Manual SIRIUS 3SK2 Safety Relays Online Help in TIA Portal V17
https://support.industry.sie
mens.com/cs/ww/en/view/1
09444336
The chapter 14. is build up like a construction kit. It is split into the "detecting", "evaluating" and "reacting" subsystems.
? ?
+
Page 5 Unrestricted | © Siemens 2021 | SI EP | October 2021
SIRIUS Safety ES in TIA Portal V17
Overview of relevant manuals
The chapter 14. is build up like a construction kit. It is split into the "detecting", "evaluating" and "reacting" subsystems.
? ?
+
Page 6 Unrestricted | © Siemens 2021 | SI EP | October 2021
SIRIUS Safety ES in TIA Portal V17
Safety Integrated Application Manual (SIAM)
Content:
• Introduction to Functional Safety
• Explanation of certain standards
• More than 90 pages of application examples with MSS, 3SK1 and
3SK2
• Each example offers downloadable content with MSS/3SK2 project
files, safety evaluation per SET, wiring diagrams and CAx download
links
SIMATIC S7-PLCSIM
Advanced
SIMATIC
STEP 7 Safety
SIMATIC ODK 1500S
SIMATIC Target™
SiVArc SINAMICS DCC
for Simulink®
SIRIUS
SIRIUS ES
SIRIUS
SIRIUS ES
+ SIMATIC
STEP 7
Advantages Advantages
• Easy to install • Possibility of configuring a PLC for the standard
• No additional license required in TIA Portal besides (non safety)
SIRIUS Safety ES • Configuring of S7 and 3SK2 in one single project
• Configuration of data exchange between PLC and
Disadvantages 3SK2
• No additional features beyond SIRIUS Safety ES
• Unable to configure other products (e.g. PLC for Disadvantages
standard non-safety) • Installation is more complex
• Additional license for STEP7 required in TIA Portal
Description
▪ After unlocking the E-Stop and pushing the start button, the contactors get energized via of the safety relay
▪ Pushing the E-Stop, the contactors switches off
▪ A restart is only possible after unlocking the E-Stop and acknowledging via start button
5
Navigation window: Selection of the
1 various views of the open project
Work space: Editing the project,
2 depends on selected view in
2 navigation window
Output window: Contains
3 information on the project
4 Catalog window: Depending on
1 4
the navigation window, here you
find the needed components for
3 the configuration
Menu bar and Tool bar:
Required functions for program
5 control and contains buttons for
frequently used program
commands
Using the project tree features gives you access to all components and project
data. You can perform the following tasks in the project tree:
1
•1 Title bar •8 Cross-device functions
2
3
•2 Toolbar •9 Unassigned devices
4
5
•3 Table header •10 Common data
8
•5 Devices (Full functionality) •12 Languages & resources
9
10
•6 Ungrouped devices •13 Online access
11
12
•7 Security settings •14 Card Reader / USB memory
13
14
In the "Online access" folder of the project tree, you •1 "Online access" folder in the project tree with all
will find all active interfaces of your programming PG/PC interfaces installed
device/PC. Each interface icon provides you with
information on the status. You can also display the •2 Display/hide interfaces
accessible devices and display and edit the properties
of an interface using the shortcut menu.
•3 Status display for the interfaces by an icon to the
1
right of the name
2
5
•5 Display more information
6
•1 Open
3
TIA Portal
V17
with Safety ES
Portal view
• “Create new project”
2
•4 “Create”
First Steps
First Steps
•3 “Control Devices”
•5 “Add”
•1 Open
TIA Portal
V17
with Safety ES
Project view
• “Project view”
2
•3 “New project”
•5 Press “Create”
•2 “Control Devices”
•3 “Detecting &
Monitoring”
“SIRIUS safety
technology”
“SIRIUS safety relay”
Select your device
•4 “OK”
•6 Additional device stations can be added via the hardware catalog using drag & drop
•7 “Device configuration”
•8 Selected 3SK2 basic module can be changed via the hardware catalog per Drag&Drop or via right-click
“Change device”
•9 All expansion modules like interface modules or diagnostics displays can be added optionally in the
configuration at station slot 1 and 2
•4 In the "Marking" area, you can enter information on the projecting machine or system.
