SERVICE : MOV VALVE

DOCUMENT TITLE : Instruction Manuals for Installation and Maintenance

PROJECT:
SHWE LIN PAN (SLP) DEPOT PROJECT
LOCATION: YANGON, MYANMAR
OWNER:

DENKO PETROCHEMICAL MANAGEMENT CO.,LTD

CONTRACTOR:

TVC JOB No. VF-006

TVC PO No : VF006-2000-0000-050

Item No. : MOV VALVE

Doc. No.: MOV017-92-001 Rev : 0

0 05-April-22 Final N.H.N N.G.P T.Q.C D.T.N


0 15-Jan-22 For Review N.H.N N.G.P T.Q.C D.T.N
REV. DATE DESCRIPTION MADE BY CHECKED APPROVED AUTH' D

VENDOR NAME : NK ENGINEERING CO., LTD


IQ Range
Instructions for Safe Use, Installation,
Basic Setup and Maintenance

This manual contains important safety


information. Please ensure it is thoroughly
read and understood before installing,
operating or maintaining the equipment.

PUB002-039-00
Date of issue 01/21
Table of Contents

1. Introduction______________________________3 6. Mounting the Actuator_________________ 14 9. Maintenance, Monitoring


1.1 Identifying Actuator Parts . . . . . . . . . . . . . . . . . . 3 6.1 Rising Stem Valves Top Mounted. . . . . . . . . . . . 15 and Troubleshooting____________________ 28
1.2 Rotork Setting Tool . . . . . . . . . . . . . . . . . . . . . . . 4 6.2 Valve with Gearbox – Side Mounting. . . . . . . . . 15
10. Decommissioning and Environmental
1.3 Introduction to this manual. . . . . . . . . . . . . . . . . 5 6.3 Non-Rising Stem Valves – Top Mounting. . . . . . 15 Considerations_________________________ 30
6.4 Handwheel Sealing. . . . . . . . . . . . . . . . . . . . . . . 16
2. Health and Safety________________________5 11. Weights and Measures__________________ 31
6.5 IQM Modulating Actuators . . . . . . . . . . . . . . . . 16
2.1 ATEX/IEC Ex Certified Actuators . . . . . . . . . . . . . 7
6.6 IQL & IQML Linear Drive Unit. . . . . . . . . . . . . . . 16
2.2 Indian Ex Certified Actuators. . . . . . . . . . . . . . . . 7 12. IQ Approvals___________________________ 32
6.7 IQL & IQML Adjusting Linear Stroke. . . . . . . . . . 17
3. Storage__________________________________7 6.8 IQL & IQML Lubrication. . . . . . . . . . . . . . . . . . . 17 13. Approved Fuses________________________ 34

4. Operating your IQ Actuator_______________8 7. Cable Connections______________________ 17 14. Vibration, Shock and Noise______________ 34
4.1 Operating by Hand. . . . . . . . . . . . . . . . . . . . . . . . 8 7.1 Terminal Block Layout . . . . . . . . . . . . . . . . . . . . 17
7.2 Earth/Ground Connections. . . . . . . . . . . . . . . . . 18
15. Conditions of Safe Use__________________ 34
4.2 Operating Electrically. . . . . . . . . . . . . . . . . . . . . . 8
7.3 Removing Terminal Cover. . . . . . . . . . . . . . . . . . 18 15.1 Thread details for ATEX and IECEx
4.3 Display – Local Indication. . . . . . . . . . . . . . . . . . . 9 Approved actuators. . . . . . . . . . . . . . . . . . . . . . 34
4.4 Display – Home screen selection . . . . . . . . . . . . 10 7.4 Cable Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
15.2 Maximum constructional flamepath gaps
4.5 Display Status Indication – Travel. . . . . . . . . . . . . 11 7.5 Connecting to Terminals . . . . . . . . . . . . . . . . . . 20 for ATEX and IECEx Approved actuators.. . . . . . 35
4.6 Display Status Indication – Control. . . . . . . . . . . . 11 7.6 Replacing Terminal Cover. . . . . . . . . . . . . . . . . . 21
4.7 Display Alarm Indication. . . . . . . . . . . . . . . . . . . . 11
8. Commissioning - Basic Settings__________ 21
4.8 Battery Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8.1 Connecting to the Actuator. . . . . . . . . . . . . . . . 22
5. Preparing the Drive Bush________________ 12 8.2 Security – Password. . . . . . . . . . . . . . . . . . . . . . 23
5.1 IQ base all sizes types A and Z3. . . . . . . . . . . . . 12 8.3 Basic Settings Menu. . . . . . . . . . . . . . . . . . . . . . 24
5.2 Non-Thrust Base Type B. . . . . . . . . . . . . . . . . . . 13 8.4 Basic Settings – Limits . . . . . . . . . . . . . . . . . . . . 25
8.5 Close Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.6 Open Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.7 Torque Switch Bypass. . . . . . . . . . . . . . . . . . . . . 27

2 
1. Introduction
1.1 Identifying Actuator Parts
Battery sealing plug
Metal (8 mm Allen key required)
Plastic (10 mm Allen key required) Side hand wheel
as appropriate.

Hand / Auto lever


Hand wheel Name plate
Oil plug Display window

Control Cover

Oil plug

Terminal Cover
Conduit entries Local / Remote / Stop
Motor Oil plug
selector
Base

Open / Close selector

IQ manual – Section: Introduction 3


1.2 Rotork Setting Tool Specification Instructions for Safe Selection, 3. The BTST v1.1 is not intended to
Enclosure: IP54 Installation, Use, Maintenance be repaired by the user. Repair of the
The Rotork Bluetooth® Setting Tool Pro and Repair equipment is only permitted by the
v1.1 (BTST) combines the legacy IR and The BTST has been built in accordance manufacturer or an approved agent
IrDA communication protocols with the with the following standards: The following instructions relevant to
in accordance with applicable code of
latest Bluetooth® wireless technology. IR / safe use in a hazardous area apply to
practice.
IrDA support for older Rotork products is I II G equipment covered by CSA certificate
retained (for use as an IR communication Ex ia IIC T4 Ga numbers 80005457, IECEx CML 20.0054 4. No user adjustment of the BTST v1.1 is
tool, please refer to publications CML 19ATEX2194 and CML 19ATEX2194. required.
PUB002-003 and PUB002-004). 2776 IECEx CML 20.0054 1. The BTST v1.1 may be used in Division 5. The BTST must be inspected every
The BTST is able to connect to Rotork 1, 2 and Zones 0, 1, 2 hazardous areas three months, in a safe (non-hazardous),
Ex ia that require IIC, IIB or IIA protection and dry area by suitably trained personnel,
Bluetooth wireless enabled actuators and
related software to setup and complete
®
Class 1, Div 1, temperature class T1, T2, T3 or T4. to ensure it has been maintained in
C US
missions. Missions are configurable Group A, B, C, D T4 accordance with the applicable code of
CSA19CA80005457 2. The following checks must be
programs of instructions that are to be practice.
conducted on the BTST v1.1 prior to
performed by the BTST on an actuator taking it into a hazardous area: 6. Subject to the applicable code of
Ex ia IIC T4 Ga
and include (but are not limited to) practice, the batteries may be replaced
downloading configuration and data GB 3836.1-2010, a. The BTST v1.1 function must be
GB 3836.4-2010 in a non-hazardous area with one fo the
logger files as well as uploading specific checked by ensuring a red or green LED
following types of Alkaline-Maganese or
configurations to the actuator. Different GYJ20.1173X illuminates under the ‘Enter’ key when
Zinc-Maganese ‘AAA’ size batteries:
missions can be programmed into the any button is pressed. If an LED does
BTST via Insight 2. Ambient Temperature Range: not illuminate, the BTST v1.1 requires - Duracell Procell type MN2400
Tamb = -30 to +50 °C inspection and battery replacement.
- Energizer Ultimate
b. The BTST v1.1 does not require
Operating Range: - Energizer HighTech
assembly or dismantling, however
Infra Red 0.75m suitable precautions must be taken if - Duracell Ultra
the BTST v1.1 may come into contact
Bluetooth 10m with damaging substances (e.g. solvents - Varta Industrial
that degrade polymeric materials). - Varta High Energy
Enclosure Materials: Regular inspections must be performed
Polycarbonate resin containing 10% to confirm enclosure damage is not - Panasonic Pro Power
Carbon Fibre, Silicone Rubber apparent. Do not use the equipment if - Eveready Super
damage is present.
- Duracell Chinese
Rotork Bluetooth® Setting Tool Pro v1.1

