Professional Documents
Culture Documents
A quick guide for the construction industry on the Danish Building Regulations 2018
Table of Contents
Energy requirements of the Building Regulations ................................................................................. 3
What energy requirements does BR18 pose? ....................................................................................... 4
Always consider energy and indoor climate ....................................................................................... 5
New buildings ........................................................................................................................... 6
Change of use ......................................................................................................................... 10
Extensions ............................................................................................................................. 11
Conversions and other alterations ................................................................................................. 13
Replacements of building elements and installations .......................................................................... 16
Holiday homes (in designated “summer house” areas) ........................................................................ 17
Requirements for installations ..................................................................................................... 18
Energy solutions and BR18 tools to help you on your way ..................................................................... 19
Change in the Building Regulations’ requirements for energy demand of single family houses 1961-2020
kWh per m2 of
living space
350
300
250
200
150
100
50
0
Average 1961-1979 1979-1998 1998-2006 2006-2010 2010-2015 2015-2020 Low energy class
consumption (voluntary)
for all buildings
calculated in 2010
Figure 1
2
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
The energy requirements are largely the same Building in accordance with BR18 of course requires a
as in BR15. However, the building class 2020 has deeper insight into all of BR18 than this quick guide on
become voluntary rather than statutory also after the energy requirements can provide. The quick guide
2020 and is now included in the regulations as a will, however, be a good primer when it comes to the
low energy class. Further, the structure of BR18 energy requirements of heated buildings.
has changed significantly. It has a new subject and
chapter structure, there are new instructional texts Six categories of construction projects
and attachments as well as a number of linguistic The Building Regulations operate with six different
clarifications. categories of construction projects that differ in
relation to the energy requirements.
This quick guide gives you a quick overview of how to
ensure that the buildings you construct or renovate In order to figure out how to adhere to the Building
live up to BR18’s energy requirements. In the actual Regulations, you should begin by placing your
regulations, these requirements are found in Chapter project in the proper category and finding the proper
11 on energy consumption, in Chapter 19 about paragraphs of BR18.
thermal indoor climate and installations as well For the first five categories, § 250 to § 258 in BR18
as Chapter 22 on ventilation. In addition, there is apply. In addition, there are specific paragraphs for
instructional text to BR18’s Chapter 11 and an Annex 2: each category.
”Tables for Chapter 11 - Energy Consumption”.
* Reparations include paint treatment, mending plaster, plastering the facade, new roof valleys and Figure 2
covering, mending holes in the roof, etc.
3
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
ENTS
L W A Y S R EQUIREM
New buildings A S
A L L AT I O N
Requirements § in BR
F O R I N S Tnts are altered or replaced
mpone
- when co
§§ 259-260
Energy performance framework
+ §§ 261-266
&
Requirements for airtightness § 263
&
Requirements for design § 264
&
transmission loss Extensions
General minimum requirements § 257
for the building envelope + Annex 2, table 1
Requirements § in BR
&
General minimum requirements
for windows, glazed external walls, § 258 Energy performance framework §§ 259-260
skylight domes and glazed roofs as for new buildings + §§ 261-266
&
Requirements for design § 264
transmission loss
& § 257
General minimum requirements
Change of use &
for the building envelope + Annex 2, table 1
General minimum requirements
Requirements § in BR for windows, glazed external walls, § 258
skylight domes and glazed roofs
Energy performance framework §§ 259-260
as for new buildings + §§ 261-266 OR (e.g. max. 22 % windows and doors)
&
Requirements for design § 264 Minimum requirements for the § 257
transmission loss building envelope for extensions + Annex 2, table 2
& &
General minimum requirements § 257
General minimum requirements
for the building envelope + Annex 2, table 1
& for windows, glazed external walls, § 258
General minimum requirements skylight domes and glazed roofs
for windows, glazed external walls, § 258
skylight domes and glazed roofs OR (e.g. more than 22 % windows and doors)
OR Heat loss framework corresponding
to the U values and linear losses § 272
Minimum requirements for the § 268 &
building envelope for change of use + Annex 2, table 2 General minimum requirements § 257
& for the building envelope + Annex 2, table 1
General minimum requirements &
for windows, glazed external walls, § 258 General minimum requirements
skylight domes and glazed roofs for windows, glazed external walls, § 258
skylight domes and glazed roofs
Figure 3
4
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
As such, the energy requirements of the Building Likewise, there are also requirements in relation to
Regulations do not only apply to new buildings, change ventilation in existing buildings in the case of change
of use and extensions but also existing buildings when of use, alterations and other changes. In the case of
making alterations and other changes (including smaller renovation jobs, for example replacement of
replacements) and when the alterations affect the windows or doors, the ventilation conditions at the time
energy consumption in the building. of construction must be maintained. This is specified by
BR18’s instructional text about ventilation, item 1.1.
