Power Transformer

2
Index sheet
This Photo by Unknown Author is licensed under CC BY

4
Commissioning Services Department
CSD- East

Why do we need Transformers in electrical Network ???

Why electrical power not transfer direct from generation to distribution ???

What is the important type of transformer ??

How Transformer Work ???

5
Commissioning Services Department
CSD- East

6
Commissioning Services Department
CSD- East

step-up transformer is used to increase the voltage


and reduce the current. ...
Less current means less energy is lost through
heating the wire. Less Voltage Drop-less cost

7
Commissioning Services Department
CSD- East

Type of insulation :
1. Oil transformer 2. dry transformer

Type of using :
1. Power transformer 2. measurement transformer 3. testing transformer 4. welding transformer

Winding number :
1- 3-phase transformer (3-winding) 2. 1-phase transformer (1-winging)
Commissioning Services Department
CSD- East

It is important to remember that transformers do not generate electrical power; they


transfer electrical power from one AC circuit to another using magnetic coupling. The core of
the transformer is used to provide a controlled path for the magnetic flux generated in the
transformer by the current flowing through the windings, which are also known as coils.

9
Commissioning Services Department
CSD- East

When an input voltage is applied to the primary winding, alternating current starts to flow in
the primary winding. As the current flows, a changing magnetic field is set up in the
transformer core. As this magnetic field cuts across the secondary winding, alternating voltage
is produced in the secondary winding.
The ratio between the number of actual turns of wire in each coil is the key in determining the
type of transformer and what the output voltage will be. The ratio between output voltage
and input voltage is the same as the ratio of the number of turns between the two windings.
A transformers output voltage is greater than the input voltage if the secondary winding has
more turns of wire than the primary winding. The output voltage is stepped up, and
considered to be a "step-up transformer". If the secondary winding has fewer turns than the
primary winding, the output voltage is lower. This is a "step-down transformer."

10
Commissioning Services Department
CSD- East

11
Commissioning Services Department
CSD- East

12
Commissioning Services Department
CSD- East

13
Commissioning Services Department
CSD- East

14
Commissioning Services Department
CSD- East

15
Commissioning Services Department
CSD- East

16
Commissioning Services Department
CSD- East

17
Commissioning Services Department
CSD- East

18
Commissioning Services Department
CSD- East

19
20
Commissioning Services Department
CSD- East

21
Commissioning Services Department
CSD- East

22
Commissioning Services Department
CSD- East

23
Commissioning Services Department
CSD- East

24
Commissioning Services Department
CSD- East

Data Shell be filled in format as per details from Nameplate


,valve schedule plate, factory acceptance test report, approved

25
Commissioning Services Department
CSD- East

26
Commissioning Services Department
CSD- East

27
Commissioning Services Department
CSD- East

28
Commissioning Services Department
CSD- East

29
Commissioning Services Department
CSD- East

30
Commissioning Services Department
CSD- East

31
Commissioning Services Department
CSD- East
Commissioning Services Department
CSD- East

Check list for Commissioning of Oil-Immersed Power Transformer Index Number:CL-NG-6460-002-018

1- Winding Insulation Resistance and Polarization Index test

2- Core and frame insulation

3-Measurement of winding resistance (DC) (at all taps)

4-Measurement of no load current (Excitation Current- MAGENTISING CURRENT)

5-Percentage impedance (Short circuit impedance) PART-1

6-Magnetic balance test.

7-Measurement of zero-sequence impedance(s)

8-Measurement of turns ratio (for all taps)

9-Vector group at normal tap.

10-Measurement of dissipation factor (tan δ)

33
Commissioning Services Department
CSD- East

Check list for Commissioning of Oil-Immersed Power Transformer Index Number:CL-NG-6460-002-018

11- Frequency test.