4 IQ manual – Section: Introduction


7. The BTST v1.1 contains no other 1.3 Introduction to this manual 2. Health and Safety and use of these actuators should be
user replaceable parts and it cannot be carried out in accordance with the
repaired by the user. If the BTST v1.1 is This manual provides instruction on: National Legislation and Statutory
This manual is produced to enable a
faulty or needs repairing, it must not be • Manual and electrical (local and competent user to install, operate, Provisions relating to the safe use of
used. remote) operation. adjust and inspect Rotork IQ range valve this equipment, applicable to the site of
• Preparation and installation of the actuators. Only persons competent by installation.
actuator onto the valve. virtue of their training or experience For the UK: Electricity at Work
should install, maintain and repair `Regulations 1989 and the guidance
• Basic commissioning. Rotork actuators. given in the applicable edition of the
• Maintenance. Under no circumstances should “IEE Wiring Regulations” should be
Refer to Publication PUB002-047 replacement parts be used in Rotork applied. Also the user should be fully
for repair, overhaul and spare part actuators, other than those supplied or aware of his duties under the Health and
instructions. specified by Rotork. Safety Act 1974. For the USA: NFPA70,
National Electrical Code® is applicable.
Refer to Publication PUB002-040 Work undertaken must be carried out in
for secondary function accordance with the instructions in this The mechanical installation should be
configuration instructions. and any other relevant manuals. carried out as outlined in this manual
and also in accordance with relevant
Using the supplied setting tool to If the actuator is used in a manner not standards such as British Standard
access the actuator set up procedures, specified in this manual and any other Codes of Practice. If the actuator has
non-intrusive setting of torque levels, Rotork manual, the protection provided nameplates indicating that it is suitable
position limits and all other control by the actuator may be impaired. for installation in hazardous areas then
and indication functions can be made The user and those persons working the actuator may be installed in Zone
safely, quickly and conveniently, even on this equipment should be familiar 1, Zone 21, Zone 2 and Zone 22 (or Div
in hazardous locations. The IQ allows with their responsibilities under any 1 or Div 2, class I or Class II) classified
commissioning and adjustment to be statutory provisions relating to the hazardous area locations only. It should
carried out with the main power supply Health and Safety of their workplace. not be installed in hazardous area
to the actuator switched on or off. Due consideration of additional locations with an ignition temperature
Visit our web site at www.rotork.com hazards should be taken when using less than 135 °C, unless suitability for
for more information on the IQ, the IQ range of actuators with other lower ignition temperatures has been
Insight 2 and other Rotork actuator equipment. Should further information indicated on the actuator nameplate.
ranges. and guidance relating to the safe use It should only be installed in hazardous
of the Rotork IQ range of actuators be area locations compatible with the
required, it will be provided on request. gas and dust groups stated on the
The electrical installation, maintenance nameplate.

IQ manual – Section: Health and Safety 5


The electrical installation, maintenance WARNING: Service Altitude WARNING: Thermostat Bypass WARNING: Operating by Hand
and the use of the actuator should be
carried out in accordance with the code Actuator installation is permitted up to If the actuator is configured to With respect to handwheel operation
of practice relevant for that particular 5000 m with the following restrictions: bypass the motor thermostat then of Rotork electric actuators, refer to
Hazardous Area certification. the hazardous area certification will section 4.1.
– Actuator power supply is not be invalidated. Additional electrical
No inspection or repair should be above 480 V hazards may occur when using this WARNING: Actuator may start
undertaken unless it conforms to the configuration. The user should ensure and operate when remote is
specific hazardous area certification – Input and output connections must selected. This will be dependent on
use the 24 VDC nominal supply that any necessary additional safety
requirements. Under no circumstances measures are considered. remote control signal status and
should any modification or alteration – Mains system must be TT, IT, TN-C-S actuator configuration.
be carried out on the actuator as this and 3-phase / wire systems WARNING: Enclosure Materials
could invalidate the actuators hazardous WARNING: Unit Weight
IQ Range of actuators are
area approval certification. Access to live Installation without restrictions must manufactured from aluminium alloy The actuator weight is shown on the
electrical conductors is forbidden in the be less than 2000 m as defined by with stainless steel fasteners and the nameplate. Care must be taken to
hazardous area unless this is done under IEC61010-1 (Safety requirements for thrust bases are manufactured in transport, move or lift the actuator
a special permit to work, otherwise electrical equipment for measurement, cast iron. safely. Lifting information is available in
all power should be isolated and the control and laboratory use). section 6.
actuator moved to a non-hazardous area The cover window is toughened
for repair or attention. WARNING: Motor Temperature glass which is retained with a 2-part
Under normal operation the temperature silicone cement and the battery plug
of actuator’s motor cover surfaces can will be either stainless steel or PPS
exceed 60 °C above ambient. (Poly-Phenolyne Sulfide).
The user must ensure that the
WARNING: Surface Temperature operating environment and any
The installer/user must ensure that the materials surrounding the actuator
actuator surface temperature rating cannot lead to a reduction in the safe
is not influenced by external heating/ use of, or the protection afforded
cooling effect (e.g. valve/pipeline by, the actuator. Where appropriate
process temperatures). the user must ensure the actuator is
suitably protected against its operating
environment.

6 IQ manual – Section: Health and Safety


2.1 ATEX/IEC Ex Certified Actuators Actuator Size: IQ/IQM/IQS 20 & 35 2.2 Indian Ex Certified Actuators 3. Storage
or IQ/IQM 25 or IQ 19
Special Conditions Special Conditions
Ex d IIB T4 Gb (-30°C to +70°C) If your actuator cannot be installed
This actuator must only be located in The manufacturer has maintained immediately, store it in a dry place until
areas where the risk of impact to the Ex d IIB T4 Gb (-40°C to +70°C) more stringent flamepath gaps than you are ready to connect incoming
viewing window is low. Ex d IIB T4 Gb (-50°C to +40°C) required by the standard. User must cables.
This equipment includes some Certificate No: CML 19ATEX1190X or refer to manufacturer before carrying
out any repairs or refurbishment to If the actuator has to be installed but
exterior non-metallic parts including IECEx CML 20.0050X
the equipment. The gap specified in cannot be cabled it is recommended
the protective coating. To avoid the
Actuator Size: IQ/IQM 20 & 25 or certificate drawings must never be that the plastic transit cable entry plugs
possibility of static build up, cleaning
IQS 20 or IQ 19 exceeded. are replaced with metal plugs which
must only be carried out with a damp
are sealed with PTFE tape.
cloth. Explosionproof, Class l, Div 1, Groups The fastening screws for cover with
B, C & D - CSAus approved spigot joint shall be stainless steel The Rotork double-sealed construction
WARNING: External Enclosure socket head cap screws of property
Model: IQ3FM - Explosionproof, Class I, will preserve internal electrical
Fasteners class A4-80 and yield stress 240 MPa.
Div 1, Groups B, C, D - FM approved components perfectly if left
Enclosure fasteners are stainless steel User should follow instructions given undisturbed.
grade A4 80 except for the following on the equipment nameplate for
sizes and when marked on the selection of cable and cable gland. It is not necessary to remove any
nameplate as shown. In these cases electrical compartment covers in order
the terminal cover fasteners are carbon End user should follow manufacturer's to commission the IQ actuator.
steel grade 12.9. If in doubt check the instructions for replacement of the
grade marked on the relevant fastener battery. Rotork cannot accept responsibility for
or contact Rotork. deterioration caused on-site once the
Bureau of Indian Standards (BIS) covers are removed.
For details of BIS certification please
visit www.bis.gov.in Every Rotork actuator has been fully
tested before leaving the factory to
give years of trouble free operation,
providing it is correctly commissioned,
installed and sealed.

IQ manual – Section: Storage 7


4. Operating your IQ Actuator To engage handwheel drive depress 4.2 Operating Electrically
the Hand/Auto lever into “Hand”
Check that power supply voltage
4.1 Operating by Hand position and turn the handwheel to
agrees with that on the actuator
engage the clutch. The lever can now
WARNING nameplate. Switch on power supply.
be released where it will return to its
It is not necessary to check phase
With respect to handwheel original position. The handwheel will
rotation.
operation of Rotork electric remain engaged until the actuator
actuators, under no circumstances is operated electrically when it will Do not operate the actuator
should any additional lever device automatically disengage and return to electrically without first checking,
such as a wheel-key or wrench motor drive. using the infra-red Setting Tool,
be applied to the handwheel in that at least the Basic Settings have
order to develop more force when If required for local lockout purposes been made (refer to Section 8).
closing or opening the valve as the Hand/Auto lever can be locked in
either position using a padlock with a Selecting Local/Stop/Remote
this may cause damage to the Fig. 4.2.1 IQ3 Local Controls
6.5 mm hasp. Operation
valve and/or actuator or may cause
the valve to become stuck in the The red selector enables either Local
Locking the lever in the "hand" Local Control
seated/ backseated position. or Remote control, lockable in each
position prevents electrical operation of
position using a padlock with a 6.5
Keep clear of the handwheel the actuator moving the valve.
mm hasp. With the red selector positioned at
when engaging hand operation.
When the selector is locked in the Local (anti-clockwise) the adjacent
Actuators driving valves via
Local or Remote positions the Stop black knob can be turned to select
extension shafts may be subject
facility is still available. The selector can Open or Close. For Stop, turn red knob
to retained shaft torsion which
also be locked in the Stop position to clockwise.
can cause the handwheel to rotate
when hand operation is engaged. prevent electrical operation by Local or
Remote control. Remote Control

Rotate the red selector to the Remote


position (clockwise), this allows remote
control signals to operate the actuator.
Local Stop can still be used by turning
the red knob anti-clockwise.

