ETABS Concrete Frame Design


Eurocode 2-2004 Column Section Design

Column Element Details Type: DC Low

Level Element Unique Name Section ID Combo ID Station Loc Length (mm) SOM LLRF

B3 C22 A/5-1 4C1-1200x1200 1.35Gk+1.5Qk 0 3950 Nominal Curvature 1

Section Properties

b (mm) h (mm) dc (mm) Cover (Torsion) (mm)

1200 1200 111 75

Material Properties

E c (MPa) f ck (MPa) Lt.Wt Factor (Unitless) E s (MPa) f yk (MPa) f ywk (MPa)

39000 60 1 200000 500 500


design mt
Design Code Parameters
eccentric mt;M(emin)=P x emin
MEd2 =
ɣC ɣS α CC α CT α LCC
M(endmax)+Mi+ emin =αH/30 > 20mm
LCT

1.5 1.15 0.85 0.85 0.85 0.85


M2 > M(emin)
Axial Force and Biaxial Moment Design For N Ed , M Ed2 , M Ed3
where
Design N Design M Ed2 Design M Ed3 Minimum M2 Minimum M3 Rebar Area Rebar %
1.Mi = Pxei kN
Ed
kN-m kN-m kN-m kN-m mm² %
ei is calculated by 11448.2953 -584.3152 457.9318 457.9318 457.9318 2880 0.2
(0.005*Lo/2)
Axial Force and Biaxial Moment Factors

2. M2 = Pxe2 M 0Ed Moment M add Moment Minimum Ecc β Factor Length


e2 is calculated by kN-m kN-m mm Unitless mm

either Nominal Major Bend(M3) 8.4045 99.048 0 1 3950

curvature or Minor Bend(M2) -195.9703 99.048 0 1 3950

Norminal stiffness
Axial Compression Ratio
method
Conc Capacity (α CC *A*f cd ) Compressive Ratio Comp Ratio Seismic Ratio
kN N Ed /(α cc *A*f cd ) Limit Load? OKay?

48960 0.234 0.75 No Yes

column near mid-ht additional seconder


moment order moment;
0.6M2+0.4M1 >0.4M2
M2 = Pxe2

20201125_UGSS and OSC_Entry D


e2 is calculated by
Page 1 of 2
Update-1_for column design check.EDB either Nominal 02/12/2020
curvature or Norminal
stiffness method
ETABS 18.1.1 License #*1E9GH4CA3NCXEA6

Shear Design for V Ed2 , V Ed3

Shear V Ed Shear V Rdc Shear V Rds tan(θ) Rebar A sw /s


kN kN kN Unitless mm²/m

Major, V Ed2 1.0106 1937.8579 0 0.4 0

Minor, V Ed3 111.5475 1937.8579 0 0.4 0

Rules: Joint shear stress ratio is only determined for a station

a) if the station has a beam-column joint (top of the column),

b) if the frame is a DCHe or DCM moment resisting frame,

c) if the column above is a concrete column when it exists,

d) if all the beams framing into the column are concrete beams

e) if the connecting member design results are available, and

f) if the load combo involves seismic load.

M(smaller)+M2

M(larger) + Mi+M2

*minimum eccentric moment areneeded to consider in


one direction only.
*Mi only added at one end (top or bot )

20201125_UGSS and OSC_Entry D


Page 2 of 2 02/12/2020
Update-1_for column design check.EDB