12- Calibration of Oil and Winding Temperature Sensors Test

13- Oil Test


PART-2
14- Cooling Fan Motor Test

15- Tests on on-load tap-changers ─ Operation test

16- Functional Check of the following

34
Commissioning Services Department
CSD- East

Winding Insulation Resistance and

Polarization Index test transformer testing

35
Commissioning Services Department
CSD- East

1- Winding Insulation Resistance and Polarization Index test

Objective
To measure the condition of a major insulation system (the insulating system between a
winding and the ground (core) or between two windings

Test Equipment's :- (mega ohm meters)(Megger)

Test preparation:-
I. Isolate the area by safety warring tape
II. Safety tagging shall be implemented
III. Tester having valid calibration
IV. Clean all Bushing of the transformer
V. May be taken to see that test leads do not touch among themselves and with
Transformer bod
VI. Confirm the tightness of all connections made
VII. Factory test

36
Commissioning Services Department
CSD- East

Test procedure:-
I. Terminals of all HV &LV bushings are shorted together.
II. Connect testing as per connection above with Apply 5 KV DC
III. Measurement insulation resistance and record from 1 minuet to
10 minuets as per test formats
IV. Obtain the Polarization Index= IR at 10Minuet /IR at 1 minuet
V. Acceptable Value IR value > 2M Ω Polarization Index>1.5
Commissioning Services Department
CSD- East

INSULATION INSULATION RESISTANCE WITH 5000 VOLTS TESTER (GΩ)


RESISTANCE
BETWEEN 1 2 3 4 5 6 7 8 9 10
PI
MIN MIN MIN MIN MIN MIN MIN MIN MIN MIN

HV to GROUND 14.8 16.9 18.3 19.3 20.2 20.8 21.6 22.2 22.6 23.0 1.55

LV to GROUND 12.1 14.8 16.5 17.8 18.9 20.2 21.0 22.0 22.8 23.6 1.95

HV to LV 12.2 16.0 19.3 22.0 24.4 26.8 28.6 30.4 32.2 33.8 2.77

Acceptable Value IR value > 2M Ω Polarization Index>1.5


Commissioning Services Department
CSD- East

Core and frame insulation testing

39
Commissioning Services Department
CSD- East

2- Core and frame insulation

Objective
To Ensure the condition of the Insulation resistance core -frame by of measuring the core-to-ground
insulation –frame-to ground and between them

Test Equipment's :- Meggers (mega ohm meters)

Test preparation:-
I. Isolate the area by safety warring tape
II. Safety tagging shall be implemented
III. Tester having valid calibration
IV. Clean all Bushing of the transformer
V. may be taken to see that test leads do not touch among
themselves and with Transformer bod
VI. Confirm the tightness of all connections made
VII. Factory test
VIII. Link to Core and Frame must be removed

40
Commissioning Services Department
CSD- East

I. Test procedure:-
II. Connect testing with applied voltage of 1 KV DC as per test Connection for 1 Min
III. Record the Result insulation resistance on format test
IV. Acceptance Value > 2M Ω
Commissioning Services Department
CSD- East

Measurement of winding resistance (DC)

(at all taps) testing

42
Commissioning Services Department
CSD- East

3-Measurement of winding resistance (DC) (at all taps)

Object :-
Measuring the resistance of the transformer windings ensures that the connections are correct and
the resistance measurements indicate that there are no severe mismatches or opens

Test Equipment's:-
Low Transformer Ohmmeter (MTO330)/ Transformer Winding Resistance Meter(TRM 40)

Test preparation:-
I. Isolate the area by safety warring tape
II. Safety tagging shall be implemented
III. Tester having valid calibration
IV. Clean all Bushing of the transformer
V. may be taken to see that test leads do not touch among
themselves and with Transformer bod
VI. Factory test

43
Commissioning Services Department
CSD- East

Test procedure:-
I. Connect test as per above connection HV / LV winding Resistance all taps and Record test Result
II. Acceptance Value= should be within ±5% of measure in factory test
WINDING RESISTANCE ()
Average
@ AMBIENT TEMP. * Res/ph @
Res /Ph @ Amb. Winding
TAP NO. 75  C
Temp Connection
()
X1-X0 X2-X0 X3-X0 ()