8 IQ manual – Section: Operating your IQ Actuator


4.3 Display – Local Indication 3. Infra-red LEDs 9. Percentage Open Icon
Used for older models of setting tool This icon will be displayed when an
10 and to initiate a data connection using integer open value is displayed e.g.
Bluetooth wireless technology. 57.3.
4. Dual position LEDs 10. Dot Matrix Display
Consisting of 2 x Yellow for mid A high resolution 168x132 pixel
2 position and 2 x bi-colour (Red / Green) display for displaying setup menus and
for end of travel indication. datalogger graphs.
5. Bluetooth indication LED When a positional display is active,
6
A dual intensity LED for indicating an the status and active alarms will be
4 8 4
active connection using Bluetooth displayed.
7 wireless technology. The LCD screen is made up of two
1 6. Alarm Icon layers; the main segment display and
9
the dot matrix display. The displays
This will be displayed for valve, control are dual stacked so that either display
5 3 and actuator alarms. Alarm indication can be enabled to show different
is supported by fault description in the information. This also allows a
text in the line above the main display. combination of both displays for added
7. Battery Alarm Icon flexibility.
This icon will be displayed when On power the LCD is backlit with a
a battery is detected as low or white light to enable the best viewing
Fig. 4.3.1 Segment Display
discharged. "Battery low" or contrast in all lighting conditions. For
"Discharged" will also be displayed in additional positional indication, the
the text display above. LEDs at either side of the LCD are used
1. Position display 2. Analogue Scale for Closed (green), mid-travel (yellow)
This is the main segment display for Scale 0% to 100% is used when 8. Infra-Red Icon and Open (red) as standard. These LEDs
position and torque; position indication Analogue torque (% of rated) or This icon flashes during setting tool are fully configurable in the settings
to 1 decimal place. Positioning (% position / demand) communication activity. LEDs will also menu or on request at time of order.
homescreens are selected. Refer to flash when keys are pressed.
section 4.4.

IQ manual – Section: Operating your IQ Actuator 9


5 3

4.4 Display – Home screen selection Permanent Home Screen display. Once selected, the set display will be
Using the setting tool (refer to 8.1) the active, permanent home screen.
The actuator display can be set to show Refer to Figs 4.4.2 to 4.4.5.
any one of the following home screens: connect to the actuator.
• Position indication From the Settings menu, select
Indication, Local Display. From
• Position & Digital Torque indication the available settings, select Home
Screen. Enter the password if
• Position & Analogue Torque indication requested (refer to section 8.2), select
• Position & Control Demand indication Home screen and from the dropdown
list, select the required Home screen
The default home screen is Position. for permanent display:
Home screens indicate the live
conditions measured by the actuator
when mains power is applied. When
mains power is switched off the Fig. 4.4.2 Position Fig. 4.4.4 Torque (A) + Position
actuator battery powers the display
and it will show the position indication Y Y
display only.
The required home screens can be
set by the user either as a permanent
display or as a temporary display for
valve or actuator operational analysis.
Fig. 4.4.1 Home Screen Selection
Temporary Home Screen display.
Using the setting tool (refer to 8.1) Position - Default valve position display
or arrow keys, scroll through Torque (A) + Pos - Position with
the available home screens until analogue torque indication Fig. 4.4.3 Torque (D) + Position Fig. 4.4.5 Positioner
the required one is displayed. The
selected screen will remain displayed Torque (D) + Pos - Position with
for approximately 5 minutes after the digital torque indication
last setting tool command or until the Positioner - Position with digital and
actuator power is cycled. analogue position demand indication

10 IQ manual – Section: Operating your IQ Actuator


4.5 Display Status Indication – 4.6 Display Status Indication – 4.7 Display Alarm Indication 4.8 Battery Alarm
Travel Control
The IQ display provides alarm indication
The IQ display provides real-time status The bottom line of the text area is in the form of text and alarm icons.
indication. The top line of the text area reserved for control status indication There are 2 alarm icons:
is reserved for travel status indication. and is displayed for approximately 2
Fig 4.5.1 shows the travel status seconds after the control mode or
example of CLOSED LIMIT signal is applied. General Alarm:
Fig 4.6.1 shows the control status
example Remote Control. Battery Alarm:

The general alarm icon will be Fig. 4.8.1


supported with text in the bottom line
indicating the particular alarm, or if The actuator checks the battery level
more than one is present, each alarm at approximately 1 hour intervals. The
will be displayed in sequence. battery alarm icon is displayed when
the actuator detects its battery as
Fig 4.7.1 shows the status example: being low and the display will indicate
Fig. 4.5.1 TORQUE TRIP CLOSED BATTERY LOW. If the battery is flat
or missing the display will indicate
Fig. 4.6.1 BATTERY DISCHARGED.
When a low or discharged battery
alarm is displayed the battery should
be replaced immediately. It is essential
that the correct battery type is fitted to
maintain actuator certification. Refer to
section 9 for details.
After replacing a battery the alarm
icon will continue to be displayed
Fig. 4.7.1 until the next check and may take
up to 1 hour. Cycling the power
will force a battery check and clear
the alarm.

IQ manual – Section: Operating your IQ Actuator 11


5. Preparing the Drive Bush Disassembly of bearing assembly
all sizes
5.1 IQ base all sizes types A and Z3 Locate and remove the snap ring (5) Thrust Base
using a suitable tool. Remove the Thrust Base Housing
Turn actuator onto its side, remove the split collar (4) See Fig. 5.1.1. Slide the
Housing
cap-headed screws holding retaining bearing (3) off the drive bush (2).
plate (1) onto the thrust base and pull
out the drive bush (2) complete with its Note Additional spacer (6) and O-rings
5. Snap Ring
bearing assembly (3). Size IQ10 to 35 to remove on sizes IQ20 to 95.
5. Snap Ring
have 2 screws, size IQ40 to 95—F25 Keep the bearings and drive bush 4. Split Collar
bases have 8 screws, and F30 have 10 locating components in a safe clean
screws. Before machining the drive bush place. The split collar (4) must be kept 4. Split Collar 6. Bearing Spacer
the thrust bearing must be removed. Ring
as a matched pair.
IQ10 to 18 actuators have a sealed Machine the drive bush (2) to suit 3. Thrust Bearing
thrust bearing located on the drive 3. Sealed Thrust
the valve stem, allowing a generous Bearing
bush and retained by the split collar (4) clearance on the screw thread for rising
and snap ring (5). steam threads. O-rings
IQ20 to 95 have a thrust race bearing 2. Drive Bush
within a steel bearing housing located 2. Drive Bush
on the drive bush and retained by the
split collar (4) and snap ring (5). The
bearing is sealed within its housing by 1. Retaining Plate 1. Retaining Plate
O-rings located on the drive bush and
the bearing spacer ring (6).
WARNING: Failure to remove
the bearing assembly and O-rings Fig. 5.1.2 F10 base assembly Fig. 5.1.3 F14 & F16 base assembly
from the drive bush prior to
machining may result in damage
to the bearing.
Fig. 5.1.1

12 IQ manual – Section: Preparing the Drive Bush


Reassembly 5.2 Non-Thrust Base Type B Types B3 and B4 Removal
WARNING: Failure to fully clean All Sizes Using external circlip pliers, expand the
Thrust Base and grease the drive bush and circlip while pulling on the drive bush.
Housing O-rings before reassembly could Undo the hex head bolts securing the The drive bush will detach from the
result in damage. base plate to the gearcase and remove actuator centre column with the circlip
the base plate. retained in its grove. Refer to Fig. 5.2.2.
Remove all swarf from the drive bush The drive bush and its retaining clip can
(2) ensuring all O-rings are undamaged, now be seen. The plate will vary with Types B1 Removal
5. Snap Ring clean and greased (for typical greases the size of the actuator. See Fig. 5.2.1. The procedure for removal and refitting
4. Split Collar
refer to Section 11, weights and of the B1 drive bush is the same as
measures). for B3 and B4, however the circlip is
6. Bearing Spacer Slide the bearing assembly (3) onto the replaced with a custom spring circlip.
Ring drive bush (2) and ensure it is fitted The spring operates in the same
3. Thrust Bearing down to the drive bush shoulder. On manner as the B3/B4 circlip but is
size IQ20 to IQ95 refit bearing spacer expanded using long nose-pliers. Refer
ring (6) into bearing assembly ensuring to Fig. 5.2.3.
O-rings O-ring is fitted and greased. Grease
and refit matched pair split collar (4)
2. Drive Bush and snap ring (5).
Grease and refit the drive bush bearing
1. Retaining Plate
assembly into the thrust base housing Fig. 5.2.1
on the actuator, ensuring that the slots
in the drive bush are located into the
drive dogs of the hollow output shaft.
Refit the retaining plate (1) and secure
with cap headed screws. For IQ40 to
IQ95 tighten base retaining screws to
Fig. 5.1.4 F25 & F30 base assembly the following torque values: Fig. 5.2.3
F25 / FA25 Base — 8 off / M12 cap
head screws: 89 Nm / 65 lbs.ft
F30 / FA30 Base — 10 off / M16 cap
head screws: 218 Nm / 160 lbs.ft
Fig. 5.2.2