•7 In addition, information on the release of the project planning have to be provided under "Release
Information“ (mandatory for commissioning).
•1 In section “Basic Unit” >> “Configuration” you can add an “Equipment identifier” for your safety relay
•2 In “Terminal list” you can assign symbolic names for in- and outputs of the 3SK2. This offers easy orientation
to the wiring diagram.
•3 Pressing the button “Supplement Identifier” adds default identifiers to all terminals that have not been set
•4 In „Parameter Assignment“ >> „Device Response“ the program cycle time can be adjusted
(limited range from 10 up to 60 ms).
•5 All expansion modules with its equipment identifier can be added optionally in the configuration for plant
documentation via “Documentation” >> “Device Connector”
If an interface module has been configured, the following additional settings are available.
•6 In “Interface modules” >> “Terminal list” you can assign symbolic names for in- and outputs of the 3SK2
PROFINET interface module. This offers easy orientation to the wiring diagram.
•7 Pressing the button “Supplement Identifier” adds default identifiers to all terminals that have not been set
•8 In section “Configuration” you can add an “Equipment identifier” for your interface module,
•9 „Block“ and „Release“ group diagnostics in „Diagnostics“ and
•10 change authorisations for „Ethernet addresses“
10
•11 The same goes for HMI modules, in section “Configuration” you can add an “Equipment identifier” for your
HMI module
11
•5 Press „OK“
Chart properties
•4 Sheet bars
• Static, dynamic or no sheet bars 3
•1 Select a function block in the chart (Note: There are different parameters depending on the function block)
In section „Properties“ ( 2 ) >> „General“ ( 3 ) you can set „Name“ ( 4 ) and „Comment“ ( 5 ) for the function block
number, Element
activated/deactivated)
•4 Input parameters (Input type, inputs,
delay, cross-circuit detection) 5
•1 Via “Properties” → 2 “Terminals & References” the identifier for in- and outputs can be edited at any time ( 3 )
Here you can now also see which function block the signal is connected to ( 4 ) and in which chart the function
block is used ( 5 )
4 5
•1 „Compile“
•2 „Load to device“
•7 Click „Load“
10 11
12
12
1
Preconditions (not mandatory but
helpful for plant documentation):
• Offline project is opened
• Active connection to 3SK2
(PC/PG cable / field bus)
• 3SK2 is in configuration mode ( 2 )
8
•6 Select your device in project tree
•7 Click „Print“
Under "Print objects/area", select what is to be Select the print scope under "Properties".
printed. The selection is only possible if you have
started the printout from an editor that supports this
function.
• Select "All" to print out the entire content of the • Select "All" to print all configuration data of the
editor. selected objects.
• Select "Selection" to print only the objects currently • Select "Visible" to print the information of an editor
selected in the editor. that is currently visible on the screen. This option
can only be chosen if you have started the printout
from an editor.
• Select "Compact" to print out an abbreviated
version of the project data.
Page 58 Unrestricted | © Siemens 2021 | SI EP | October 2021
Change to test mode
Step 3
Starting with SIRIUS Safety ES in TIA Portal V17
Commissioning – Prepare configuration test
12
•1 In section „Commissioning“
→„Commands“ changing of
operating state ( 2 ) is only possible 1
in online mode 2
•1 Online monitoring is now possible in chart view using the button „Monitor“ ( 2 )
•3 Afterwards you can watch the signal states of each function block
1
3
Icon Meaning
The function element is deactivated.
At least one output is active.
The function element is ready and is waiting for a start signal.
The function element is waiting for the startup test. When the startup test is active, the sensor that is
being monitored must be actuated once. Faults must not occur here.
A time function is running.
Wiring fault. For input cells this means that the substitute value is active.
