TABLE OF CONTENTS

DESCRIPTION SHEET NO.

SITE DEVELOPMENT PLAN


TABLE OF CONTENTS
VICINITY MAP A1 BUILDING OFFICIAL

FLOOR PLAN
ELEVATIONS
SECTIONS A2
REFLECTED CEILING PLAN
SCHEDULE OF DOORS
AND WINDOWS A3 LINE AND GRADE

FOUNDATION PLAN
ROOF FRAMING PLAN
DETAIL OF FOOTINGS
DETAIL OF WALL FOOTING
DETAIL OF BEAM
S1
LAND USE AND ZONING

WATER LINE LAYOUT


SEWER LAYOUT
DETAIL OF SEPTIC TANK
LEGENDS AND SYMBOLS
GENERAL PLUMBING NOTES
P1
ARCHITECTURAL
LIGHTING LAYOUT
POWER LAYOUT
LOAD COMPUTATION
GENERAL ELECTRICAL NOTES E1
PERSPECTIVE RISER DIAGRAM

STRUCTURAL

VICINITY MAP

ELECTRICAL

SANITARY

MECHANICAL

SITE DEVELOPMENT PLAN


SCALE: 1:100 MTS
BUREAU OF FIRE
PROPOSED PROJECT OWNER SHEET CONTENT: SHEET NUMBER

PTR NO. :
ARCHITECT-UAP
PROPOSED AS SHOWN
PRC NO:
TIN:
2- STOREY RESIDENTIAL DESIGNED BY: DRAWN BY: APPROVED BY:
1 2 3

ROOF APEX LINE

1 2 3

2.850
1 2 3
A A
TOP OF THE BEAM

5.000 3.500 CEILING LINE


5.000 3.500

0.300
2.700

9.550
W
2
W
SECOND FLOOR LEVEL
A
3
A
CEILING LINE

2.000
2.000

0.300
D 12 D
3.000

4 3

3.000
5 B

4.300
W

B W
2

4 19
17
6 FINISH FLOOR LINE

3.000
C

3.000
C 7
W
2.000

W
D NATURAL GROUND LINE

0.400
D 5
4

D
D 5

D
3

2.700
D
3
W
2
W
2
16
D
8 D
18
2.000

W 3
2
4
D
4 5

E E

14.300
11
FRONT ELEVATION
14.300
4.300

W
2
15

2.100
W
7 SCALE: 1:100 MTS
3
B B
W
W 1 D
1
3.500

F F

1.200
13 D
1.200

6
9
G G 14
W
D 6
1
2.000

2.950
A

5.000
I G F E D C B
5.000

1
2.750

W
5
D
3

2
H
10 H
1.000

W
5

I I ROOF APEX LINE

2.500 2.300 3.700


2.500 2.300 3.700

2.850
8.500
8.500

TOP OF THE BEAM

CEILING LINE

A GROUND FLOOR PLAN A SECOND FLOOR PLAN

0.300
2.700

9.550
SCALE: 1 : 100 SCALE: 1 : 100
SECOND FLOOR LEVEL

CEILING LINE

0.300
LEGEND:

3.000
FINISH FLOOR LINE

GROUND FLOOPR 6. GUEST BEDROOM SECOND FLOOR 18. COMMON TOILET NATURAL GROUND LINE

0.400
7. PANTRY AND BATH
1. ENTRY PORCH 8. STORAGE 13. HALLWAY 19. MASTER TOILET
2. GARAGE 9. STAIR 14. BALCONY AND BATH
3. LIVING ROOM 10. TOILET AND BATH 15. BOY'S BEDROOM
4. DINING ROOM 11. LANAI 16. GIRLS BEDROOM
LEFT SIDE ELEVATION
SCALE: 1:100 MTS
5. KITCHEN AREA 12. SERVICE AREA 17. MASTER BEDROOM

PROPOSED PROJECT OWNER SHEET CONTENT: SHEET NUMBER

PTR NO. :
ARCHITECT-UAP PROPOSED AS SHOWN
PRC NO: 2- STOREY RESIDENTIAL DESIGNED BY: DRAWN BY: APPROVED BY:
TIN:
LEGEND: PIN LIGHT