IQ manual – Section: Preparing the Drive Bush 13


6. Mounting the Actuator WARNING: IQ Cover Tubes.
Cover tubes not supplied by Rotork
Refer to Section 11 Weights and shall be designed to ensure that
Measures for actuator weight. they do not exceed BOTH mass
and moment parameters listed in
Ensure the valve is secure before fitting Section 11 Weights and Measures.
the actuator as the combination may
be top heavy and therefore unstable. WARNING: Do not lift the
If it is necessary to lift the actuator actuator and the valve combination
using mechanical lifting equipment via the actuator. Always lift the
certified slings should be attached as valve/actuator assembly via the
indicated in Fig. 6.2.1 for vertical shafts valve.
and Fig. 6.2.2 for horizontal shafts. Each assembly must be assessed on an
At all times trained and experienced individual basis for lifting.
personnel should ensure safe lifting
WARNING: If the actuator Fig. 6.2.1
particularly when mounting actuators.
orientation when installed is
WARNING: The actuator should inverted (base up), additional oil
be fully supported until full valve is required to ensure adequate
shaft engagement is achieved and lubrication. The user should top up
the actuator is secured onto the the oil by the quantity stated in the
valve flange. table under section 11 Weights and
A suitable mounting flange confirming Measures. Failure to do will cause
to ISO 5210 or USA Standard MSS premature wear.
SP101 must be fitted to the valve.
Actuator to valve fixing must confirm
to Material specification ISO Class 8.8,
yield strength 628 N/mm2.

Fig. 6.2.2

14 IQ manual – Section: Mounting the Actuator


6.1 Rising Stem Valves Top Mounted Continue to turn actuator until fixing Metric Torque 6.2 Valve with Gearbox – Side
holes align. Using bolts supplied fix Mounting
Fitting the Actuator and Base as a actuator to thrust base and tighten Flange Fixing Nm lbs.ft
combined unit, all sizes. down to required torque, see table A. F10 M10 51.6 38
Check that the mounting flange is at
Fit the machined drive bush into the right angles to the input shaft, and
Open valve by two turns and firmly F14 M16 219.8 162.1 that the drive bush fits the shaft and
thrust base as previously described, tighten down onto valve flange to the
lower the actuator onto the threaded F16 M20 430.5 317.5 key with adequate axial engagement.
required torque, see table B. Engage HAND, offer up actuator to
valve steam, engage HAND operation F25 M16 219.8 162.1
and wind the hand wheel in the open It may not be possible to install the the input shaft and turn handwheel
direction to engage the drive bush thrust base separately for IQ10 - IQ25 F30 M20 430.5 317.5 to align keyway and key. Tighten
onto the stem. Continue winding until actuators with fireproof coating. Imperial Torque
mounting bolts to the required torque
the actuator is firmly down onto the indicated in Table B.
Flange Fixing Nm lbs.ft
valve flange. Wind two further turns,
fit securing bolts and tighten fully to FA10 3
/8 42.3 31.2 6.3 Non-Rising Stem Valves – Top
the required torque indicated in FA14 5
/8 205.3 151.4 Mounting
Table B.
FA16 3
/4 363.6 268.1 Treat as for side mounting except that
Fitting Thrust Base to Valve Actuator FA25 5
/8 205.3 151.4 when thrust is taken in the actuator,
Fit the machined drive bush into the a thrust nut must be fitted above the
3
FA30 /4 363.6 268.1 drive bush and securely tightened.
thrust base as previously described.
Remove the thrust base from the Fig. 6.1.3 Table B
actuator, place it on the threaded
valve stem with the slotted end of Fig. 6.1.1
the drive bush uppermost and turn it
in the open direction to engage the
Torque (±10%)
thread. Continue turning until the base Size
is positioned onto the valve flange. Fit Nm lbs.ft
the securing bolts but do not tighten at M8 13.8 9.8
this stage. Lower the actuator onto the
thrust base and rotate the complete M12 45.9 33.8
actuator until the drive dogs on the M16 101 74
actuator output shaft engage into the
drive bush. Actuator flange should now Fig. 6.1.2 Table A
be flush with the base.

IQ manual – Section: Mounting the Actuator 15


6.4 Handwheel Sealing 6.5 IQM Modulating Actuators 6.6 IQL & IQML Linear Drive Unit
Ensure that the sealing cap and The IQM range of actuators are Consists of a lead screw assembly
O-ring is fitted securely to ensure that suitable for modulating control duty of arrangement attached to the base
moisture does not pass down the up to 1,200 starts per hour. of the actuator in order to provide a
centre column of the actuator. For linear output stroke between 8 mm
valves with rising spindles a cover tube IQM have a dynamic breaking facility (3/4 in) minimum and 110 mm (4 1/4 in)
may be fitted, this must also be sealed as standard. If mechanical overrun maximum.
with an O-ring and secured with cap of the actuator and valve prove to
screws. be excessive for accurate control, the The IQL/IQML actuator can be supplied
brake can be enabled. With dynamic with or without a yoke mounting
breaking enabled, motor heating adaptor. The adaptor consists of four
effects increase and therefore the pillars and a base flange to suit the
number of starts may require reducing valve.
to prevent motor thermostat tripping.
Commissioning of the IQM range is
identical to the standard IQ - refer to
Fig. 6.6.2 IQML without Yoke
Section 8.

Fig. 6.4.1

Fig. 6.4.2 Fig. 6.6.1 IQML with Yoke

16 IQ manual – Section: Mounting the Actuator


6.7 IQL & IQML Adjusting Linear 6.8 IQL & IQML Lubrication 7. Cable Connections
Stroke
The linear drive unit is lubricated from
7.1 Terminal Block Layout
With the actuator securely fitted to the factory with extreme pressure
the valve, but with the linear drive multi-purpose grease to suit the
disconnected ensure valve is at its fully required operating temperature range.
closed (down) position.
-30 to +70 °C (-22 to +158 °F) -
Turn the actuator handwheel Multis MS2
clockwise, the linear drive will move
down towards the valve spindle and -40 to +70 °C (-40 to +158 °F) -
couple the linear drive to the valve ROCOL SAPPHIRE Lo-Temp 2
spindle. -50 to +40 °C (-69 to +104 °F) -
Configure the actuator operating limits ROCOL SAPPHIRE Lo-Temp 2
following instructions in section 8. A grease nipple is situated in the base
of the actuator to enable lubrication of
the lead screw.
Apply two pumps of the specified
grease from a standard grease gun
every 30,000 starts. More frequent
greasing may be necessary depending
on usage and temperature.

Fig. 7.1.1 Terminal numbers refer to connections as shown on the actuator circuit diagram

IQ manual – Section: Cable Connections 17


WARNING: Ensure all power WARNING: Actuators for use on
supplies are isolated before phase to phase voltages greater
removing actuator covers. than 600 V must not be used on
supply systems such as floating, or
Check that the supply voltage agrees earth-phase systems, where phase
with that stamped on the actuator to earth voltages in excess of 600
nameplate. VAC could exist.
A switch or circuit breaker must be
included in the wiring installation or Power supply cables must have sufficient
the actuator. The switch or circuit mechanical protection properties to meet
breaker must meet the relevant installation requirements and be screened
requirements of IEC60947-1 and to comply with EMC requirements of
the installed actuator. Suitable methods Fig. 7.3.1 Fig. 7.3.2 Actuator terminal compartment
IEC60947-3 and be suitable for the
include armoured and/or screened cables and setting tool (Packed separately in
application. The switch or circuit
or cables contained within conduit. shipping box).
breaker must not disconnect the
The setting tool is packed separately,
protective earth conductor. The switch 7.2 Earth/Ground Connections with the actuator, in the shipping box A plastic bag in the terminal
or circuit breaker must be mounted as
identified with a yellow label. compartment contains:
close to the actuator as possible and A lug with a 6.5 mm diameter hole is
shall be marked to indicate that it is the cast adjacent to the conduit entries for The wiring code card fixed in the cover • Terminal screws and washers.
disconnect device for that particular attachment of an external protective is particular to each actuator and must
actuator. The actuator must be earthing strap by nut and bolt. An not be interchanged with any other • Spare cover O-ring seal.
protected with overcurrent protection internal earth connection is also provided actuator. If in doubt check the serial
devices rated in accordance with the number on the code card with that of • Wiring diagram.
however it must not be used alone as
applicable electrical data publication: the Protective Earth Connection. the actuator. • Instruction book.
• PUB002-099 7.3 Removing Terminal Cover
(3-phase actuators)
Using a 6 mm Allen key loosen the four
• PUB002-019 captive screws evenly. Do not attempt
(single-phase actuators) to lever off the cover with a screw
driver this will damage the O-ring seal
• PUB002-120 and may damage the flamepath on a
(3-phase modulating actuators) certified unit.
• PUB002-121
(DC actuators)

18 IQ manual – Section: Cable Connections


ATTENTION: RED PLASTIC PLUGS IN CONDUIT ENTRIES ARE FOR TRANSIT ONLY.
FOR LONG TERM PROTECTION FIT SUITABLE METAL PLUGS.