5
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
The reason for the Building Regulations having a higher energy performance framework for buildings that are not dwellings Figure 4
is that the energy demand for lighting in these buildings – for example offices, schools and institutions – is included when
calculating the energy demand.
6
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
Figure 5
7
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
General minimum requirements for the building As such, the purpose of the values in relation to new
envelope buildings is primarily to ensure that all building parts
The individual building elements should be insulated – e.g. also small areas – are constructed with a level
such that the heat losses through them do not exceed of insulation that does not result in condensation and
the values in figure 6 below. moisture issues.
Typically, the U values will have to be considerably The stated maximum U values apply to the entire
lower than the requirements for the general building part. Any cold bridges in the building part
requirements for the building envelope in order to must therefore be included. DS 418, Calculation of
comply with the energy performance framework and heat loss from buildings, details typical cold bridges
the requirements for the design transmission loss. and their contribution to the heat loss.
Approximate
New buildings (and possibly extensions). U value
W/m2 K insulation thicknesses
Annex 2: Tables for Chapter 11, Table 1
mm
External walls and basement walls in contact with the soil 0.30 150
Suspended upper floors and walls against freezer rooms 0.15 275
Suspended upper floors and walls against cold stores 0.25 150
Ψ-value Figure 7
Requirements for linear loss for joints between building elements
W/m K
Joints between roof construction and roof lights or skylight domes 0.20
Figure 6
8
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
Figure 8
9
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
&
Requirements for design § 264
transmission loss
& Energy Requirements of BR18
General minimum requirements § 257
for the building envelope + Annex 2, table 1
&
General minimum requirements
for windows, glazed external walls, § 258
skylight domes and glazed roofs &
External walls and basement walls in contact with the soil 0.15 300
Ceiling and roof structures, including jamb walls, flat roofs and 0.12 300
sloping walls directly adjoining the roof
Doors/gates 1.80 Figure 10
Hatches to the outside or to rooms where there is a 5° C
temperature difference or more (does not apply to ventilation 1.40
openings of less than 500 cm2)
Skylight domes Ændret anvendelse og tilbygning. Kap. 7.3.2 1.40
Ψ value
Requirements for linear loss for joints between building elements W/m K
Foundations 0.12
Joints between external walls, windows, external doors,
0.03
glazed external walls, gates and hatches
Joints between roof construction and roof lights or skylight domes 0.10
Figure 9
10
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
S
S R E Q U IREMENT
New buildings A LW A Y O NS
Energy Requirements of BR18
A L L A T I
Requirements § in BR
FOR INST altered or
ts are
replaced
mponen
- when co
§§ 259-260
Energy performance framework
+ §§ 261-266
&
& Extensions
Requirements for airtightness
Requirements for design
§ 263
§ 264
&
transmission loss Extensions
General minimum requirements § 257
for the building envelope + Annex 2, table 1
Requirements § in BR
& Extensions:
General minimum requirements
When you erect
for windows, more
glazed square
external metres attached§to
walls, 258 Energy performance framework §§ 259-260
skylight domes and glazed roofs as for new buildings + §§ 261-266
an existing building. E.g. a new wing, new top &
Requirements for design
storey or a new attic that provides an extra area. transmission loss
§ 264
& § 257
General minimum requirements
Change
The energy requirements for of use
extensions can be satisfied &
for the building envelope + Annex 2, table 1
by three different methods, as shown in the figure to General minimum requirements
Requirements § in BR for windows, glazed external walls, § 258
the right. skylight domes and glazed roofs
Energy performance framework §§ 259-260
Theasfirst twobuildings
for new methods are similar to cases of + §§change
261-266 OR (e.g. max. 22 % windows and doors)
&
of use and are specified
Requirements for design on the previous page. When § 264 Minimum requirements for the § 257
transmission
calculating theloss
energy performance framework, the building envelope for extensions + Annex 2, table 2
& &
area in m2 minimum
General for the entire building should be used.§The
requirements 257
General minimum requirements
for
energy the building envelope + Annex 2,
performance framework is, however, rarely usedtable 1
& for windows, glazed external walls, § 258
for General
extensions.