----- 0.00755 0.00755 0.00756 0.007553 0.008672 STAR

44
Commissioning Services Department
CSD- East

Measurement of no load current

(Excitation Current- MAGENTISING CURRENT)

45
Commissioning Services Department
CSD- East

4-Measurement of no load current (Excitation Current- MAGENTISING CURRENT)

Objective :-
I. To confirm no loose contact or loose connection in winding or core.
II. To ensure that there is no shorting in the core material.
III. To ensure no inter turn shorting of winding
IV. To measure current that maintain the magnetic flux excitation in the core

Test Equipment's:- voltmeters and ammeters & 3 phase variable input supply,

Test preparation:-
I. Isolate the area by safety warring tape
II. Safety tagging shall be implemented
III. Tester having valid calibration
IV. Clean all Bushing of the transformer
V. may be taken to see that test leads do not touch among themselves and with
Transformer bod
VI. Confirm the tightness of all connections made
VII. Factory test

46
Commissioning Services Department
CSD- East

Test procedure:-
I. Connect as per connection
II. Three phase voltage applied on HV side, by
keeping LV, TV side open.
III. Current measurement carried at HV terminals.
IV. IO% =Average Current /Average Voltage *rated
Voltage/rated current *100
V. Excitation current should not be higher than the
guaranteed value by more than 30%.

47
Commissioning Services Department
CSD- East

MAGNETIZING CURRENT AT
APPLIED VOLTAGE AT
secondary
Tap
Rated Rated
Pos Avg. Avg. Current
Tap Tap Io%
PRIMARY Voltage WINDING IN mA (A)
Voltage Current
WINDING(V)

H1-H2 H2-H3 H3-H1 IH1 IH2 IH3

1 418000 693 366.4 383.2 376.8 375.46 1.5 1.9 1.9 0.00176 0.28

9 380000 763 364.5 380.6 375.5 373.53 2.1 2.5 2.2 0.00266 0.354

21 323000 897 368.00 382.1 370.8 373.63 2.8 3.6 4.8 0.00373 0.359

AVERAGE CURRENT RATED TAP VOLTAGE


Io= ____________ × ________________ *100
AVERAGE VOLTAGE RATED TAP CURRENT

48
Commissioning Services Department
CSD- East

Short circuit impedance measurement

49
Commissioning Services Department
CSD- East

5-(Short circuit impedance)

Objective:-
1- To determine copper losses at full load –to obtain parameters the equivalent circuit
2-To check the occurrence of any inter-turn shorting or shift of the winding during transportation

Test Equipment's :- Ammeter, Voltmeter and Wattmeter.

Test preparation:-
I. Isolate the area by safety warring tape
II. Safety tagging shall be implemented
III. Tester having valid calibration
IV. Clean all Bushing of the transformer
V. may be taken to see that test leads do not touch among
themselves and with Transformer bod
VI. Confirm the tightness of all connections made
VII. Factory test

50
Commissioning Services Department
CSD- East

Test procedure:-
I. Connect test as per above connection (LV shorted)
II. Inject 380 V Power supply at Primary Side (lower tap, normal tap and higher tap.
III. Measured current and Voltage between phases as per above and calculate =
IV. Z=(applied voltage/measured current ×rated current/rated voltage)×100
V. Acceptance Criteria 10 % of specified value

51
Commissioning Services Department
CSD- East

Acceptance Criteria 10 % of specified value

52
Commissioning Services Department
CSD- East

Magnetic balance test

53
Commissioning Services Department
CSD- East

6-Magnetic balance test

Objective:-
The purpose of this test is to check whether the flux path in the core is uniform and
properly distributed in the core limbs
identify inter turn faults and magnetic imbalance

Test Equipment's :- Ammeter, Voltmeter and Wattmeter.