CHANDELIER A B C D E F G H I

CIRCULAR LED FLUORESCENT LIGHT

RECTANGULAR FLUORESCENT LIGHT


ROOF APEX LINE
WALL LAMP

3 2 1 3 2 1

2.850
TOP OF THE BEAM
3.500 5.000
3.500 5.000
CEILING LINE

0.300
2.700

9.550
A A SECOND FLOOR LEVEL

2.000
2.000

CEILING LINE

0.300
3.000
12
B

4.300

3.000
B
5

3.000
C
3.000

FINISH FLOOR LINE


6 C
2.000
7 NATURAL GROUND LINE
D

0.400
D

2.700
8
2.000

14.300
E

4.300
RIGHT SIDE ELEVATION
14.300

4.300

11

2.100
SCALE: 1:100 MTS

3
3.500

F F

1.200
9
G G
3 2 1

2.950
5.000
5.000

2.750

10
1

H H ROOF APEX LINE


2
1.000

I I

2.850
3.700 2.300 2.500
3.700 2.300 2.500

8.500 TOP OF THE BEAM


8.500
CEILING LINE

0.300
2.700
REF. GROUND CEILING PLAN REF. SECOND CEILING PLAN

9.550
SCALE: 1 : 100 SCALE: 1 : 100 SECOND FLOOR LEVEL

CEILING LINE

0.300
3.000
LEGEND: FINISH FLOOR LINE

NATURAL GROUND LINE

0.400
GROUND FLOOPR 6. GUEST BEDROOM SECOND FLOOR 18. COMMON TOILET
7. PANTRY AND BATH
1. ENTRY PORCH 8. STORAGE 13. HALLWAY 19. MASTER TOILET
2. GARAGE 9. STAIR 14. BALCONY AND BATH
3. LIVING ROOM 10. TOILET AND BATH 15. BOY'S BEDROOM REAR ELEVATION
4. DINING ROOM 11. LANAI 16. GIRLS BEDROOM
5. KITCHEN AREA 12. SERVICE AREA 17. MASTER BEDROOM SCALE: 1:100 MTS

PROPOSED PROJECT OWNER SHEET CONTENT: SHEET NUMBER

PTR NO. :
ARCHITECT-UAP
PROPOSED AS SHOWN
PRC NO:
TIN:
2- STOREY RESIDENTIAL DESIGNED BY: DRAWN BY: APPROVED BY:
0.800 0.900
0.300 1.200 0.300

0.700 0.600

0.050

0.050

0.050
0.800

0.400
0.400
F F F F 1 2 3
F
ROOF APEX LINE
F F F
2.100

2.100

2.100

2.100

2.100
F

2.850
FLOOR F TOP OF THE BEAM
FINISH LVL.
CEILING LINE HALLWAY

0.300
D D D D D

2.700
1 2 3 4 5

9.550
BOYS BEDROOM

QUANTITY 1 1 4 1 5 SECOND FLOOR LEVEL

LOCATION MAIN ENTRANCE LANAI BEDROOMS KITCHEN PANTRY; STORAGE; T&B CEILING LINE ENTRANCE

0.300
STAIR

SINGLE DOOR, 50 MM THK SOLID SINGLE DOOR, 50 MM THK SOLID

3.000
TYPE DOUBLE DOOR, 50 MM THK SOLID SLIDING; ALUMINUM FRAME FULL GLASS SINGLE DOOR, 50 MM THK SOLID T&B
LANAI
HARDWOOD PANEL W/ FIXED PANEL HARDWOOD PANEL HARDWOOD PANEL HARDWOOD PANEL
DOOR W/ FIXED PANEL

50 mm x 100 mm THK. HARDWOOD 60 X 100 MM THK ALUMINUM FRAME 50 mm x 100 mm THK. HARDWOOD 50 mm x 100 mm THK. HARDWOOD 50 mm x 100 mm THK. HARDWOOD FINISH FLOOR LINE
FRAME
TIMBER DOOR FRAME DOOR TIMBER DOOR FRAME TIMBER DOOR FRAME TIMBER DOOR FRAME
NATURAL GROUND LINE

0.400
GLASS 6MM THK LAMINATED GLASS 6MM THK LAMINATED GLASS
NONE NONE NONE

STAINLESS STEEL LEVER STYLE DOOR LATCH STAINLESS STEEL LEVER STYLE DOOR LATCH
HARDWARE 12" PULL DOOR HANDLE STAINLESS STEEL LEVER STYLE DOOR LATCH STAINLESS STEEL LEVER STYLE DOOR LATCH
WITH UNIQUE LOCK AND KEY. WITH UNIQUE LOCK AND KEY.
WITH UNIQUE LOCK AND KEY. WITH UNIQUE LOCK AND KEY.
CROSS SECTION
0.400 SCALE: 1:100 MTS

0.150

0.950

H G F E D C B A

3.600
1.500
1.950
2.000 1.950

0.600 ROOF APEX LINE


2.000
0.600
1.500

2.850
0.600

2.200

2.100
2.500

1.800

TOP OF THE BEAM


1.500

0.300
1.200

0.300
0.900

FLOOR CEILING LINE

0.300
FINISH LVL.

2.700
MASTER BEDROOM

9.550
W W W W W W W
1 2 3 4 5 6 7 GIRLS BEDROOM
SECOND FLOOR LEVEL

QUANTITY 2 5 1 4 2 1 1 CEILING LINE LIVING ROOM


KITCHEN

0.300
LIVING ROOM BEDROOMS KITCHEN PANTRY; STORAGE; T&B STAIR 2ND FLOOR HALLWAY 2ND FLOOR HALLWAY
LOCATION

3.000
AWNING, ALUMINUM SLIDING, ALUMINUM AWNING, ALUMINUM AWNING, ALUMINUM FIXED, ALUMINUM FRAME AWNING, ALUMINUM FIXED, ALUMINUM FRAME PANTRY
TYPE STORAGE
FRAME WINDOW WITH FRAME WINDOW FRAME WINDOW FRAME WINDOW WINDOW FRAME WINDOW WINDOW
FIXED PANEL FINISH FLOOR LINE

POWDER COATED POWDER COATED POWDER COATED POWDER COATED POWDER COATED POWDER COATED POWDER COATED
FRAME FINISHED ALUMINUM FINISHED ALUMINUM NATURAL GROUND LINE
FINISHED ALUMINUM FINISHED ALUMINUM FINISHED ALUMINUM FINISHED ALUMINUM

0.400
FINISHED ALUMINUM
FRAME WINDOW FRAME WINDOW FRAME WINDOW FRAME WINDOW FRAME WINDOW FRAME WINDOW FRAME WINDOW

SINGLE GLAZED CLEAR. GLASS SINGLE GLAZED CLEAR.