minimum requirements skylight domes and glazed roofs
for windows, glazed external walls, § 258
skylight domes and glazed roofs
The third method is to employ a heat loss framework. OR (e.g. more than 22 % windows and doors)
IfOR
this method is used, you should stay within a Heat loss framework corresponding
§ 272
to the U values and linear losses
framework that does not
Minimum requirements formake
the the extension’s heat § 268 &
lossbuilding
biggerenvelope
than if for
thechange
minimumof userequirements
+ Annex 2,for
table
the2 General minimum requirements § 257
&
building
for the building envelope + Annex 2, table 1
Generalenvelope
minimum described
requirementsin Table 2, Annex 2 to &
for windows,
Chapter glazed
11 (see external
figure walls,
9) were satisfied. § 258 General minimum requirements
skylight domes and glazed roofs for windows, glazed external walls, § 258
skylight domes and glazed roofs
Furthermore, the minimum requirements for the
building envelope for building elements
Conversions described in
and other
Table 1, Annex 2 to Chapter 11 should be adhered to
alterations
(see figure 6). To demonstrate that the Replacements
actual heat loss isof
below the
Requirements § in BR heat loss framework, twobuilding
separate parts
calculations are
What is a heat loss framework? required:
InMinimum
combination with adhering
requirements to theKapitel
for the building general minimum Requirements § in BR
envelope for conversions and other i BR • Calculation of the heat loss framework
requirements for the building envelope,
alterations concerning cost-effective
a heat loss
§ 279
• Minimum requirements
Calculation of thefor the
extension’s actual heat §loss
building envelope for conversions 279
framework calculation
energy improvements can be used
(a calculation + Annex 7.2
of to ensure that 3
2, table
and other alterations – regardless + Annex 2, table 3
cost-effectiveness
you must be available
meet the requirements if
for extensions added
requirements are not complied with) 7.6 stk. 1 to Theseoftwo calculations differ in two manners:
cost-effectiveness
an existing building and for new holiday homes in &
General minimum requirements § 258
OR
designated “summer house” areas as well as extensions First of
forall, the Uglazed
windows, valuesexternal
and linear losses of the actual
Energy performance
to these holiday homes. framework for calculation can vary
walls, skylight in relation
domes and glazedto the U values and
§§ 280-282
existing buildings – called linearroofs skylights
losses in and 2,
Table glass roofs2– to Chapter 11
Annex
regardless of cost-effectiveness
“renovation
The classes”
heat loss framework indicates the maximum heat (figure 9); some U values may be higher, some may
transmission loss allowed. The maximum framework be lower.
varies from construction to construction as it is
calculated based on information on square metres for Secondly, in the actual calculation, 50 % of the heat loss
the extension in question. that the extension covers of the existing building can be
deducted. This does not apply to dwellings in roofs and
The Building Regulations are as such adhered to when second storeys.
the actual heat loss is below the maximum allowed heat
loss framework – while also satisfying the requirements There is furthermore a requirement that window areas,
for general minimum requirements for the building etc. in the heat loss framework is set to 22 % of the
envelope indicated in Table 1, Annex 2 to Chapter 11 of heated storey area in the extension. In the actual
BR18 (see figure 6). building, there may be a larger area of windows, etc. as
long as you stay within the heat loss framework overall.
11
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
Example
The window area is one large window Length of joint between external wall and window for sides and top:
section of 6 metres from floor to ceiling 2 x 7.9/6 = 8.6 m
Figure 11
* Requirements for U values and line loss are given in Table 2 of Annex 2 to Chapter 11
of BR18. For the window part, U value is found in Section 273.
Figure 12
Conclusion
In the example, the result of calculating the heat loss of the actual building is 778 W. This is lower than the 787 W,
which is the result of the heat loss calculation in the example. As such, the example building is within the heat loss
framework and adheres to BR18.
