You are on page 1of 2

Thermostats of stainless steel 3.4.

05-E
types V4.03 and V4.05 GB-1

The adjusting cylinder has O‑ring sealings


Characteristics
and is sealed with silicone glue at the top
• Self-acting for hermetical closure. The thermostat is
• P-controller available with settings between -30ºC
• Completely sealed and +280ºC.
• Excess temperature protection At flow temperatures above 170ºC, a
• All parts made of stainless steel cooling unit must be installed between
• Non-magnetic the valve and the thermostat. Please
see datasheet no. 8.5.00.

Application
The thermostat is particularly suitable for Neutral Zone
installation in demanding environments The neutral zone of the thermostat,
such as tank installations, outdoor plants which is less than 2ºC, is the temperature
and where it must be non-magnetic, e.g. difference which can accur at the sensor
in submarines. without the thermostat spindle being
actuated.

Function
The adjusting cylinder of the thermostat Sensor types
is set at the temperature in ºC for the Rod or spiral sensors of stainless steel
required heated medium. The temperature with pipe thread.
is regulated by the thermostatically Sensors are also available with a pack-
controlled valve reducing or increasing box on the capillary tube for applications Technical data
the flow of the heating medium. Together where the sensor is to be lowered into a
with the adjusting cylinder, the liquid-filled Max. closing force 500 N
tank etc.
sensor and capillary tube constitute a Standard settings:
closed system. -Type V4.03 0-160 ºC
If the temperature of the medium to be -Type V4.05 0-120, 40-160 ºC
heated is above the required level, the
Sensor liquid Reinforcement (mm/ºC):
sensor liquid expands, causing the spindle Glycerine at a scale range between - 30ºC (Glycerine) Type V4.03: 0.3
of the thermostat to act upon the valve, and 160ºC. Type V4.05: 0.5
thereby reducing the flow of the heating Paraffin at a scale range between 140ºC (Paraffin) Type V4.03: 0.33
medium. and 280ºC. Type V4.05: 0.7
If the temperature is below the required For valves with
level, the temperature of the liquid lifting height up to 21 mm
in the sensor decreases and the Capillary tube Sensor material W. No. 1.4436
volume is reduced, thereby the valve Time constant for rod sensor:
The capillary tube is made of stainless
spring opens the valve causing an - Type V4.03: 90 sec.
steel and is available in lengths from 3 m
increasing flow of the heating medium. - Type V4.05: 100 sec.
up to 21 m.
Time constant for spiral sensor, sec. 20
Neutral zone < 2ºC
Excess temperature protection 40ºC
Construction Valves
The parts of the thermostat are made of The thermostat may be used for valves
stainless steel. The thermostat consists up to DN 150 mm for heating and cooling
of a liquid-filled sensor, a capillary tube, plants.
and an adjusting cylinder. See data sheet "Quick choice of tem-
perature controller" no. 9.0.00 and data
sheet for the particular valve. Subject to change without notice.

Clorius Controls A/S


Tempovej 27 · DK-2750 Ballerup · Denmark
Tel.: +45 77 32 31 30 · Fax: +45 77 32 31 31
E-mail: mail@cloriuscontrols.com
Web: www.cloriuscontrols.com
Thermostats of stainless steel 3.4.05-E
types V4.03 and V4.05 GB-2

Sensors with pipe thread Type V4.03 Type V4.05

E F C 190 mm 380 mm
D 170 mm 250 mm
E 22 mm 22 mm
C

D
G H F 49 mm 49 mm
G* 1" 1"
H* 2" 2"

Weight including G connection 2.4 kg 2.6 kg


Weight including H connection 2.9 kg 3.1 kg

Sensors without connection


Type V4.03 Type V4.05
Available with capillary packbox

1) 2) E 22 mm 22 mm
E F
F 49 mm 49 mm
U 230 mm 410 mm
V 220 mm 310 mm
V
U

G* 1" 1"
H* 2" 2"

3) 4) 1) 2.2 kg 2.3 kg
2) 2.2 kg 2.4 kg
Weight

G H
3) 2.4 kg 2.6 kg
4) 2.9 kg 3.1 kg
* The measurements G and H are pipe threads according to ISO R7/1.

Measurements in mm
385 mm
525 mm
min.

Subject to change without notice.

Clorius Controls A/S


Tempovej 27 · DK-2750 Ballerup · Denmark
Tel.: +45 77 32 31 30 · Fax: +45 77 32 31 31
E-mail: mail@cloriuscontrols.com
Web: www.cloriuscontrols.com

You might also like