfaces can be deteriorated by
A-CBR108-201-EN
Since the resistance is important for analysis, it is calculated for each sample by
Ohm’s law as RINST=VDC/IDC. RINST represents instantaneous resistance values. That means
the injected current (IDC) also needs to be measured. Dynamic resistance curve as a function
of the time is generated on the basis of these instantaneous resistance values obtained for
each sample.
In order to extract all diagnostic parameters related to condition of the arcing contact,
dynamic resistance curve and motion curve should be plotted simultaneously and
overlapped (as shown for an opening operation in the Figure 2.), or the resistance curve
should be plotted as a function of the contact travel (as shown in the Figure 3.). These
graphs are generated by DV-Win software. If needed to see values at ordinate for all
mentioned curves, then the view presented in the Figure 4. is suitable for that. To enable
A-CBR108-201-EN
this view it is needed to select option Switch view in the DV-Win in options above the graph.
2
Figure 2. Dynamic resistance curve and motion curve as function of the time
The resistance curve starts as a straight line before the breaker starts to move
(Figure 2, 3 and 4). This represents the main contact resistance. As the contact starts to
move, small fluctuations of the main contact resistance can appear (can be seen easier in
the Figure 3.). When the main contacts separate, there is a spike in the resistance curve
(because higher resistance of the arcing contact) and after that the arcing contact resistance
can be measured. When the resistance goes to infinity, it means the breaker is open.
Resistance curve as a function of a contact travel can be used to reveal failures
related to arcing contact position. For example, the highest spike of the resistance curve in
the Figure 3. indicates change in the arcing contact condition. Spike can appear in resistance
curve due to transition, but in that case it is a short-term event. Since this spike is a long-term
event, it indicates a bad contact or contact bounce at opening.
The most important diagnostic parameters (extracted in the Figure 2.) that are used
to assess the condition of the main and arcing contacts are:
Arcing contact wipe (overlapping distance)
Arcing contact overlapping time.
These parameters can be used to determine a length condition of the arcing contact,
i.e. to measure a length reduction of the arcing contact. In cases when the contact motion is
not recorded (becomes impossible to determine Arcing contact wipe), Arcing contact
overlapping time can be useful to assess condition of the breaker contacts, especially when
A-CBR108-201-EN
.
Figure 3. Dynamic resistance curve as function of the contact travel
Figure 4. Display of curves (resistance, motion, voltage drop) with values at ordinate