12
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Requirements for design § 264
transmission loss
& Energy Requirements§of257
General minimum requirements BR18
External walls and basement walls in contact with the soil 0.18 200 (heavy) / 250 (light)
Ceiling and roof structures, including jamb walls, flat roofs and 0.12 300
sloping walls directly adjoining the roof
Ψ value
Requirements for linear loss for joints between building elements
W/m K
Foundations 0.12
Figure 13
13
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
What is cost-effectiveness?
Cost-effectiveness indicates how rewarding an energy- Lifetimes that can be used to calculate Years
saving measure is. Or in other words: Does the building cost-effectiveness
owner save more money in the long term than was
used to invest in the measure? Retro-fitted insulation to building elements 40
Cost-effectiveness is calculated like so: Windows with secondary windows and coupled
30
(cf. § 275 in BR18) frames
Heating systems, radiators and underfloor
Lifetime in years x annual savings in DKK heating and ventilation ducts and fittings 30
≥ 1.33
Extra investment including insulation
Heat appliances, etc., for example boilers, heat
If the cost-effectiveness is greater than or equal to 20
pumps, solar heating systems, ventilation units
1.33, the investment is considered cost-effective for
the building owner. This corresponds to the measure Lighting fittings 15
being repaid within ¾ of the expected lifetime.
Automation for heating and climatic control
15
The investment sum used in the calculation should only equipment
include the price of extra labour and materials for the
actual energy improvement – e.g. the insulation and Joint sealing works 10
any labour resulting thereof. It is often the case that Figure 15
retrofitting of insulation, for example, is more cost-
effective when you are already doing other renovation
work. Useful guide for assessing cost-effectiveness
A guide from the Danish Transport, Construction
When determining the lifetime, you can use figure
and Housing Authority about constructions that
15, which also appears in BR18’s guide to energy
are often cost-effective demonstrates a range of
consumption (Chapter 11), Cost-effective energy
the typical cost-effective retrofitting measures
savings.
during conversions and other alterations.
If an investment is cost-effective, you must adhere to
You can find it at www.bygningsreglementet.dk
the minimum requirements for the building envelope
(Danish) under Chapter 11, Guides (Vejledninger).
and linear loss that are specified in Table 3, Annex 2 to
Chapter 11 (see figure 13).
14
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
Energy performance frameworks for existing buildings Note, however, that when completely replacing
During larger building renovations, as an alternative to a building element – e.g. an entire roof structure
satisfying the U values and linear losses of Table 3, including new trusses, etc., or an installation – the
Annex 2 to Chapter 11, you can choose to use the requirements of figure 13 must always be met.
energy performance frameworks for existing buildings –
also called renovation classes. To fulfil the renovation classes, an energy performance
framework must be satisfied, and the energy demand
This new method of satisfying the energy requirements must be reduced by at least 30 kWh/m² per year.
during larger conversions and other alterations is Furthermore, there must be a percentage of renewable
voluntary and has been introduced to allow developers energy in the total energy supply to the building. For
greater flexibility. Renovation Class 1, a number of requirements for a
satisfactory indoor climate must also be met.
This means that instead of having requirements for
achieving heat savings by re-insulating per building
element and with accompanying cost-effectiveness Practical savings calculator
calculations, the energy performance framework gives
In order to calculate the expected savings for
the freedom to carry out other energy saving measures
single-family houses, terraced houses and tower
that in total bring the building’s energy demand down
blocks, you can use the savings calculator at
to a future-proof level.
www.ByggeriogEnergi.dk (Danish)
1,650
Renovation class 1 71.3 + kWh/m² per year
heated floor area
3,200
Renovation class 2 135 + kWh/m² per year
heated floor area
Figure 16
15
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
OR Heat loss framework corresponding
to the U values and linear losses § 272
Minimum requirements for the § 268 &
building envelope for change of use + Annex 2, table 2 General minimum requirements § 257
Energy Requirements of BR18
& for the building envelope + Annex 2, table 1
General minimum requirements &
for windows, glazed external walls, § 258 General minimum requirements
skylight domes and glazed roofs for windows, glazed external walls, § 258
skylight domes and glazed roofs
Replacement of
building
alterations elements and installations
Conversions and other
Replacements of
Requirements § in BR building parts
When being replaced, the building element or requirements for windows, doors etc. specified in § 258
installation should in all cases be replaced by a more (figure 8).
energy efficient component. As such, when replacing
a building element or installation, cost-effectiveness New installations should satisfy the requirements in
is not a factor – but it is generally most cost-effective BR18’s chapter 19 (read more on page 18). This chapter
to get a more modern central heating system or better refers to two standards: DS 469, Heating and cooling
insulated windows when installations or building systems in buildings and DS 452, Thermal insulation of
elements are being replaced anyway. technical installations.