ATTENZIONE: I TAPPI IN PLASTICA ROSSA PER L'ENTRATA CAVI SONO SOLO


TEMPORANEI. PER UNA PROTEZIONE PERMANENTE PREGO SOSTITUIRLI CON APPOSITI
TAPPI METALLICI.

ATENCION: LOS TAPONES ROJOS DE PLASTICO EN LAS ENTRADAS DE CABLE SON


UNICAMENTE PARA TRANSPORTE. PARA PROTECCION PERMANENTE COLOCAR
TAPONES METALICOS APROPIADOS.

ACHTUNG: DIE ROTEN PLASTIKSTOPFEN SIND NUR FÜR DEN TRANSPORT GEEIGNET.
FÜR DAVERHAFTEN SCHUTZ SIND DIESE GEGEN GEEIGNETE BLINDSTOPFEN
AUSZÜTAUSCHEN.

ATTENTION: LES BOUCHONS PLASTIQUES ASSURENT UNE PROTECTION TEMPORAIRE.


POUR UNE PROTECTION DEFINITIVE UTILISER DES BOUCHONS METALLIQUES.

IQ manual – Section: Cable Connections 19


7.4 Cable Entry Remove plastic transit plugs. Make
cable entries appropriate to the cable
Only appropriate certified explosion type and size.
proof cable glands or conduit may be
used in hazardous locations. The cable Ensure that threaded adaptors, cable
entries in the actuator are tapped M25 glands or conduit are tight and fully
x 1.5p or M40 x 1.5p. waterproof. Seal unused cable entries
with steel or brass threaded plug.
In hazardous locations, only one In hazardous areas an appropriate
appropriate certified Explosion-Proof certified threaded blanking plug must
thread adaptor per entry may be used. be installed at the cable entry without
the use of an interposing thread
adaptor.

7.5 Connecting to Terminals


Field wiring connections are by
wire termination ring/spade tags. If
necessary, suitable insulation must be
applied to bare metal ring/spade tags
in order to ensure adequate separation
between 'hazardous live' and non-
Fig. 7.4.1 hazardous' live circuits considering,
and in accordance with, national
regulations and statutory provisions.
Tags are secured with the supplied
4 mm (control and indication) and
5 mm (power) pan head screws.

Fig. 7.4.2

20 IQ manual – Section: Cable Connections


To ensure secure electrical Refer to the wiring diagram inside the 8. Commissioning - Basic Settings and operation must be
connections, it is important terminal cover to identify functions of verified by electric operation and
terminals. Check the supply voltage
Settings
that the requisite washers are function test of the actuated valve.
used as shown in Figure 7.5.1. is the same as that marked on the
All actuator settings, Datalogger and THIS PUBLICATION PROVIDES
Failure to do so may result in actuator nameplate.
asset management data is accessed INSTRUCTION ON MAKING THE
connections working loose or Remove power terminal guard. using the supplied setting tool. Status
screws not clamping down on BASIC SETTINGS ONLY.
Begin by connecting power cables and and alarm data in addition to that
wire termination tags. Spring shown on the home screen can also For instruction on control and
replace guard. When all connections
washers must be compressed. be accessed. indication settings and for information
are made ensure wiring diagram is
Screw tightening torques must not on diagnostics refer to PUB002-040.
replaced in the terminal compartment.
exceed 1.5 Nm (1.1 lbf.ft) THE CONTROL COVER MUST
WARNING: Wiring can reach NOT BE REMOVED; NO USER
4 or 5 mm 80 oC in a 70 oC ambient CONFIGURABLE SETTINGS ARE
Pan Head temperature. For safety reasons AVAILABLE WITHIN THE CONTROL
the same voltage level must be ENCLOSURE. THE CONTROL
Spring
washer connected to all the actuator's COVER IS SEALED BY A QUALITY
indication terminals, remote input LABEL WHICH IF BROKEN MAY
Plain INVALIDATE WARRANTY.
washer Ring crimp terminals and digital I/O terminals
terminal (if applicable).
This instruction details the basic
All external circuits must be provided settings that must be completed before
Fig. 7.5.1 the actuator is put into service.
with insulation suitable for the rated
voltage whilst considering national
ELECTRICAL OPERATION MUST
To comply with Ex e certification, regulations and statutory provisions.
NOT TAKE PLACE UNTIL THE BASIC
terminals numbered 1 - 3 and earth SETTINGS HAVE BEEN MADE AND
must be fitted with 1 off AMP ring 7.6 Replacing Terminal Cover CHECKED.
crimp terminal 160292 per terminal
and terminals numbered 4 - 47 must Ensure cover O-ring seal and spigot The basic settings affect the correct
be fitted with 1 off AMP ring crimp joint are in good condition and lightly operation of the valve by the actuator.
terminal 34148 per terminal when greased before refitting cover. If the actuator has been supplied with
required. the valve, the valvemaker or supplier
may have already made these settings.

IQ manual – Section: Commissioning - Basic Settings 21


8.1 Connecting to the Actuator Below are the relevant navigation and Connecting to the actuator The Setting Tool will automatically
configuration keys to commission an IQ using Bluetooth connect using Bluetooth which
The Rotork setting tool incorporating range actuator. takes up to 5 seconds and when
Bluetooth wireless technology (Rotork The default security set in the actuator
for Bluetooth connection is by initiation connected will be indicated by blue
Bluetooth® Setting Tool Pro v1.1 – lights illuminating on the tool and
BTST) is shown below. It is identified using an infra red command. This
means that the user must be in close in the actuator display window.
by the key symbols being clear and a Once connected, the tool can be
clear seal between the top and bottom proximity and in direct line of sight of
Up used without pointing it at the
casings. the actuator.
actuator display window.
The infrared only tool has filled yellow Point the setting tool at the actuator
keys and a yellow seal between display window within a range 0.25 m Bluetooth connection will be
casings. (10 in) and Press key. maintained while setting tool key
commands are made. After a period
Left/Decrease Right/Increase The screen will change to the Main
Select/Save of 6 minutes with no key commands,
Menu screen. Bluetooth connection will be turned off
and the Setting tool and display blue
lights will go out. To manually turn
Back Forward off Bluetooth connection at any time,
Down press the setting tool and keys
together.

Fig. 8.1.1

22 IQ manual – Section: Commissioning - Basic Settings


8.2 Security – Password With the actuator selected to Local The setting screen will again be The function and its setting option or
or Stop and when any function is displayed. The example below shows range will then be highlighted:
The default security level for selected, the Password screen will be Settings – Limits – Close Settings
connecting to the actuator is by infra- displayed: with the function Action highlighted:
red Bluetooth initiation. This requires
that the user is at the actuator within
0.25 metre distance and in direct line
of sight of the display. For instruction
on connecting to the actuator refer
to 8.1.
All actuator settings can be viewed
with the actuator selected to Local,
Stop or Remote mode.
To change an actuator setting, the
actuator must be selected to Local or Fig. 8.2.2 Fig. 8.2.3 Fig. 8.2.4
Stop and a correct password entered.
The factory set default password Press the key to select. If the user does not wish to change
If the actuator is selected to Remote ROTORK is displayed and the OK the function value, press the
and a setting is selected, the following key is highlighted. back button to escape without
warning will be displayed: changing.
Press the key.

Fig. 8.2.1

Select OK to return to settings screen.

IQ manual – Section: Commissioning - Basic Settings 23


Use the or arrow keys to change The highlight will return to the function 8.3 Basic Settings Menu
the setting to the required value, the name only and its stored setting will be
example below show a close action of displayed:
Torque selected. Settings Menu CLOSE SETTINGS
Direction (CW/ACW)
Action (Torque/Limit)
Limits Torque (40 - 100%)
Set Limit

Indication
OPEN SETTINGS
Action (Torque/Limit)
Fig. 8.2.5 Fig. 8.2.6
Torque (40 - 100%)
Control
Press the key to save. The password will be requested Set Limit
the first time a function is selected.
Once correctly entered, the
password will not be required to ESD
be entered again for the duration
of setting tool communication with TORQUE SWITCH
the actuator. Other functions can BYPASS
be set as required.
Security Close
Closing Position (100 - 5%)
Open
Defaults Open Position (0 - 95%)

24 IQ manual – Section: Commissioning - Basic Settings


8.4 Basic Settings – Limits The settings menu will be displayed: The limit settings are shown below with their factory default values:
Settings and operation must be Settings Limits
verified by electric operation and
function test of the actuated valve. Limits Close Settings
Indication 1 / 15 Direction Clock Anti
Connect to the actuator as described in
Section 8.1. From the Position display Control 2 / 15 Action Limit Torque
home screen press the key. The ESD
main menu will be displayed. 3 / 15 Torque 40%
Security
4 / 15 Set Limit
Navigate to Settings using the Defaults
keys and press to select. Open Settings
Navigate to Limits using the keys 5 / 15 Action Limit Torque
and press to select.
6 / 15 Torque 40%
The setting first selected to be
changed will require a password to 7 / 15 Set Limit
be entered – refer to section 8.2. 8 / 15 Turns 25
9 / 15 Position 95.0
10 / 15
Torque Switch Bypass
Fig. 8.4.1 11 / 15 Opening On X Off
12 / 15 OP. Bypass Pos 10%
13 / 15 Closing On X Off
14 / 15 CL. Bypass Pos 90%
15 / 15
1 / 15

Function Close Direction (1 / 15) is shown highlighted. Use to scroll through


functions. Functions will be highlighted in turn. Blank settings are IQT only.