GLASS SINGLE GLAZED CLEAR. GLASS SINGLE GLAZED CLEAR. GLASS SINGLE GLAZED CLEAR. SINGLE GLAZED CLEAR. GLASS SINGLE GLAZED CLEAR. GLASS
THICKNESS TO AS 6 MM GLASS THICKNESS TO AS 6
THICKNESS TO AS 6 MM THICKNESS TO AS 6 MM GLASS THICKNESS TO AS 6 THICKNESS TO AS 6 MM THICKNESS TO AS 6 MM
MM
MM
LONGITUDINAL SECTION
HARDWARE MANU. STANDARD SASH LOCK MANU. STANDARD SASH LOCK MANU. STANDARD SASH LOCK MANU. STANDARD SASH LOCK NONE MANU. STANDARD SASH LOCK NONE SCALE: 1:100 MTS

PROPOSED PROJECT OWNER SHEET CONTENT: SHEET NUMBER

PTR NO. :
ARCHITECT-UAP PROPOSED AS SHOWN
PRC NO:
TIN:
2- STOREY RESIDENTIAL DESIGNED BY: DRAWN BY: APPROVED BY:
COLUMN DETAIL
1 2 NOT DRAWN TO SCALE
3

4.700 3.550
L L
100 MM THK CONCRETE
SLAB WITH 10 MMø
REBARS SPACED @

A
C1F1
WF C1F1
500 MM BOTHWAYS TYPICAL FOOTING PLAN DETAIL

W
NOT DRAWN TO SCALE
C2F2
3.350

WF
B WF WF

WF

C1F1

2.800
C C1F1 WF
WF

D
3.350

WF WF C1F1
WF
WF
NATURAL GRADE LINE
WF
C1F1 4" thick CONCRE HOLLOW BLOCKS
E C1F1

4.250
WF
GB

10 MM ø VERTICAL BARS
3.450

DEPTH(D)
WF Natural Grade Line
SPACED @ 400 MM ON
F WF
GB
C1F1 CENTER WITH 10 MM ø
C1F1 C1F1 HORIZONTAL BAR IN EVERY
G C1F1
THIRD LAYER OF
CONCRETE HOLLOBLOCK

0.60
WF WF
2.750

5.000
WF WF
GB
WF
GB
H 3-12 MMø STRAIGHT BARS WITH
12 MM ø CROSS BAR SPACED AT
C1F1 WF C1F1
0.20 m 300 MM ON CENTER

I C2F2

THICKNESS(T)
GB C2F2

2.250 2.550 3.450


0.40 m
FOOTING LENGTH

FOUNDATION PLAN COLUMN FOOTING DETAIL SECTION WALL FOOTING


SCALE: 1:100 MTS
NOT DRAWN TO SCALE
S DETAIL SECTION
5 SCALE: 1:30

FOOTING DETAILS
DESCRIPTION DEPTH(D) LENGTH(L) WIDTH(W) THICKNESS(T) SIZE OF DSB NO. OF DSB ALONG LENGTH NO. OF RSB ALONG WIDTH
F1(13PCS) 2.00 MTR 1.500 MTR 1.500 MTR 0.30 MTR 16 MM ø 10 PCS (150 MM SPACEING) 10 PCS (150 MM SPACEING)
F2(3PCS) 1.00 MTR 1.00 MTR 1.00 MTR 0.30 MTR 12 MM ø 7 PCS (141 MM SPACING) 7 PCS (141 MM SPACING)

COLUMN DETAILS
DESCRIPTION LENGTH(L) WIDTH(W) CLEAR COV. SIZE AND NO. OF DSB TO USED LATERAL TIES SIZE AND SPACING
C1(13PCS) 0.35 MTR 0.25 MTR 0.04 MTR 6 PCS - 16MM ø SINGLE 10 MM ø DSB SPACED AT 4
C2(3PCS)
PCS @ 50 MM. 4PCS @ 100 MM,4PCS
0.04 MTR 4 PCS - 12 MM ø
@ 150 MM AND REST @ 200 MM 0.C,

PROPOSED PROJECT OWNER SHEET CONTENT: SHEET NUMBER

PTR NO. :
ARCHITECT-UAP
PROPOSED AS SHOWN
PRC NO:
TIN:
2- STOREY RESIDENTIAL DESIGNED BY: DRAWN BY: APPROVED BY:
1 2 3
1 2 3