Logic error. Example: The status of the feedback contact does not match the desired value.
•1 Forcing enables commissioning of the plant without hardware by right click on the signal
• Only available in test mode
• Manual manipulation of signal states
• Output pins of all software elements can be forced ( 2 )
• Test of safety logic through incomplete plant installation
• Active connection to PG/PC necessary (Online connection to 3SK2 Basic Unit)
1
Preconditions (mandatory):
• Save the configured project
• Offline project is opened
• Active connection to 3SK2 per
PG/PC cable or fieldbus
• 3SK2 is in configuration mode
(2)
3
•8 If you need to do some changes in configuration, you can cancel your released configuration anytime ( 9 )
•9 After configuration release, „Go online“ and change to operation mode „Safety mode“ ( 10 ) and confirm ( 11 )
11
10
Hint:
Now if you want to expand the
application, change from
“Safety mode” back to
“Configuration mode” in online
state. The approval prohibits
any changes which concern
the configuration CRC.
• The application is now approved
• The connection to the PG/PC can be removed
• The 3SK2 safety relay works by itself
path
„Options“ → „Settings“
General
•1
1
User
•2 Interface Language 2
•3 Mnemonic 3
•4 General settings
•5 Reset settings to default
4
Print settings
•1 General
•2 Hardware configuration
1
•3 Printout
2
Charts
SIRIUS ES
•1 Cyclic update
•2 License
In order to establish a connection with the PROFINET interface module, the PG/PC interface must first be set.
This can be found under 1 “Options“ → “Settings” → 2 Online & diagnostics” → “Default connection path for
online access”. Select the interface of your PG/PC that is connected to the PROFINET IM ( 3 ).
When the PROFINET IM is put into operation for the first time, it must first be provided with a PROFINET device
name in order to establish a connection with the PG/PC.
•1 Select „Online & diagnostics“
•2 „PROFINET Interface“ → „Functions“
→ „Assign PROFINET device name“
•3 Select the PG/PC interface
connected to the PROFINET IM and
set device filter if necessary 3
Now it is possible to load via the PROFINET IM. At the first load, the IP address configured in the project is
assigned for the PROFINET IM.
TIA Portal
STEP7+SafetyES
Configuring Parameterization
•4 In „Parameter Assignment“ → „Device Response“ the „Process data structure“ can be set
(32DI/32DQ or 64DI/64DQ).
•1 In „Device configuration“,
select the PROFIBUS IM
from the hardware
catalog
•2 Add the PROFIBUS IM
to system slot 2 via
drag&drop
•3 Double click →
„Properties“ → „General“
→ „PROFIBUS address“
•4 Assign here PROFIBUS
parameters
4
•
1
“Options”
•
2
“Manage general station description
files (GSD)”
•
3
Select file path with stored GSDML file
•
4
Select the correct GSDML file
•
5 „Install“
•4 If necessary,
change process
image for data
exchange with the
PLC into the device
view (64DI/64DQ or
32DI/32DQ)
Attention:
The chosen structure
of process data must
correspond to the
structure chosen in
Safety ES.
•5 In „Parameter Assignment“ → „Device Response“ the „Process data structure“ can be set
(32DI/32DQ or 64DI/64DQ).
•1 Project libraries are used to better organize and sort plans within a project.
The individual plans, which are to serve as templates, can be inserted
1
within the “Master copies" section.
•2 Global libraries are used to reuse charts across projects and users. New
global libraries can be created, opened, saved, and closed again. The
folder function is also available here.
Optionally you can store your chart in „Master copies“ in the project library or a global library for use in other
projects again
•1 Open „Libraries“
•2 Select „Project 2
library“ or a „Global
library“
•3 Insert Charts via
Drag&Drop in folder
„Master copies“
Former projects can be migrated from SIRIUS Safety ES V 1.0 (*.sdp) to TIA Portal V17 (*.ap17).
In order to migrate macros from your project (*. sdp), you have to create the stored macros ( 1 ) as individual
plans first ( 2 ), save your project and close Safety ES. For the migration, proceed as follows.