IQ manual – Section: Commissioning - Basic Settings 25


8.5 Close Settings 2 / 15. Close Action 3 / 15. Close Torque 8.6 Open Settings
1 / 15. Close Direction The actuator can be configured close The value of torque available to close 5 / 15. Open Action
on torque for seating valve types or the valve can be set between 40%
Function sets the direction required to limit for non-seating valve types. and 100% of rated. The actuator The actuator can be configured open
close the valve. Manually operate the rated torque value is shown on its on torque for seating valve types or
actuator and valve to establish closing Refer to Valve manufacturer nameplate. limit for non-seating valve types.
direction. for recommended setting. In the
absence of valvemaker instruction Press to select Close Torque Refer to Valve manufacturer
Press to select Close Direction refer to the following table. function. Use key to decrease value for recommended setting. In the
function. Use or to check and key to increase value. absence of valvemaker instruction
required setting. Press to set. Close Open set open action to “Limit”.
Valve Type Press key to set.
Action Action Press to select Open Action
Wedge gate Torque Limit function. Use or to check
4 / 15 Set Close Limit required setting. Press to set.
Globe Torque Limit
Press to select Close Limit Function.
Butterfly Limit Limit The actuator will display the following 6 / 15. Open Torque
Through Conduit Limit Limit Instruction:
The value of torque available to open
Ball Limit Limit the valve can be set between 40%
Plug Limit Limit and 100% of rated. The actuator
rated torque value is shown on its
Sluice gate Limit Limit nameplate.
Penstock Limit Limit
Press to select Open Torque
Parallel Slide Limit Limit function. Use key to decrease value
and key to increase value.
Press to select Close Action Fig. 8.5.1
Press to set.
function. Use or to check Move the actuator and valve to the
required setting. Press to set. close position. Allow for overrun by
winding in the opening direction by
½ to 1 turn.
Press to set the close limit position.

26 IQ manual – Section: Commissioning - Basic Settings


7 / 15. Set Open Limit 8.7 Torque Switch Bypass 12 / 15. Opening Bypass position 14 / 15. Closing Bypass position
Press to select Open Limit Function. The default setting for opening and When enabled (refer to 11 / 15), the When enabled (refer to 13 / 15), the
The actuator will display the following closing torque switch bypass is Off position over the opening stroke where position over the Closing stroke where
instruction: (torque protection active at all times). the torque protection is bypassed can the torque protection is bypassed can
Bypassing the torque protection allows be configured in the position range 0% be configured in the position range
torque up to approximately 150% of (closed limit) to 95% open. Outside the 100% (open limit) to 5% open.
rated to be available. The valvemaker/ bypass position, torque switch value
will revert to that set, refer to 6 / 15. Press to select Closing Bypass
integrator should be consulted to Position function. Use key to
confirm the valve structure and Press to select Opening Bypass decrease value and key to increase
interface components can withstand Position function. Use key to value. Press to set.
the additional torque/thrust. decrease value and key to increase
value. Press to set.
Fig. 8.6.1 11 / 15. Opening
Move the actuator and valve to the Opening torque protection can be 13 / 15. Closing
open position. Allow for overrun by bypassed over a configurable portion Closing torque protection can be
winding in the closing direction by ½ of the opening stroke. When enabled, bypassed over a configurable portion
to 1 turn. torque up to approximately 150% of of the closing stroke. When enabled,
Press to set the open limit position. rated torque is available for opening torque up to approximately 150% of
“sticky” valves. rated torque is available for closing
8 / 15. Turns (not editable) Press to select Opening Torque the valve. Outside the bypass position,
Shows the actuator output turns Switch Bypass function. Use or torque switch value will revert to that
between the set Closed and Open limit to check required setting. set, refer to 3 / 15.
positions. Press to set. Press to select Closing Torque
Switch Bypass function. Use or
9 / 15. Position (not editable) to check required setting.
Shows the actuator current position in Press to set.
terms of % open.
Note: Turns and Position values do
not update while being displayed
on screen. To see updated values,
use key to return to Settings
Menu, then select Limits.

IQ manual – Section: Commissioning - Basic Settings 27


9. Maintenance, Monitoring actuator covers are removed – refer to With mains power switched off and WARNING:
battery replacement instructions. without a battery fitted or when
and Troubleshooting discharged, all configured settings are Battery Replacement
Routine maintenance should include the
following: retained safely in EEPROM and position If the actuator is located within a
Maintenance hazardous area permission must be
changes are tracked by the absolute
Every Rotork actuator has been fully • Check actuator to valve fixing bolts encoder. obtained in the form of a "hot work
tested before dispatch to give years of for tightness. permit" or other local regulation
On power up, the correct, current
trouble-free operation providing it is • Ensure valve stems and drive nuts are before removal and/or replacement
position will be displayed and the
installed, sealed and commissioned in clean and properly lubricated. of the battery.
actuator will operate normally.
accordance with the instructions given in Removal of the battery with the main
• If the motorised valve is rarely WARNING: The battery holder in
this publication. electrical power switched off will result in
operated, a routine operating the actuator gearcase also protects
The IQ actuator’s unique double schedule should be set up. stored datalogger records time reference
the user from the hazardous live
sealed, non-intrusive enclosure provides being lost for the duration when there
• Replace actuator battery every connections inside the actuator and
complete protection for the actuator is no mains and battery power. It is
5 years. therefore it must not be damaged.
components. therefore recommended that the battery
• Check the actuator enclosure for The actuator must be isolated or
The IQ actuator gearing is located in an disconnected if the battery holder is replaced with the main electrical supply
damage, loose or missing fasteners. to the actuator switched on.
oil bath and is lubricated for life and does has to be removed from the actuator
not need replenishing. Should the oil be • Ensure there is not an excessive gearcase. Battery Removal
removed or lost it must not be electrically build up of dust or contaminant
on the actuator. A unique circuit has been incorporated The actuator must be selected to Stop
operated as premature failure may result.
into the battery function of the IQ, using the red selector – refer to section
Covers should not be removed for routine • Check for any loss of lubricant. effectively reducing the overall drain and 4.2. Access to the battery is via a labelled
inspection as this may be detrimental to (refer to section 11 for lubricants). significantly increasing the battery life. sealing plug situated on the main
the future reliability of the actuator. gearcase near the handwheel hub.
The Actuator Battery In normal circumstances battery
The electrical control module cover is replacement interval should not Remove the sealing plug using the
bonded by the Rotork quality control The battery supports the actuator valve
position indication relays, datalogger exceed 5 years. Ambient temperature appropriate Allen key, ensuring the
seal. It should not be removed as the and plant operating conditions may O-ring seal remains on the plug.
module contains no site-serviceable and the position display (LCD) only when
the main power supply is turned off. It affect battery life. Disconnect the battery wiring loom from
components. the battery terminals. Using the black pull
ensures the current position is indicated Battery level status is indicated by an
All electrical power supplies to the and displayed when manual operation icon on the actuator display – refer to strap, lift the battery out of the rubber
actuator must be isolated before any takes place. section 4.3. sealing pocket.
maintenance or inspection is carried out,
The battery is not required to retain If the battery icon is displayed the battery
except replacement of the battery.
any actuator settings or track position should be replaced to ensure correct
Electrical supplies must be isolated before changes. power off valve position indication.