The new building elements should meet the minimum Remember that the ventilation conditions cannot be
requirements for the building envelope specified in impaired when replacing for example windows or
BR18’s Table 3, Annex 2 to Chapter 11 (figure 13) and doors. In many cases, this can be resolved via valves in
external walls.
16
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
Holiday homes
New holiday homes in designated “summer house”
Minimum requirements for the building
areas are not covered by the same regulations as envelope for holiday homes, camping Approximate
U value insulation
other new buildings. cottages and similar holiday dwelling. W/m2 K thicknesses
Annex 2: Tables for Chapter 11 - mm
Here, there are no requirements for the energy Energy consumption, Table 4
performance framework – only for the U values and
External walls and basement walls in 0.25 150
linear loss in figure 17. contact with the soil
This is, however, under the provision that the total Suspended upper floors and partition 0.40 75
walls to adjoining rooms/spaces
area of windows and outer doors, including roof lights
that are unheated
and skylight domes, glazed outer walls, glazed roofs
Ground slabs, basement floors in
and hatches leading outside, make up no more than 0.15 200
contact with the soil and suspended
30 % of the heated floor area. upper floors above open air or a
ventilated crawl space
There is in-built flexibility that allows you to deviate
Ceiling and roof structures, including 0.15 250
from U values and linear loss if you can substantiate jamb walls, flat roofs and sloping
that the design transmission loss does not become walls directly adjoining the roof
bigger than if the values of figure 17 had been Windows, external doors, roof lights, Figure 18
adhered to. glazed external walls, glazed roofs 1.80
and skylight domes facing the outside
If, for example, you want more window area, you or facing unheated rooms/spaces
should be able to satisfy a heat loss framework. See
Requirements for linear loss for joints Ψ value
pages 11 and 12 on heat loss framework. between building elements W/m K
17
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
18
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
Energy Requirements of BR18
www.ByggeriOgEnergi.dk
The Building Regulations’ Annex 2: Tables for Experience sheets with buildable solutions:
Chapter 11 on energy consumption: www.Byg-erfa.dk (Danish)
http://bygningsreglementet.dk/Bilag/B2/Bilag_2
(Danish) Danish Transport, Construction and Housing
Authority’s guide on functional testings:
The Building Regulations’ instructional text on the http://bygningsreglementet.dk/Tekniske-bestem-
building envelope and installations for heating and melser/22/Vejledninger/Generel_vejledning/Kap-
cooling systems: 1_9 (Danish)
http://bygningsreglementet.dk/Tekniske-bestem-
melser/19/Vejledninger/Termisk-indeklima (Danish) Guides on functional testings published by Danish
Knowledge Centre for Energy Savings in Buildings:
http://byggeriogenergi.dk/
soeg/?q=funktionsafprøvning (Danish)
19
Danish Knowledge Centre for Energy Savings in Buildings generates knowledge about concrete and practical options for reducing the energy consumption in buildings.
About the Danish Knowledge Centre for Energy Savings in Buildings
The Danish Knowledge Centre for Energy Savings in Buildings gathers and communicates
knowledge about concrete and practical possibilities for reducing the energy consumption
of buildings. This is achieved by the Knowledge Centre having a hand in the parties of the
construction sector attaining more qualifications and new tools for implementing energy-saving
measures in buildings.
The Knowledge Centre as such assists in the total energy savings effort in Denmark.
The Danish Knowledge Centre for Energy Savings in Buildings was established as part of the
Danish energy policy agreement from 2008 and carried on in the agreement from 2012 and 2015.
Our logo – the house in bright colours – is inspired by thermographic imaging, which is an
excellent tool in mapping the energy loss of buildings.