You are on page 1of 1

MAN HOLE 0.6 x 0.

SEPTIC TANK COVER SLAB DETAILS

100mmØ VENTILATING PIPE 3.0m HT.


CIA MAN HOLE COVER 0.6 x 0.6
(HEAVY DUTY 250KG)
RCC COVER SLAB 0.20 THK
RCC COVER SLAB 0.15 THK

INSPECTION CHAMBER INSPECTION CHAMBER 0.6 X 0.45

GL GL

150Ø INLET
150Ø OUTLET TO SOAK PIT

12mm THK. PLASTERING


SLOPE 1 : 30

SECTION

INSPECTION CHAMBER 0.6 X 0.45 INSPECTION CHAMBER 0.6 X 0.45

BAFFLE WALL

150Ø INLET IC MAN HOLE IC 150Ø OUTLET


0.6 X 0.6

SEPTIC TANK PLAN

BRICK CHAMBER WITH DRY JOINTS

RCC 1:1.5.3

GL GL

INLET BRICK LINING WITH OPEN JOINTS

BRICK BAT AND BROKEN STONE

BRICK WORK OUTER CASTING


WITH COARSE SAND

SOAK PIT DETAILS

9 SEPTIC TANK & SOAK PIT DETAILS


BD 110

D - CADD DESIGNER'S
ENGINEERING CONSULTANT

IDEAL GEO STRUCT


AADI GROUPS MYSURU
A 10 ,Jaya Nagar,
Ph no. 98-86-471409
Kannankurichi Main Road,
E-MAIL : dileepdcadd@gmail.com
Salem - 8
CONSULTANTS :-

NEW MS/HSD RETAIL OUTLET AT

PROJECT
THADGOLU VILLAGE
INDIAN OIL CORPORATION LIMITED
SEPTIC TANK & SOAK PIT Bangalore Divisional Office
DRAWING TITLE (20 USERS) OWNER

* REFER RELEVANT ARCHITECTURAL DRAWING NOTES: TENDER NTS

BD 110
* DO NOT COPY, RETRACE OR REPRODUCE THIS DRAWING
01. Bend, Hook, Covers & lap length should be taken as per 456-2000. PURPOSE DATE SCALE
WITHOUT THE PERMISSION OF IOCL AUTHORITY.
02. Inspection chamber to be provide on both Inlet & Outlet.
* ALL DIMENSIONS ARE IN METERS UNLESS SPECIFIED OTHER WISE.
* DO NOT SCALE THIS DRAWING.
03. The Invert of the outlet pipe shall be 50mm below the invert of the inlet pipe. AADI DILEEP
04. Provide 150Ø pipe at Inlet & Outlet.
* ANY DISCREPANCY FOUND SHOULD BE BROUGHT TO THE
05. Top Level of cover slab shall be suit at site. KARNATAKA. DRAWN DESIGN BY DRAWING NO.
NOTICE OF THE ARCHITECT IMMEDIATELY. PROJECT DETAILS