28 IQ manual – Section: Maintenance, Monitoring and Troubleshooting


Fitting Replacement Battery in order to set appropriate open and Digital Torque and Position indication
Fit the pull strap around the closed torque switch settings.
replacement battery and insert into There a two home screen displays
the rubber sealing pocket. Reconnect that indicate torque and position
the battery wiring loom to the battery simultaneously. Refer to section 4.4
terminals. Refit the battery sealing plug
ensuring O-ring is in good condition Analogue Torque and Position
and correctly fitted. Hand tighten the indication
sealing plug to 8 Nm (6 lbs/ft) using
Fig. 9.7.1 the appropriate Allen key.
Battery Types Oil
Fig. 9.7.4
For European hazardous area certified Unless specially ordered for extreme
actuators (ATEX / IECEx) use a lithium climatic conditions, Rotork actuators Example shows that actuator at 35.0%
manganese dioxide battery as stated in are dispatched with gearcases filled open, producing 27% of rated torque.
Fig. 9.7.2 Battery Type Table. with SAE 80EP oil which is suitable for The status bar and warning triangle
For FM / CSAus and CSA certified ambient temperatures ranging from indicate that the actuator has torque
enclosures use an Ultralife U9VL lithium -30 to +70 ºC (-22 to +160 °F). tripped when closing.
manganese dioxide battery. Equivalent, IQ actuators do not require regular oil Note: The actuator will torque trip and
UL recognised, batteries may be used. Fig. 9.7.3
changes (refer to Section 11, Weights stop when the value of torque reaches
For watertight (WT) actuator and Measures). Example shows that actuator at 35.0% that set for the open (when opening)
enclosures Rotork recommend a lithium open, producing 27% of rated torque. and closing (when closing) torque
manganese dioxide battery, however Torque and Position Monitoring The warning triangle indicates the switches (refer to 8.5 and 8.6). Due
any equivalent 9V battery may be used. The IQ range of actuators incorporate actuator has torque tripped. to the effects of inertia (variable with
If in doubt regarding the correct real time, instantaneous Torque & Note: The torque and position values speed/load) and valve resilience, the
battery type, contact Rotork. Position monitoring as standard. displayed are dynamic and will show torque delivered and displayed may be
Torque & Position can be used to the actual torque and position values higher.
monitor valve performance during currently measured. After a torque trip,
Enclosure Type Battery Type Detail
operation. The effect of process the torque value tends to drop away
ATEX / IECEx - Ultralife PP3 U9VL or changes (differential pressure etc.) can as the internal mechanical components
Standard Temp Types U9VL-J-P be evaluated, tight spots in valve travel relax as no drive is present.
ATEX / IECEx - Rotork Part 95-462 or can be pinpointed as well as gauging
Low/High Temp Numbers: 95-614 the torque developed through stroke
Fig. 9.7.2 Battery Type Table

IQ manual – Section: Maintenance, Monitoring and Troubleshooting 29


10. Decommissioning In all cases check local authority All warnings as detailed in the WARNING: It is essential that
regulation before disposal. mounting and cable connection the actuator is not subject to any
and Environmental sections must be followed. Disposal of
The actuator can be removed by valve / system loads at the time
Considerations reversing the operations detailed in the the actuator or any of its components of removal as this could cause
mounting and cabling sections. should be done in accordance with the operator injury due to the actuator
End user advice on disposal at end of table below. moving unexpectedly.
life of the product.

EU Waste
Subject Definition Remarks / examples Hazardous Recyclable Disposal
Code
Lithium IQ battery Yes Yes 16 06 06 Will require special treatment before
Batteries disposal, use specialist recyclers or waste
Alkaline Setting tool Yes Yes 16 06 04 disposal companies
Electrical & Electronic Printed circuit boards All products Yes Yes 20 01 35
Use specialist recyclers
Equipment Wire All products Yes Yes 17 04 10
Glass Lens/Window IQ No Yes 16 01 20 Use specialist recyclers
Aluminium Gearcases and covers No Yes 17 04 02
Copper/Brass Wire, IQ gears, motor windings No Yes 17 04 01
Use licensed recyclers
Metals Zinc IQ clutch ring and associated components No Yes 17 04 04
Iron/Steel Gears and bases No Yes 17 04 05
Mixed Metals IQ motor rotors No Yes 17 04 07
Glass filled nylon Covers, electronics chassis No No 17 02 04 Disposal as general commercial waste
Plastics
Unfilled Gears No Yes 17 02 03 Use specialist recyclers
Mineral & Kerosene Mixed Gearbox lubrication Yes Yes 13 07 03
Mineral Gearbox lubrication Yes Yes 13 02 04 Will require special treatment before
Oil /Grease disposal, use specialist recyclers or waste
Food Grade Gearbox lubrication Yes Yes 13 02 08 disposal companies
Grease Side handwheel / linear drive Yes No 13 02 08
May require special treatment before disposal,
Rubber Seals & O-rings Cover and shaft sealing Yes No 16 01 99
use specialist waste disposal companies

30 IQ manual – Section: Decommissioning and Environmental Considerations


11. Weights and Measures Grease – Base assembly Inverted installation *Oil capacity shown for Top Hand
O-rings use either Multis EP2 / If inverted installation (base uppermost) Wheel actuators. Side Hand Wheel
Lubricating oil Lithoshield EP2 or equivalent for all was specified with the order, Rotork actuator capacity is 2.20 (4.65).
Refer to actuator name plate. IQ temperature ranges between will oil fill to the quantities shown
actuators are lubricated using the -50 and +70 ºC (-58 and +158 ºF). in the table below and the actuator
oil grades specified below. They are will be labelled “Factory filled with
Oil capacity is shown on the actuator additional oil for inverted use”. If not
factory filled for life and in normal
oil capacity label. Only use the oil specified with order but site installation
service do not require topping up.
capacities stated in this manual if an oil will be inverted, to ensure adequate
Ambient temperatures ranging from fill label is not present. lubrication the installer must top up
-30 to 70 °C (-22 to 160 °F): SAE 80EP the oil before installation using the top
lubricating oil. Standard weight and lubricating oil
capacities: oil plug by the amount indicated in the
Ambient temperatures below -30 °C table.
(-22 °F): Mobil SHC 624 lubricating oil. Actuator Weight Oil Capacity For oil plug location, refer to section
Food grade lubricating oil Size kg (lbs) litres (pt.-US) 1.1.
If user specified, IQ actuators will IQ10 31 (68) 1.25 (2.64) Inverted installation lubricating oil
be filled with Hydralube GB Heavy IQ12 31 (68) 1.25 (2.64) capacities:
food grade lubricating oil suitable for
IQ18 31 (68) 1.25 (2.64)
temperature range -20 to 70 °C Inverted Oil Capacity Top-up quantity
Actuator Size
(-4 to 160 °F). IQ19 54 (119) 1.9 (4.0)* litres (pt.-US) litres (pt.-US)

Grease – Side handwheels IQ20 54 (119) 1.9 (4.0)* IQ10, 12, 18 1.25 (2.64) 0.0 (0.0)

Extreme pressure multipurpose grease IQ25 54 (119) 1.9 (4.0)* IQ19, 20, 25 1.90 (4.0)* 0.0 (0.0)
MULTIS MS2 or equivalent. For low IQ35 75 (165) 2.4 (5.1) IQ35 2.75 (5.81) 0.35 (0.74)
temperatures use a grease suitable for
IQ40 145 (320) 3.7 (7.8) IQ40, 70, 90, 91, 95 5.7 (12.04) 2.0 (4.23)
use at -50 °C such as Optitemp TT IEP.
IQ70 145 (320) 3.7 (7.8)
Grease – Linear drive unit
IQ90 160 (353) 3.7 (7.8)
IQL and IQML linear drive assemblies
should be regularly lubricated using the IQ91 150 (331) 3.7 (7.8)
specified grease. Refer to section 6.8. IQ95 160 (353) 3.7 (7.8)

IQ manual – Section: Weights and Measures 31


IQ Cover tubes 12. IQ Approvals European – Hazardous Area
Cover tubes not supplied by Rotork ATEX (2014/34/EU) II 2 GD
shall be designed to ensure that they Refer to actuator nameplate for unit
do not exceed BOTH mass and moment specific approval details. Ex db1 h IIB T4 Gb IP66/IP68
parameters listed in the table below. Ex h tb IIIC T120ºC Db
Temperature -20°C to +70°C (-4°F to +158°F)
They shall also be of a suitable
material for the application and be *Option -30°C to +70°C (-22°F to +158°F)
suitably finished and protected for the *Option -40°C to +70°C (-40°F to +158°F)
environmental conditions. *Option -50°C to +40°C (-58°F to +104°F)

If cover tubes exceed these parameters Ex db1 h IIC T4 Gb IP66/IP68


(due to weight, length, wind, etc.) they Ex h tb IIIC T120ºC Db
must be properly supported. Temperature -20°C to +70°C (-4°F to +158°F)
*Option -30°C to +70°C (-22°F to +158°F)
Maximum Maximum Maximum Maximum *Option -40°C to +70°C (-40°F to +158°F)
Frame size mass mass moment* moment* *Option -50°C to +40°C (-58°F to +104°F)
(kg) (lbs) (Nm) (lbf.ft)
1
E x eb added if the terminal enclosure
IQ10 – IQ18 5 11 305 225 is increased safety.
IQ19 – IQ25 11 24.3 690 509
IQ35 17 37.5 955 704
IQ40 – IQ95 17 37.5 955 704

*Moment measured about centre of


cover tube bolt mounting PCD.

32 IQ manual – Section: IQ Approvals


International – Hazardous Area China - Hazardous Area (CCC Ex) USA – Hazardous Area International Non Hazardous
IECEx. IEC60079-0, IEC60079-1 GB 3836.1-2010, GB 3836.2-2010, FM & CSAus - Explosionproof and Watertight, BS EN60529
& IEC60079-31 GB 3836.3-2010 Dust Ignition Proof to NEC Article 500, IP66 & IP68, (20 metres for 10 days).
Ex db1 h IIB T4 Gb IP66/IP68 FM 3600, FM 3615 and FM 3616.
GB 12476.1-2013, GB 12476.5-2013 Temperature -30°C to +70°C (-22°F to +158°F)
Ex h tb IIIC T120ºC Db Ex d IIB T4 Gb Class I, Division 1, Groups C & D *Option -40°C to +70°C (-40°F to +158°F)
Temperature -20°C to +70°C (-4°F to +158°F) Ex tb IIIC T120°C Db, IP66 & IP68 Class II, Division 1, Groups E, F & G *Option -50°C to +40°C (-58°F to +104°F)
*Option -30°C to +70°C (-22°F to +158°F) Temperature -30°C to +70°C (-22°F to +158°F)
Temperature -20°C to +70°C (-4°F to +158°F)
*Option -40°C to +70°C (-40°F to +158°F) *Option -30°C to +70°C (-22°F to +158°F)
*Option -40°C to +70°C (-40°F to +158°F) USA – Non Hazardous
*Option -50°C to +40°C (-58°F to +104°F) *Option -50°C to +40°C (-58°F to +104°F).
*Option -40°C to +70°C (-40°F to +158°F) Enclosure Type 4 & 6
*Option -50°C to +40°C (- 58°F to +104°F). Class I, Division 1, Groups B, C & D
Ex db1 h IIC T4 Gb IP66/IP68 Temperature -30°C to +70°C (-22°F to +158°F).
Ex h tb IIIC T120ºC Db Ex d IIC T4 Gb Class II, Division 1, Groups E, F & G *Option -40°C to +70°C (-40°F to +158°F)
Temperature -30°C to +70°C (-22°F to +158°F) *Option -50°C to +40°C (-58°F to +104°F).
Temperature -20°C to +70°C (-4°F to +158°F) Ex tb IIIC T120°C Db, IP66 & IP68
*Option -40°C to +70°C (-40°F to +158°F)
*Option -30°C to +70°C (-22°F to +158°F) Temperature -20°C to +70°C (-4°F to +158°F)
*Option -50°C to +40°C (-58°F to +104°F). Canada – Non Hazardous
*Option -40°C to +70°C (-40°F to +158°F) *Option -30°C to +70°C (-22°F to +158°F)
*Option -50°C to +40°C (-58°F to +104°F) *Option -40°C to +70°C (-40°F to +158°F) Enclosure Type 4, 4X & 6
*Option -50°C to +40°C (-58°F to +104°F). Canada – Hazardous Area
1 Temperature -30°C to +70°C (-22°F to +158°F)
 x eb added if the terminal enclosure
E
is increased safety. Ex de IIB T4 Gb CSA Explosionproof to C22.2 No. 30 *Option -40°C to +70°C (-40°F to +158°F).
*Option -50°C to +40°C (-58°F to +104°F).
Ex tb IIIC T120°C Db, IP66 & IP68 CSA Dust Ignition Proof to C22.2
Indian Hazardous Area No. 25
Temperature -20°C to +70°C (-4°F to +158°F)
IS/IEC-60079-0, IS/IEC-60079-1 *Option -30°C to +70°C (-22°F to +158°F) Class I, Division 1, Groups C & D Rotork can supply actuators to national
Ex db IIB T4 Gb *Option -40°C to +70°C (-40°F to +158°F) Class II, Division 1, Groups E, F & G standards not listed above. For details
Temperature -20°C to +70°C (-4°F to +158°F)
*Option -50°C to +40°C (-58°F to +104°F). Temperature -30°C to +70°C (-22°F to +158°F) please contact Rotork.
*Option -40°C to +70°C (-40°F to +158°F)
Ex de IIB T4 Gb
Ex db IIC T4 Gb *Option -50°C to +40°C (-58°F to +104°F).
Ex tb IIIC T120°C Db, IP66 & IP68
Temperature -20°C to +70°C (-4°F to +158°F)
Temperature -20°C to +70°C (-4°F to +158°F) Class I, Division 1, Groups B, C & D
*Option -30°C to +70°C (-22°F to +158°F) Class II, Division 1, Groups E, F & G
*Option -40°C to +70°C (-40°F to +158°F) Temperature -30°C to +70°C (-22°F to +158°F)
*Option -50°C to +40°C (-58°F to +104°F). *Option -40°C to +70°C (-40°F to +158°F)
*Option -50°C to +40°C (-58°F to +104°F).

IQ manual – Section: IQ Approvals 33


13. Approved Fuses 14. Vibration, Shock and Noise 15. Conditions of Safe Use
FS1 = Bussman TDC11 (rating as per Standard IQ range actuators are EMC
transformer type. See actuator wiring suitable for applications where The equipment is intended for use
diagram for transformer type). vibration and shock severity does not in an industrial electromagnetic
Type 1 = 250 mA anti-surge exceed the following: environment.
Type 2 = 250 mA anti-surge Type Level
Type 3 = 150 mA anti-surge 15.1 Thread details for ATEX and
1g rms total for all vibration IECEx Approved actuators
Plant induced
within the frequency range of
FS2 (ATEX units only) vibration
10 to 1000 Hz
Bussman TDS 500 - 100 mA Quickblow Shock 5g peak acceleration Threaded Flamepath Thread Size Thread Length Actuator Type and Size
or Littel Fuse 217 - 100 mA Quickblow
2g acceleration over a Battery Cover M40x1.5 10.00 All Types and Sizes
frequency range of 1 to 50 Hz
Seismic
if it is to operate during and M25x1.5 20.00 All Types and Sizes
after the event Cable Entry
M40x1.5 20.00 All Types and Sizes
Independent tests have shown
Emitted noise that at 1m generated noise
does not exceed 65 db(A)

34 IQ manual – Section: Approved Fuses


15.2 Maximum constructional flamepath gaps for ATEX and IECEx Approved actuators.

Flamepath Max. Gap (mm) Min. Length (mm) Actuator Type and Size

Motor Cover / Gearcase 0.15 25.00 IQ10, IQ12, IQ18, IQ19, IQ20, IQ25, IQ35, IQM10, IQM12, IQM20, IQM25, IQS12, IQS20, IQS35, IQ40, IQ70, IQ90, IQ91, IQ95
35.00 IQ10, IQ12, IQ18, IQM10, IQM12, IQS12
Wormshaft Shroud / Gearcase 0.05 38.00 IQ19, IQ20, IQ25, IQM20, IQM25, IQS20
35.00 IQ35, IQS35
Wormshaft Shroud / Gearcase -0.04/0.00 49.75 IQ40, IQ70, IQ90, IQ91, IQ95
26.00 IQ10, IQ12, IQ18, IQM10, IQM12, IQS12
Wormshaft / Wormshaft Shroud 0.24 26.00 IQ19, IQ20, IQ25, IQM20, IQM25, IQS20
27.00 IQ35, IQS35
Wormshaft / Wormshaft Shroud 0.25 49.75 IQ40, IQ70, IQ90, IQ91, IQ95
Terminal Bung Gearcase (IIB) 0.20 27.00 All Types and Sizes
Terminal Bung Gearcase (IIC) 0.115 27.00 All Types and Sizes
Terminal Cover / Gearcase 0.15 27.00 All Types and Sizes
Electrical Cover / Gearcase 0.15 26.00 All Types and Sizes
Encoder Shaft / Encoder Shaft Bush 0.08 27.00 All Types and Sizes
Encoder Shaft Bush / Gearcase 0.07 25.00 All Types and Sizes
28.75 IQ10, IQ12, IQ18, IQ19, IQ20, IQ25, IQ35, IQM10, IQM12, IQM20, IQM25, IQS12, IQS20, IQS35
Motor Loom Bush / Gearcase 0.15
33.25 IQ40, IQ70, IQ90, IQ91, IQ95
DC Motor Adaptor / Gearcase 0.15 25.00 IQD10, IQD12, IQD18, IQD20, IQD25
DC Motor Cover / DC Motor Cover Adaptor 0.15 12.50 IQD10, IQD12, IQD18, IQD20, IQD25

Note: Negative sign denotes an interference fit.

IQ manual – Section: Conditions of Safe Use 35


UK USA A full listing of our worldwide sales and service
Rotork plc Rotork Controls Inc. network is available on our website.
tel +44 (0)1225 733200 tel +1 (585) 247 2304
fax +44 (0)1225 333467
email mail@rotork.com
fax
email
+1 (585) 247 2308
info@rotork.com www.rotork.com
Original instructions: English language version only. As part of a process of on-going product development, Rotork reserves the right to amend and
change specifications without prior notice. Published data may be subject to change. For the very latest version release, visit our website at www.rotork.com
PUB002-039-00
The name Rotork is a registered trademark. Rotork recognises all registered trademarks. The Bluetooth® word mark and logos are registered trademarks
owned by Bluetooth SIG, Inc. and any use of such marks by Rotork is under license. Published and produced in the UK by Rotork. POWTG0121 Date of issue 01/21