Test preparation:-
I. Isolate the area by safety warring tape
II. Safety tagging shall be implemented
III. Tester having valid calibration
IV. Clean all Bushing of the transformer
V. may be taken to see that test leads do not touch among themselves and
with Transformer bod
VI. Confirm the tightness of all connections made
VII. Factory test

54
Commissioning Services Department
CSD- East

Test Procedure
I. Inject 220 V/230 V Single phase as per connection above and reading voltage other phases
II. The Sum of these two voltages should give the applied voltage
III. If there is any inter-turn short circuit that may result in the sum of the two voltages not being equal to the applied
voltage
Injection
H1-H0 H2-H0 H3-H0 X1- X0 X2-X0 X3- X0 Y1-Y2 Y2-Y3 Y3-Y1
(V)
H1-H0 219.2 186 22.48 57.52 49.55 4.94 12.22 10.95 1.39
H2-H0 116.1 219.4 102.5 30.17 57.63 27.63 6.25 12.46 6.57
H3-H0 20.57 218.3 218.3 5.20 49.06 57.80 1.46 10.89 12.20

55
Commissioning Services Department
CSD- East

Measurement of zero-sequence impedance(s)

56
Commissioning Services Department
CSD- East

7-Measurement of zero-sequence impedance(s)

Objective
The zero-sequence impedance is usually measured for all star-connected windings of the transformer
measure zero sequence impedance which is necessary for ground fault protection

Test Equipment's:- Ammeter, Voltmeter and Wattmeter..

Test preparation:-
I. Isolate the area by safety warring tape
II. Safety tagging shall be implemented
III. Tester having valid calibration
IV. Clean all Bushing of the transformer
V. may be taken to see that test leads do not touch among
themselves and with Transformer bod
VI. Confirm the tightness of all connections made

57
Commissioning Services Department
CSD- East

Test procedure Zero Sequence :-


1- Connect test as per above connection (LV shorted)
2- Inject 380 V single Power supply at Primary Side (lower tap, normal tap and higher tap )
3- Record the measured (I)-(V)
4- Calculate The Zero Sequence impedance Formula as per
5-

58
Commissioning Services Department
CSD- East

59
Commissioning Services Department
CSD- East

Measurement of turns ratio (for all taps)

60
Commissioning Services Department
CSD- East

8-Measurement of turns ratio (for all taps)

Objective:-
I. To ensure the Turns ratios of the transformer are designed / manufactured as per the
specifications/ requirements.
II. To ensure the Turns ratio errors are within acceptable limits

Test Equipment's :- TTR 330 (Megger)

Test preparation:-
I. Isolate the area by safety warring tape
II. Safety tagging shall be implemented
III. Tester having valid calibration
IV. Clean all Bushing of the transformer
V. may be taken to see that test leads do not touch among themselves
and with Transformer bod
VI. Confirm the tightness of all connections made
VII. Factory test

61
Commissioning Services Department
CSD- East

Test Procedure:-
I. connect the tester as per connection above.
II. Test Ratio at all Taps
Limit :- ± 0.5% of the design
Measured value – Calculated value
* % Error = ------------------------------------------------------- X 100
Calculated value
Compare result with factory report

MEASURED RATIO MEASURED RATIO MEASURED RATIO


A B C
Tap No. HV LV Calc. Ratio
Iexc. Dev. Iexc. Iexc.
Ratio Dev. (%) Ratio Ratio Dev. (%)
(mA) (%) (mA) (mA)

1 79500 13800 9.5263 9.5374 0.12 0.61 9.5347 0.09 0.42 9.5352 0.09 0.68

2 75038 13800 9.4180 9.4295 0.12 0.61 9.4264 0.09 0.48 9.4278 0.10 0.69

3 74175 13800 9.3098 9.3218 0.13 0.63 9.3207 0.12 0.50 9.3212 0.12 0.70

62
Commissioning Services Department
CSD- East

Vector Group

63
Commissioning Services Department
CSD- East

9-Vector Group

Objective:-
To ensure the vector group of the Transformer is designed/ manufactured as
per the specification.