4.700 3.550

4.700 3.550

A ROOF BEAM 3

ROOF BEAM 5

ROOF BEAM 5
2B4

3.350
3.350
S2 ROOF BEAM
B 2B5
2B5
C

ROOF BEAM
ROOF BEAM 3

2.800
C

ROOF BEAM 5
ROOF BEAM 5
2B4
D

3.350
ROOF BEAM 6
D
3.350

2B6

ROOF BEAM 7
2B5 S2 2B5

4.250
ROOF BEAM 3
E

ROOF BEAM 4
ROOF BEAM 4
4.250
2B7
2B4 S3

3.450
F
3.450

2B3 2B3
ROOF BEAM 6
S1
F ROOF BEAM 8
2B6
G ROOF BEAM 1

ROOF BEAM 2

ROOF BEAM 2
G 2B10

2.750
2B1

5.000
2.750

2B2 2B2
STAIR 2B9 S4
WELL
2B8
H
ROOF BEAM 1
H
2B1

I 2B6
2.250 2.550 3.450

2.250 2.550 3.450

ROOF BEAM PLAN


SECOND FLOOR FRAMING PLAN SCALE: 1 : 100
SCALE: 1 : 100

PROPOSED PROJECT OWNER SHEET CONTENT: SHEET NUMBER

PTR NO. :
ARCHITECT-UAP PROPOSED AS SHOWN
PRC NO: 2- STOREY RESIDENTIAL DESIGNED BY: DRAWN BY: APPROVED BY:
TIN:
SCHEDULE OF SLAB
SLAB NO. SIZE(mm) THICKNESS (mm) TOP RBARS BOTTOM REBARS
S1 3.45 X 4.70 100 SHORT SPAN 12 mm ø @ 300 mm ON CENTER 12 mm ø @ 300 mm ON CENTER
LONG SPAN 12 mm ø @ 250 mm ON CENTER 12 mm ø @ 300 mm ON CENTER
S2 3.50 X 4.70 100 SHORT SPAN 12 mm ø @ 300 mm ON CENTER 12 mm ø @ 300 mm ON CENTER
LONG SPAN (L)
LONG SPAN 12 mm ø @ 250 mm ON CENTER 12 mm ø @ 300 mm ON CENTER
S3 4.25 X 3.55 100 SHORT SPAN 12 mm ø @ 300 mm ON CENTER 12 mm ø @ 300 mm ON CENTER
L/4 L/2 L/4
LONG SPAN 12 mm ø @ 250 mm ON CENTER 12 mm ø @ 300 mm ON CENTER
S4 5.00 X 3.45 100 SHORT SPAN 12 mm ø @ 300 mm ON CENTER 12 mm ø @ 300 mm ON CENTER
LONG SPAN 12 mm ø @ 200 mm ON CENTER 12 mm ø @ 300 mm ON CENTER
S/4

TOP REBARS TOP REBARS


SHORT SPAN (S)

S/2

BOTTOM REBARS
S/4

Span (L)
LEFT END RIGHT END

TOP REBARS 0.10 m

D
BOTTOM REBARS B
L/4 L/2 L/4 SEE SCHEDULE

TYPICAL BEAM SECTION DETAIL


TYPICALSLAB DETAIL NOT DRAWN TO SCALE

SCHEDULE BEAM
SIZE (mm) REINFORCEMENTS
BEAM NO. LOCATION STIRRUPS ( 10 mmø)
B D LEFT END MID SPAN RIGHT END
2nd FLOOR BEAM 25 35 TOP 4 - 16 mm ø 3 - 16 mm ø 4 - 16 mm ø 1 @ 50mm, 5 @ 100 mm, 4 @ 150 mm, REST @ 20 mm
BOTTOM 4 - 16 mm ø 4 - 16 mm ø 4 - 16 mm ø
TYPICAL ROOF BEAM 25 35 TOP 4 - 16 mm ø 3 - 16 mm ø 4 - 16 mm ø 1 @ 50mm, 5 @ 100 mm, 4 @ 150 mm, REST @ 20 mm
BOTTOM 4 - 16 mm ø 4 - 16 mm ø 4 - 16 mm ø

PROPOSED PROJECT OWNER SHEET CONTENT: SHEET NUMBER

PTR NO. :
ARCHITECT-UAP
PROPOSED AS SHOWN
PRC NO:
TIN:
2- STOREY RESIDENTIAL DESIGNED BY: DRAWN BY: APPROVED BY:
0.600

0.600

0.600

0.600

0.600

0.600

0.600

0.800

2.55
1 2 3 1 2 3

6.27
4.700 3.550 4.700 3.550

TRUSS -1
TRUSS-1 DIAGRAM
A ROOF BEAM 3
A
ROOF BEAM 5

ROOF BEAM 5
TRUSS -3
3.350

3.350
B TRUSS -1
B
TRUSS -3 0.600

0.600

2.800
C ROOF BEAM 3 TRUSS -3 C 0.600

0.600
ROOF BEAM 5
ROOF BEAM 5

D D 0.600
3.350

3.350
0.600
ROOF BEAM 6
TRUSS -1
0.900

1.300
ROOF BEAM 7
TRUSS -2
E E

4.250

4.250
ROOF BEAM 3
TRUSS -2
ROOF BEAM 4

ROOF BEAM 4

5.300
3.450

3.450
TRUSS -1
TRUSS -2

F F
ROOF BEAM 6
TRUSS-2 DIAGRAM
ROOF BEAM 8
G ROOF BEAM 1
G
ROOF BEAM 2

ROOF BEAM 2
2.750

2.750
TRUSS -4
0.600

H H 0.600
ROOF BEAM 1
0.600

0.600

0.600

2.250 2.550 3.450 2.250 2.550 3.450

1.100
3.800

ROOF FRAMING PLAN ROOF PLAN TRUSS-3 DIAGRAM


SCALE: 1 : 100 SCALE: 1 : 100

4.100

0.200
TRUSS-4 DIAGRAM

PROPOSED PROJECT OWNER SHEET CONTENT: SHEET NUMBER

PTR NO. :
ARCHITECT-UAP PROPOSED AS SHOWN
PRC NO: 2- STOREY RESIDENTIAL DESIGNED BY: DRAWN BY: APPROVED BY:
TIN:
1 2 3 1 2 3