Portal view
•1 “Start”
•2 “Migrate project”
•3 Select project to be migrated
•4 Set Target Project name, path, author and
Comment
•5 Click “Migrate”
Project view
•1 „Project“
•2 „Migrate project…“
•3 Select project to be migrated
•4 Set target project name, path, author and
Comment
•5 Click “Migrate”
•6 TIA Portal V17 starts creating a new project (*.ap17) at your target path with your choosen project properties
•7 Afterwards the migration of your former project in your •8 Confirm after successful migration with “OK”
new project (*ap17) starts
Hint:
•1 In case you have created plans with macros, during the migration, these plans are then migrated
•2 After that, these can subsequently be transferred to project library or a global library.
2
1
•1 Make sure that one of these options is •4 Select „PG/PC interface“, click „Start search ( 5 )
selected •6 Select your device and click „Upload“ ( 7 )
Accessible devices can be uploaded via
2
"Online" → 3 “Upload device as new station“.
•1 Alternatively, in section „Online Access“ via right- •4 After upload, the new station appears in the project
click the „Accessible device“ ( 2 ) can be upload as tree. Now the full functionality is given.
new station ( 3 )
1
After the online connection has been established successfully, the user interface changes. If a device is
unavailable, this is indicated by a symbol. The following figure shows a device connected online and the
corresponding user interface:
1
•4 Diagnostic status
2
in foreground
3
Icon Meaning
The connection is currently being established.
Device is not reachable at the set address.
The configured device and the device actually present are of incompatible types.
The password dialog was terminated without specification of the correct password.
No fault
Maintenance required
Maintenance demanded
Error
The module or device is deactivated.
The module or the device cannot be reached.
The functionality of the module or submodule is no longer available.
Diagnostics not or only partially possible.
The connection is established, but the module status has not yet been determined or is unknown.
The configured module does not support display of the diagnostics status.
Hardware error in lower-level component: A hardware fault has occurred in at least one lower-level hardware component
•1 In section „Online & diagnostics“ you can set or change the „Online access“ ( 2 ) between PC/PG and the
3SK2 safety relay
•5 „Diagnostic status“ shows the diagnostic state of •6 Detailed Information to the status are listet in
the online connected safety relay „Channel diagnostics“
5
6
•1 In section “Commissioning” > 2 “Diagnostics” > you will find an “Overview” ( 3 ) of the current errors and
warnings
•4 In the table below you get more information on the pending faults or warnings
1
3
•5 Select between „flat view“ and „hierarchical view“ (with option „Collapse all“)
•6 Optionally, you can filter the table by „Error“, „Operating error“, Warning, „Prewarning“ or „Event“
•7 And export the table as an CSV file (*.csv)
Flat view
Hierarchical view
•1 In Section „Status“ you will find the element numbers ( 2 ) at which the error or warning occurs
•4 In Section „Configuring“ and „Configuration“ ( 5 ) the indicators to diagnose the configuring/configuration state
( 6 ) of the safety relay can be found
6
6
activities significantly
• Quick help by
SIEMENS service from
offsite
4
•4 CSV export and logbook
delete
„Element diagnostics“
1
•3 After troubleshooting you
can do an „Element reset“
•4 „Element status“ shows the 4
the problem
•1 In section „Compare
parameters“ you can check
„Offline CRC“ and „Online
CRC“ anytime ( 2 ) 2
• It is quite possible to configure several 3SK2 in one and the same TIA Portal
V17 project.
• In this case, any additional devices have to be inserted into the project via “Add
1
new device” or “Upload device as new station”.
• The configuration of the individual 3SK2 takes place independently of each other
2
(see 1 and 2 ).
• There are applications which require to read out the diagnostics data from the 3SK2 by
means of a SIMATIC S7 CPU. In this case, both devices can be configured
independently in one and the same project (see 1 and 2 ).
• For data exchange between the two devices, the 3SK2 PROFINET IM is available.