Test Equipment's :- Multimeter,380 VAC supply

Test preparation:-
I. Isolate the area by safety warring tape
II. Safety tagging shall be implemented
III. Tester having valid calibration
IV. Clean all Bushing of the transformer
V. may be taken to see that test leads do not touch among
themselves and with Transformer bod
VI. Confirm the tightness of all connections made
VII. Factory test

64
Commissioning Services Department
CSD- East

Test Procedure:- DY1

I. Apply 380 V 3 phase Voltage to the High

voltage Winding terminal and short

between H1-X1the induced voltages across

the terminals for the following above are

measured.

II. The vector is confirmed as DY1, if the

measured voltages as per the above satisfy

65
Commissioning Services Department
CSD- East

Measurement of dissipation factor (tan δ)

66
Commissioning Services Department
CSD- East

10-Measurement of dissipation factor (tan δ)

The Objective
I. Capacitance and power factor/dissipation factor (PF/DF) measurements are performed to
investigate the condition of the insulation of power transformers and bushings. Both insulation
systems are essential for the reliable operation of the transform
II. To measure the power loss due to leakage current through the transformer insulation
III. To determine material quality of the insulation
IV. The purpose of the measurement is to determine the capacitances between the windings and the
earthed parts and between the different windings of the transformer

67
Commissioning Services Department
CSD- East

10-Measurement of dissipation factor (tan δ)

Test Equipments :-
The Double power factor insulation test equipment measures the charging current and watts-loss from which the
power factor, capacitance

Test preparation:-

I. Isolate the area by safety warring tape

II. Safety tagging shall be implemented

III. Tester having valid calibration

IV. Clean all Bushing of the transformer

V. may be taken to see that test leads do not touch among themselves and with

Transformer bod

VI. Confirm the tightness of all connections made

VII. Factory test

68
Commissioning Services Department
CSD- East

Test Procedure
For Doble equipment, measurement may be done in the following modes.
1CH refers to all insulation between the high voltage winding and grounded parts
CL refers to the same parts and materials between the low voltage windings and grounded parts
CHL refers to all winding insulation, barriers, and oil between high- and low-voltage windings

69
Commissioning Services Department
CSD- East

70
Commissioning Services Department
CSD- East

71
Commissioning Services Department
CSD- East

Frequency Test

72
Commissioning Services Department
CSD- East

11- Frequency Response Analysis

Objective:-
detecting damage arising due to dislocation/ movement of core and winding during transportation
or after occurrence any fault

Test Equipment's :- FRA Analyzer

Test preparation:-
I. Isolate the area by safety warring tape
II. Safety tagging shall be implemented
III. Tester having valid calibration
IV. Clean all Bushing of the transformer
V. may be taken to see that test leads do not touch among
themselves and with Transformer bod
VI. Confirm the tightness of all connections made
VII. Factory test

73
Commissioning Services Department
CSD- East

Calibration of Oil and Winding Temperature

Sensors Test

74
Commissioning Services Department
CSD- East

12- Calibration of Oil and Winding Temperature Sensors Test

Objective:-
This is to ensure proper working of temperature indicators within the acceptable tolerance
according to the actual sensing of temperature.

Test Equipment's :-Heating Calibrator (BROMAN- MODEL 861A /Drywell-Hart Scientific………)

Test preparation:-
I. Isolate the area by safety warring tape
II. Safety tagging shall be implemented
III. Tester having valid calibration
IV. Clean all Bushing of the transformer
V. May be taken to see that test leads do not touch among
themselves and with Transformer bod
VI. Confirm the tightness of all connections made
VII. Factory test

75
Commissioning Services Department
CSD- East

A- Calibration of Sensors By Heating

76
Commissioning Services Department
CSD- East

Test Procedure
1-Temperature calibration test is to be done (of thermometer) Bulb of the temperature relays is
to be taken out from pocket and exposed through some liquid medium to slow temperature
rising. By means of thermometer, temperature of medium is to be check and compared to
temperature relays measuring.