LEGEND:
5.000 3.500 5.000 3.500

A
A

4" ø SOIL PIPE

2.000
KS 12

2.000
GROUND FLOOPR 6. GUEST BEDROOM

3.000
5
B 7. PANTRY B

4.300
LAV
4" øPVC RISER 6 1. ENTRY PORCH 8. STORAGE 4" øPVC RISER 19
17

3.000
WC
C 2. GARAGE 9. STAIR

3.000
7
C

2.000
CO FD

3. LIVING ROOM 10. TOILET AND BATH


D 4" ø SOIL PIPE
CO
4. DINING ROOM 11. LANAI D LAV
8
2.000

2.700
16 FD
5. KITCHEN AREA 12. SERVICE AREA WC
DIGESTIVE
CHAMBER

4 18
E 11

14.300
4.300
E

14.300
LEACHING
CHAMBER

4" øPVC RISER 15


3

2.100
4" øPVC RISER
4" ø SOIL PIPE
3.500

F
F

1.200
9

1.200
13
G
G 14

2.000
SECOND FLOOR 18. COMMON TOILET

5.000
2.750

LAV 1

2.950

5.000
FD
10
CO 2 AND BATH
H WC
13. HALLWAY 19. MASTER TOILET H
1.000

I 14. BALCONY AND BATH


I
15. BOY'S BEDROOM
GROUND FLOOR SEWERLINE LAY OUT 16. GIRLS BEDROOM
17. MASTER BEDROOM SECOND FLOOR SEWERLINE LAY OUT
SCALE: 1 : 100 SCALE: 1 : 100

1 2 3 1 2 3
5.000 3.500 5.000 3.500

1/2" ø CWL

A
1/2" ø CWL

A
2.000

FAU. 12

2.000
3.000

1/2" ø CWL

FAU.1/2" ø CWL
5
B
B

4.300
LAV

6 19
1/2" ø CWL

17
3.000

WC
C

3.000
7
C FAU.
2.000

SHO.

D
D
FAU. SHO.
2.000

2.700
16 LAV
WC
4 18
RISER
E 11 RISER
14.300
4.300

14.300
RISER RISER
15
3
LEGEND:

2.100
3.500

F
WC WATER CLOSET F
1.200

9
1/2" ø CWL

1.200
13
G LAV LAVATORY G 14
KS KITCHEN SINK
2.000

5.000
2.750

LAV 1
FD FLOOR DRAIN

2.950

5.000
10 SHO.

H WC FAU. 1/2" ø CWL


2 DS DOWNSPOUT
WM FROM FAU FAUCET H
1.000

1/2" ø CWL WATER


I MAIN
SOIL PIPE LINE
SOURCE
I
WATER LINE
M WATER METER
GROUND FLOOR WATERLINR LAY OUT SECOND FLOOR WATERLINE LAY OUT
SCALE: 1 : 100 SCALE: 1 : 100

PROPOSED PROJECT OWNER SHEET CONTENT: SHEET NUMBER

PROPOSED
PTR NO. :
ARCHITECT-UAP
2- STOREY RESIDENTIAL
AS SHOWN
PRC NO:
DESIGNED BY: DRAWN BY: APPROVED BY:
TIN:
SEPTIC VAULT DETAILS
GENERAL PLUMBING NOTES
SCALE: 1:35 ALL PLUMBING WORKS INCLUDED HEREIN SHALL BE EXECUTED ACOORDING TO
NO. OF DEPTH "D" WIDTH "H" LENGTH "L" THE PROVISION OF THE NATIONAL PLUMBING CODE OF THE PHILIPPINES AND
PERSONS LOCAL RULES AND REGULATIONS
METERS METERS METERS A. VERTICAL PIPING
2.30 m 10 PERSONS 1.20 0.90 1.80
1. PLASTIC PIPE - SHALL BE SUPPORTED AT EVERY - (1) METER INTERVAL.

B. HORONTAL PIPING

0.10 m 0.10 m 0.10 m 15 PERSONS 1.20 1.10 2.20 1. PLASTIC PIPE - SHALL BE MANUFACTURED BY STIFF METAL BACKING
HANGERS IN ITS ENTIRE LENGTH FOR SMALL SIZE TUBING UP TO 38mm
20 PERSONS 1.20 1.25 2.50 DIAMETER AND WITHOUT BACKINGS BUT WITH SPACED METAL HANGERS
1.20 m 0.80 m 25 PERSONS 1.20 1.40 2.50
AT APPROVED FOR LARGER-SIZED TUBING.

