CIRCUITO 5

DMD + Regulación
Numero de K conductor Momento Regulacion
Tramo Longitud (m) DMD (kVA) alumbrado acumulada
usuarios (%kVA - m) (kVA-m) parcial
(kVA) (%)
tramo 1 101-102 26 2 5,46 5,535 6,59E-04 143,91 9,48E-02 7,97E-01
100-101 27,5403 3 8,19 8,265 6,59E-04 227,62058 1,50E-01 7,02E-01
99-100 28 6 13,2 13,275 6,59E-04 371,7 2,45E-01 5,52E-01
98-99 28 8 16,56 16,635 6,59E-04 465,78 3,07E-01 3,07E-01
97-98 29,5831 19 32,11 32,185 6,59E-04 952,132074 6,27E-01 6,27E-01
91-97 25,1773 31 46,81 46,885 6,59E-04 1180,43771 7,78E-01 7,78E-01
tramo 2 117-118 28 1 2,73 2,805 6,59E-04 78,54 5,17E-02 1,72E+00
116-117 28 4 10 10,075 6,59E-04 282,1 1,86E-01 1,67E+00
115-116 27,7804 6 13,2 13,275 6,59E-04 368,78481 2,43E-01 1,48E+00
103-115 26,9708 7 14,91 14,985 6,59E-04 404,157438 2,66E-01 1,24E+00
98-103 27 10 19,5 19,575 6,59E-04 528,525 3,48E-01 9,75E-01
97-98 29,5831 19 32,11 32,185 6,59E-04 952,132074 6,27E-01 6,27E-01
91-97 25,1773 31 46,81 46,885 6,59E-04 1180,43771 7,78E-01 7,78E-01
tramo 3 107-108 23,5 1 2,73 2,805 6,59E-04 65,9175 4,34E-02 1,00E+00
106-107 23,5 4 10 10,075 6,59E-04 236,7625 1,56E-01 9,59E-01
105-106 23,5 6 13,2 13,275 6,59E-04 311,9625 2,06E-01 8,03E-01
104-105 23,5 9 18,09 18,165 6,59E-04 426,8775 2,81E-01 5,97E-01
97-104 24,5 10 19,5 19,575 6,59E-04 479,5875 3,16E-01 3,16E-01
91-97 25,1773 31 46,81 46,885 6,59E-04 1180,43771 7,78E-01 7,78E-01
tramo 4 95-96 24,5 1 2,73 2,805 6,59E-04 68,7225 4,53E-02 8,50E-01
94-95 23,2535 2 5,46 5,535 6,59E-04 128,708123 8,48E-02 8,04E-01
93-94 23,5 5 11,85 11,925 6,59E-04 280,2375 1,85E-01 7,20E-01
92-93 23,5 7 14,91 14,985 6,59E-04 352,1475 2,32E-01 5,35E-01
91-92 23,5 10 19,5 19,575 6,59E-04 460,0125 3,03E-01 3,03E-01

trafo en el 91

KVA 66,46
usuarios 41