Reference Temp. Oil Temp. Indicator HV Winding LV Winding WTI-The dial marking
in ̊ C in ̊ C Temp. Indicator in ̊ C Temp. Indicator in ̊ C
shall be 20 to 160°C
with ±0.5% accuracy.
starting 31 30 31

40 41 40 41

60 60 60 61 OTI -The dial marking


shall be 20 to 160°C
80 80 80 80
with ±0.5% accuracy.
100 98 99 100

120 119 119 120

140 139 140 140

157 156 157 158

77
Commissioning Services Department
CSD- East

Function Test for OTI/WTI

DEVICE FUNCTION SETTING OPERATION REMARKS

Cooling Fan Start Spare N/A N/A


Oil Temperature Indicator Alarm 95 95 OK
26Q
Trip 105 105 OK

DEVICE FUNCTION SETTING OPERATION REMARKS

Cooling Fan Start 75 75 OK

High Voltage Winding Alarm - 115 115 OK


Temperature indicator 49W1
Trip 125 125 OK

DEVICE FUNCTION SETTING OPERATION REMARKS

Cooling Fan Start 75 75 OK


Low Voltage Winding
Temperature indicator Alarm - 115 115 OK
49W2
Trip 125 125 OK

78
Commissioning Services Department
CSD- East

WINDING TEMPERATURE CALIBRATION BY SECONDARY CURRENT INJECTION

79
Commissioning Services Department
CSD- East

B-CALIBRATION BY SECONDARY CURRENT INJECTION

80
Commissioning Services Department
CSD- East

WINDING TEMPERATURE CALIBRATION BY SECONDARY CURRENT INJECTION

HIGH VOLTAGE WINDING TEMPERATURE INDICATOR:


CT RATIO : 500 / 2 A
HIGH LOAD TAP CURRENT : 420 AMPS
CURRENT INJECTION TO HEATING COIL : 1.68 AMPS

READING
Oil Temp. at start (A) 22
TIME (MIN.) TEMP. READING (° C )
0 22
Oil Temp. at end (B) 23
5 30
10 38
Winding Temp. Before current injection (C) 22
15 40
20 44
Winding Temp. After 45 mins (D) 46
25 45
30 46 Simulated Temp. Rise Measured: [(D-C)-(B-A)] 23
35 46
40 46
45 46

81
Commissioning Services Department
CSD- East

Oil Test-Dielectric strength

82
Commissioning Services Department
CSD- East

13- Oil Test-Dielectric strength

Objective:-
This is one of the points to the ensure condition of oil

Test Equipment's :- Calibrated Oil Tester

Test preparation:-
1- Isolate the area by safety warring tape
2- Safety tagging shall be implemented
3- Tester having valid calibration
4- Position the test equipment on a safe location where possibility
of falling objects is remote to happen..
5- Make sure the bottle is clean and dry
6- Factory test

83
Commissioning Services Department
CSD- East

84
Commissioning Services Department
CSD- East

Test Procedure:-
This test is performed by applying an AC voltage between two
electrodes immersed in an oil sample. When the current arcs
across the gap between the electrodes, the voltage at that instant
is the dielectric breakdown strength

85
Commissioning Services Department
CSD- East

ASTM D 877 ASTM D 1816


This test method uses This method uses
thin flat-faced cylindrical spherically shaped
electrodes with a 2.5 electrodes with a 1 mm
mm gap.), gap.
Tap Changer, LPOF (Low Applied for Power
Pressure Oil Filled) Transformer
Applied Voltage = 3 K Applied Voltage = 0.5 KV

Minimum Strength : 50 KV

86
Commissioning Services Department
CSD- East

Other tested in an independent lab.


Color-Moisture Content-Dissipation Factor Test-Dissolved Gas in
Oil Analysis………….

87
Commissioning Services Department
CSD- East

Cooling Fan Motor Test

88
Commissioning Services Department
CSD- East

13- Fan Test

Objective:-
To ensure the performance of the fan motor

Test Equipment's :-Digital Multimeter with Clamp Meter and megger for IR test

Test preparation:-
1- Isolate the area by safety warring tape
2- Safety tagging shall be implemented
3- Tester having valid calibration
4- Position the test equipment on a safe location where possibility
of falling objects is remote to happen..
5- Make sure the bottle is clean and dry
6- Factory test

89
Commissioning Services Department
CSD- East

90
Commissioning Services Department
CSD- East

Test Procedures:-
1- Perform insulation Resistance testing through terminal block
2-Measure the Motor starting Current for each cooling fan’s 3phases
3-Measure the running Current for each cooling fan’s 3phases
4-Calculate the total starting and Running current of each group
5- Check the Rotation direction of fan’s
6-Operate the fan separately to ensure that each switch is of the same fan
7-The separation of the fan is ensured by its respective switches by a failure representation

91
Commissioning Services Department
CSD- East

92
Commissioning Services Department
CSD- East

Tests on on-load tap-changers ─ Operation test

93
Commissioning Services Department
CSD- East

15- on-load tap-changers Test

Objective:-
To ensure the proper operation / performance of On Load Tap Changer and its compliance with the
requirements.

Test Equipment's :-Digital Multimeter with Clamp

Test preparation:-
1- Isolate the area by safety warring tape
2- Safety tagging shall be implemented
3- Tester having valid calibration
4- Position the test equipment on a safe location where possibility
of falling objects is remote to happen..
5- Factory test

94
Commissioning Services Department
CSD- East

Test Procedures

ITEM DESCRIPTION REMARKS

1 Heater, light OK
.2 One complete operation by motor OK
3 One complete operation by hand crank OK
4 Mechanical lock (lower and upper ) limit. OK
5 Electrical lock (lower and upper) limit. OK
6 Interlocking with hand switch. OK
7 Check local OK
8 Tap position indicator. OK
9 Counter operation. OK
10 Check Control switch local/remote/off OK
11 Check voltage and phase sequence OK
I R (A) IY (A) IB (A)
12 OLTC Motor staring current
4.60 4.71 4.65

95
Commissioning Services Department
CSD- East

96
Commissioning Services Department
CSD- East

97
Commissioning Services Department
CSD- East

Functional Check

98
Commissioning Services Department
CSD- East

16-Functional Check

Objective:-
To ensure the proper operation / performance of of these devices
And to fully perform it

Test Equipment's :-Digital Multimeter with Clamp

Test preparation:-
1- Isolate the area by safety warring tape
2- Safety tagging shall be implemented
3- Tester having valid calibration
4- Position the test equipment on a safe location where possibility
of falling objects is remote to happen..
5- Factory test

99
Commissioning Services Department
CSD- East

Test Procedures:-
1-Check all circuits as per schematic drawing of MK panel and highlight
with yellow if its ok
2- All functions shall be checked as per scheme, checklist, test forms
and settings and all should be recorded in
3- Alarms & trips shall be checked in HMI’s, work stations and
gateways. Trip commands shall be checked actually

100
Commissioning Services Department
CSD- East

DESCRIPTION DEVICE NO. SIGNAL TYPE REMARKS

OIL LEVEL MAIN TANK HIGH LEVEL 71Q1 ALARM OK


OIL LEVEL MAIN TANK LOW LEVEL 71Q1 ALARM OK
OIL LEVEL OLTC HIGH LEVEL 71Q2 ALARM OK
OIL LEVEL OLTC LOW LEVEL 71Q2 ALARM OK
ALARM OK
BUCHHOLZ RELAY MAIN 96B
TRIP
ALARM
PROTECTED RELAY OLTC 96 OK
TRIP
ALARM
PRESSURE RELIEF DEVICE -1 MAIN TANK 63P1 OK
TRIP
ALARM
PRESSURE RELIEF DEVICE -2 MAIN TANK (OLTC) 63P2 OK
TRIP
PRESSURE RELIEF DEVICE - 3 ALARM
63P3 OK
OLTC TRIP
GAS DETECTOR RELAY 63 D ALARM OK
ALARM
PROTECTED RELAY OLTC 96P1 OK
TRIP
ALARM
PROTECTED RELAY OLTC 96P2 OK
TRIP
SUDDEN PRESSURE RELAY 63S TRIP OK

101
Commissioning Services Department
CSD- East

102