C. PLUMBING FIXTURES
1. PLUMBING FIXTURES SHALL BE MANUFACTURED OF DENSE, DURABLE,

0.10 m
30 PERSONS 1.30 1.50 3.00 NIN-BORBENT MATERIALS AND HAVE SMOOTH, IMPERVIOUS SURFACES,
FREE FROM UNNCESSARY CONCEALED FOULING SURFACES, EXCEPT AS
35 PERSONS 1.30 1.60 3.20 PERMITTED ELSEWHERE IN THIS CODE, ALL FIXTURE SHALL CONFORM IN
QUALITY AND NATIONALLITY RECOGNIZED APPLICABLE STANDARDS.
40 PERSONS 1.40 1.65 3.30
WATER SUPPLY
45 PERSONS 1.40 1.75 1. EACH PLUMBING FIXTURE SHALL BE PROVIDED WITH AN ADEQUATE
3.50 SUPPLY OF POTABLE RUNNING WATER , SO ARRANGED AS TO FLUSH AND
KEEP SAME IN CLEAN AND HEALTHFUL CONDITIONS WITHOUT DANGER OF
50 PERSONS 1.20 1.75 3.50 BACKFLOW OR CROSS-CONNECTION.

60 PERSONS 1.20 1.95 3.90 D. SEWERLINE

1.10 m

1.30 m
C.O. MANHOLE MANHOLE C.O. 1. DRAINAGE PIPING SHALL BE PROVIDED WITH APPROVED INLET FITTINGS
FOR FIXTURE CONNECTIONS, CORRECTLY LOCATED ACCORDING TO THE

INSIDE DIMENSION OF DIGESTIVE CHAMBER


SIZE AND TYPE OF FIXTURE PROPOSED TO BE CONNECTED.
2. CHANGE IN DIRECTION OF DRAINAGE PIPING SHALL BE MADE BY THE
400mm x 400mm 400mm x 400mm APPROPRIATE USE OF APPROVED FITTINGS AND SHALL BE OF THE
INLET PIPE ANGLES PRESENTED BY A 22 21 DEGRESS OR 181
BEND, 45 DEGRESS OR 81
BEND AND 60 DEGREES OR 81 BEND OR OTHER APPROVED FITTINGS.

E. INDIRECT WASTE
1. NO EVAPORATIVE COOLER OR SIMILAR AIR AIR CONDITIONING EQUIPMENT
SHALL HAVE ANY DRAIN PIPE IN CONNECTION THEREWITH, DIRECTLY
CONNECTED TO ANY SOIL, WASTE AND VENT PIPE SUCH EQUIPMENT
SHALL BE DRAINED BE MEANS OF INDIRECT WASTE PIPES AND ALL
0.10 m WASTES DRAINED BY THEM SHALL DISCHARGE THROUGH AN AIRBREAK
INTO AN OPEN FLOOR SINK OR OTHER APPROVED TYPE RECEPTOR
PROPERLY CONNECTED TO THE DRAINNAGE SYSTEM.

PLAN F.
1.
VENT PIPES
EACH PLUMBING FIXTURES TRAP, EXCEPT AS OTHERWISE PROVIDED IN
THIS CODE, SHALL BE PROTECTED AGAINST SIPHONAGE AND
BACK-PRESSURE, AIR CIRCULATION SHALL BE ASSURED THROUGHOUT
ALL PARTS OF THE EXCRETA DRAINAGE SYSTEM BY MEANS OF VENT PIPES
2. ALL VENT PIPES SHALL EXTEND UNDIMINISHED IN SIZE ABOVE THE ROOF
C.O. C.O. SHALL BE RECONECTED WITH THE SOIL OR WASTE STACK VENT OF
400mm x 400mm 400mm x 400mm PROPER SIZE AT A POINT BELOW THE ROOF, THE VENT THROUGH THE
ROOF (VSTR) SHALL INCREASE ONE PIPE SIZE ABOVE.

0.10 m G.
1.
STORM DRAINAGE
STORM DRAINAGE SHALL BE PROVIDED FOR ROOF AREAS, COURTS AND
COURTYARDS TO COLLECT STORM WATER AND DISCHARGE THE
AIR SPACE STORMWATER TO AN APPROVED POINT OF DISPOSAL NOT IN CONFLICT
INLET PIPE
OUTLET PIPE PLUMBING LEGENDS H.
WITH OTHER ORDINANCES OR REGULATIONS.

HANGERS NAD SUPPORT


1. PIPES SHALL BE SUPPORTED AT SUFFICIENTLY CLOSE INTERVALS TO
KEED THEM IN ALIGNMENT AND PREVENT SAGGING.
SD SHOWER DRAIN LS LAUNDY SINK
CB CATCH BASIN LAV LAVATORY MATERIAL SPECIFICATIONS
CV CHECK VALVE MV MIXING VALVE
1.50 m

COLD WATERLINE SHALL BE POLYPROPYLENE RANDOM


CWL COLD WATER LINE MVSTR MAIN VENT STACK THRU ROOF CO-POLYMER TYPE 3
DIGESTIVE CHAMBER LEACHING CWR COLD WATER RISER NRCP NON-REINFORCED CONCRETE PIPE SEWER LINE SHALL BE UNPLASTICIZED POLYVINYL
CO CLEAN OUT PVC POLYVINYL CHLORIDE CHLORIDE (UPVC SERIES)

CHAMBER DP
DSP
DRAIN PIPE
DOWNSPOUT
RD
SHO
ROOF DRAIN VENT PIPES
DOWNSPOUTS
SHOWER STORM DRAINAGE
FD FLOOR DRAIN SD SHOWER DRAIN
100 mm thk CHB spaced every 3rd Layer LABORATORY/ SHALL BE HIGH DENSITY POLYETHYLENE
with 10 mm REBARS @ 600 mm OC
FHC FIRE HOSE CABINET SP SOIL PIPE (HDPE PB16)

Bothways FWL FIRE WATER LINE SS SOIL STACK


FWR FIRE WATER RISER SLS SLOP SOIL
FV FLOATVALVE ST SEPTIC TANK
GI GALVANIZED IRON TP TRANSPER PUMP
GV GATE VALVE VPAC VENT PIPE ABOVE CEILING
0.20 m HB HOSE BIBB WS WASTE STACK
HWL HOT WATER LINE WP WASTE PIPE
HWR HOT WATER RISER VSTR VENT STACK THRU ROOF
KS KITCHEN SINK WM WATER METER
SECTION
0.10 m 1.20 m 0.80 m

0.10 m 0.10 m
2.30 m

PROPOSED PROJECT OWNER SHEET CONTENT: SHEET NUMBER

PTR NO. :
ARCHITECT-UAP
PROPOSED AS SHOWN
PRC NO:
TIN:
2- STOREY RESIDENTIAL DESIGNED BY: DRAWN BY: APPROVED BY:
1 2 3 1 2 3
A
5.000 3.500
CONVE. OUTLET 5.000 3.500

A 10
REF
A

2.000

2.000
15

3.000
PB

WP

B B

4.300
ACU

14
11 18
RAN

3.000
C

3.000
C

2.000
D D

2.700
ACU

2.000
17

E E

14.300
4.300

14.300
4.300
13 ACU

2.100
16

3.500
F F

1.200
12

1.200
G G

2.000

5.000

2.950
2.750

5.000
H H

1.000
I I
2.500 2.300 3.700 2.500 2.300 3.700

8.500 8.500

3 2 1
3 2 1 ELECTRICAL LAYOUT
SCALE: 3.500 5.000
1:100 MTS
3.500 5.000

A
A

2.000
4
2.000

3.000

4.300
PB S1
S1
5 S3

S1

3.000
3 C
3.000

8
2
C S3

2.000
S1

D
D

2.700
S1 S1

S2
1
2.000

S1
9
E
S1

14.300

4.300
S3

E
14.300

4.300

S3

2.100
S2

6
7

F
3.500

1.200
S2

F S3

G
S3

S2
S1

5.000

2.950
S1

S2
5.000

2.750

H
H
I
1.000

I
3.700 2.300 2.500

3.700 2.300 2.500


LIGHTING (REFLECTED) 8.500

PROPOSED PROJECT OWNER SHEET CONTENT: SHEET NUMBER

PTR NO. :
ARCHITECT-UAP
PROPOSED AS SHOWN
PRC NO:
TIN:
2- STOREY RESIDENTIAL DESIGNED BY: DRAWN BY: APPROVED BY:
LEGENDS

KILOWATT HOUR METER


M S1 ONE GANG SWITCH

PANELBOARD S2 TWO GANG SWITCH

S3 THREE GANG SWITCH


CIRCUIT BREAKER
SERVICE ENTRANCE
CONVE. OUTLET
HOMERUN CIRCUIT NO.
M
CONDUIT CONCEALED OVER CEILING
WP
WEATHER PROOF OUTLET

CONDUIT CONCEALED UNDER FLOORING RAN RANGE OUTLET

SCHEDULE OF LOADS AND COMPUTATION PANELBOARD

ACU
AIR CONDITION UNIT OUTLET
CKT. BREAKER SWITCH LINE
CKT.
DESCRIPTION QTY. VA VOLT AMP. SIZE OF WIRE AND CONDUIT
NO.
AT AF NO. POLE 20 A 20 A
PIN LIGHT

1 1x5W LED PINLIGHT; 1x21W LED FLUORESCENT 10+2 92 230 0.400 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT 1 2
20 A 20 A
2 1x5W LED PINLIGHT; 1X5W LED WALL LAMP 12+4 80 230 0.350 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT
3 4
3 1x5W LED PINLIGHT; 1x50W LED CHANDELIER 10+1 100 230 0.430 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT
20 A 20 A
4 1x5W LED PINLIGHT; 1x21W LED FLUORESCENT 6+4 114 230 0.500 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT
5 6
5 1x5W LED PINLIGHT; 1x21W LED FLUORESCENT:1X5W 4+1+2 51 230 0.200 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT 20 A 20 A
LED WALL LAMP
7 8
6 1x5W LED PINLIGHT; 1x21W LED FLUORESCENT;1x50W 8 + 3 +1 153 230 0.670 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT
LED CHANDELIER
20 A 20 A

7 1x5W LED PINLIGHT; 1x21W LED FLUORESCENT 11+1 76 230 0.330 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT 9 10
8 1x5W LED PINLIGHT; 1x21W LED FLUORESCENT 8+1 61 230 0.270 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT CELING FLOOR LINE 20 A 20 A

9 1x5W LED PINLIGHT; 1x21W LED FLUORESCENT 4+1 41 230 0.180 20 50 2 2-5.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT
C3 C4
11 12
TO POWER SOURCE
10 CONVE. OUTLET(180) 5 900 230 3.910 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT 20 A 50 A

11 CONVE. OUTLET(180) 5 900 230 3.910 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT C7 C8 C11 C12
13 14
12 CONVE. OUTLET(180) 20 A 20 A
3 540 230 2.330 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT
SECOND FLOOR LINE

13 CONVE. OUTLET(180) 6 1080 230 4.700 20 50


2-Ga. No. 6 THW Copper

C1 C2
15 16
2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT
20 A 20 A
14 RANGE 1 8000 230 34.78 50 50 2 2-5.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT
17 18
15 REFRIGERATOR 1 1518 230 6.60 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT C5 C6 C9 C10
SPARE SPARE
16 ACU. OUTLET (1.5) 1 1492 230 6.49 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT
GROUND FLOOR LINE 19 20
17 ACU. OUTLET (1.5) 1 1492 230 6.49 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT

18 ACU. OUTLET (1.5) 1 1492 230 6.49 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT
SINGLE LINE RISER DIAGRAM
19 1500 230 6.52 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT

20 1500 230 6.52 20 50 2 2-3.5 sq.mm THHN WIRE ON 15 MM ø PVC CONDUIT


PANEL BOARD
TOTAL 93.070

D.F. (DEMAND FACTOR) 80 % GENERAL ELECTRICAL NOTES


1. ALL ELECTRICAL WORKS HEREIN SHALL BE EXECUTED IN ACCORDANCE 9. FOR EVERY SPARE BRANCH CIRCUIT IN THE PANELBOARD PROVIDE ONE 20mm
I = (93.07 x 0.80) + (6.49 x 0.25) WITH THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE THE
NEW ELECTRICAL ENGINEERING LAW (R.A. 7920). LAWS AND ORDINANCES
uPVC WITH ITS RATED AMPACITY. # 16 G.I. PULLWIRE CONNECTED TO JUNCTI0N
BOX W/ COVER AT THE CONCRETE SLAB.
= 76.08 AMPERES OF THE LOCAL GOVERNMENT UNIT AND LAWS AND REGULATIONS OF THE
LOCAL ELECTRICAL POWER UNIT COMPANY.
10. BOXES SHALL BE PRESSED STEEL WITH REQUIRED THICKNESS IN CONFORMNCE
WITH THE LATEST EDITION OF THGE PHILIPPINE ELECTRICAL CODE
2. ALL WIRINGS SHALL BE IN RIGID STEEL CONDUIT (R.S.C.) FOR EXPOSE MAIN
SERVICE LINES AND UNPLASTICIZED POLYVINYL CHLORIDE.RIGID ( uPVC) 11. MOUNTING HEIGHT OF THE PANEL AND DEVICES ARE AS FOLLOWS:
FOR BURIED UNDERGROUND CONDUIT MAIN SERVICE LINE. FLEXIBLE ( FROM FLOOR FINISH TO CENTER OF THE UNIT)
USE 100 AF 2P 100 AT 220V POLYVINYL CHLORIDE ( P.V.C.) WITH ACCEPTABLE DURABILITY FOR LOAD
LINES. A. WALL SWITCHES 1400 mm
B. WALL CONVENIENCE OUTLETS 300 mm
3. PANEL BOARDS AND OVERCURRENT PROTECTION ENCLOSURES SHALL BE
C. WALL AIR CONDITIONING UNIT 900 mm
NEMA - 1 FOR INDOOR USE AND NEME - 3 FOR OUTDOOR USE UNLESS
D. COUNTER TOP OUTLET 1200 mm
OTHERWISE SPECIFIED.
E. KWHr. METER 1650 mm
4. POWER SERVICE SHALL BE 230 V, 60 HZ., 3 WIRE, SINGLE PHASE F. PANELBOARD 1350 mm
5. ALL WIRING INSTALLTION SHALL BE CONCEALED FROM VIEW.
12. CONDUIT/RACEWYAYS SHALL BE ADEQUATELY SUPPORT AS REQUIRED INTHE
6. UNLESS OTHERWISE INCATED BRANCH CIRCUIT CONDUCTORS SHALL
COMFORMANCE WITH TEH LASTEST EDITION OF THE PHILIPPINE ELECTRICAL CODE.
NOT BE SMALLER THAN 1.6mm DIAMETER, SOLID COOPER, MEDIUM
13. DISTRIBUTION PANEL SHALL BE READILY ACCESSIBLE THAT NO OBSTACLE SHOULD BLOCK
DRAWN, TW TYPE, 600 V INSTALLATION
ACCESS TO THE PANEL .
7. MINIMUM SIZE OF OF CONDUIT SHALL BE 20mm FOR RIGID CONDUIT
14. THE INSTALLATION SAHLL BE DIRECTLY SUPERVISED BY DULY LICENCSED ELECRTRICAL
(R.S.V.) AND 20mm FOR UNPLASTICIZED POLYVINYL CHLORIDE, FLEXIBLE
PRACTITIONER IN COMFORMANCE WIHT R.A. 7920
OR RIGID (uPVC). ALL FLEXIBLE POLYVINYL CHLORIDE CONDUIT
INSTALLED IN SLABS OR CHB SHOULD BE.
8. NO BRANCH CIRCUIT CONDUCTORS SHALL BE LOADED 80% OF ITS RATED
CAPACITY

PROPOSED PROJECT OWNER SHEET CONTENT: SHEET NUMBER

PTR NO. :
ARCHITECT-UAP
PROPOSED AS SHOWN
PRC NO:
TIN:
2- STOREY RESIDENTIAL DESIGNED BY: DRAWN BY: APPROVED BY: