Annexure - A

ONGC SPD Technical Specification


SL No. Description
600V AC Type-1+2 In-Build fuse SPD for Power Line Surge
1
Protection for L-1, L-2, L-3 without Neutral
Type-1+2 SPD having Encapsulated Spark Gap Technology with In-
a Build Fuse inside. No External Fuse is allowed.
b IEC Test Classification: T1/T2
c Standard Regulations: IEC 61643-11 2011
d Mounting Type- DIN RAIL 35mm
e Flammability Rating: UL 94 V-0
f Nominal Voltage Un: 400/690 V AC(TN-C) / 400V AC (IT)
g Maximum Continous Operating Voltage Uc: 440V AC
h Nominal discharge Current In (8/20µs): 25kA
i Maximum discharge Current Imax (8/20µs): 50kA
j Impulse discharge Current Iimp (10/350µs): 25kA
k Voltage Protection Level: ≤2.5kV
Temporary Overvoltage behaviour at Ut
a) 580 V AC (5 s / withstand mode)
l
b) 760 V AC (120 min / withstand mode)
c) 1640 V AC (200 ms / safe failure mode)
m Response time: ≤ 100 ns
n Mandatory Approval/Certification: KEMA KEUR / UL

Three Phase AC SPD Type-1+2 for 415V Power Line Surge


2 Protection
a SPD Type-1+2, Metal Encapsulated Spark Gap based Technology
b SPD should be pluggable per Pole
c Maximum Continuous operating Voltage Uc: 350V AC
d Nominal Discharge Current In 8/20µs (L-N): 25kA and N-PE: 100kA
Lightning Impulse Discharge Current Iimp 10/350µs (L-N): 25kA and N-
e
PE: 100kA
f Voltage Protection Level: ≤ 1.5kV
Temporary Overvoltage Ut (L-N)
a) 415 V AC (5 s / withstand mode)
b) 440 V AC (120 min / withstand mode)
c) 485 V AC (10 h / withstand mode)
g
Ut (N-PE):-
1200 V AC (200 ms / withstand mode)

Visual Indication Per Pole(L-N & N-PE): Healthy: Green & Faulty: Red
h Colour
i Approval/Certification as per IEC 61643-11-2011: KEMA/UL

Single Phase AC SPD Type-1+2 for 230V Power Line Surge


3
Protection
a SPD Type-1+2, Metal Encapsulated Spark Gap based Technology
b SPD should be pluggable per Pole
c Maximum Continuous operating Voltage Uc: 350V AC
d Nominal Discharge Current In 8/20µs (L-N): 25kA and N-PE: 100kA
Lightning Impulse Discharge Current Iimp 10/350µs (L-N): 25kA and N-
e
PE: 100kA
f Voltage Protection Level: ≤ 1.5kV
Temporary Overvoltage Ut (L-N)
a) 415 V AC (5 s / withstand mode)
b) 440 V AC (120 min / withstand mode)
c) 485 V AC (10 h / withstand mode)
g
Ut (N-PE):-
1200 V AC (200 ms / withstand mode)

Visual Indication Per Pole(L-N & N-PE): Healthy: Green & Faulty: Red
h
Colour
i Approval/Certification as per IEC 61643-11-2011: KEMA/UL

4 Three Phase AC SPD Type-2 for 415V Power Line Surge Protection
a SPD Type-2, MOV Based
b SPD should be pluggable per Pole
c Maximum Continuous operating Voltage Uc: 350V AC
d Maximum Discharge Current In 8/20µs (L-N): 40kA
e Nominal Discharge Current In 8/20µs (L-N): 20kA
f Voltage Protection Level: ≤ 1.5kV
Temporary Overvoltage Ut (L-N)
a) 415 V AC (5 s / withstand mode)
b) 440 V AC (120 min / withstand mode)
c) 485 V AC (10 h / withstand mode)
g
Ut (N-PE):-
1200 V AC (200 ms / withstand mode)

Visual Indication Per Pole(L-N & N-PE): Healthy: Green & Faulty: Red
h Colour
i Approval/Certification as per IEC 61643-11-2011: KEMA/UL

Singal Phase AC SPD Type-2 for 230Vac Power Line Surge


5
Protection
a SPD Type-2, MOV Based
b SPD should be pluggable per Pole
c Maximum Continuous operating Voltage Uc: 350V AC
d Nominal Discharge Current In 8/20µs (L-N): 20kA
e Maximum Discharge Current In 8/20µs (L-N): 40kA
f Voltage Protection Level: ≤ 1.5kV
Temporary Overvoltage Ut (L-N)
a) 415 V AC (5 s / withstand mode)
b) 440 V AC (120 min / withstand mode)
c) 485 V AC (10 h / withstand mode)
g
Ut (N-PE):-
1200 V AC (200 ms / withstand mode)

Visual Indication Per Pole(L-N & N-PE): Healthy: Green & Faulty: Red
h
Colour
i Approval/Certification as per IEC 61643-11-2011: KEMA/UL

6 Profinet Communication Lines (PLC Control network)


Surge protection for data newtorks upto 1 Gbps, For use in Ethernet,
Power Over Ethernet. RJ45 attachment plug with separate grounding
cable
Degree of Protection IP20
Flammability rating according to UL94 V-0
IEC test Classification: -
B2
C2
D1
Maximum continuous voltage UC (wire-wire): ± 5 V DC (± 57 V DC /
PoE+)
Nominal discharge current In (8/20) µs (line-line): 350A
Nominal discharge current In (8/20) µs (line-earth): 2kA
Pulse discharge current Iimp (10/350) µs (line-earth) : 1kA
Total discharge current Itotal (8/20) µs: 8kA
Max. total discharge current I total max (8/20) µs : 10kA
Voltage protection level Up (line-line): ≤ 20 V (B2 - 1 kV / 25 A)
Voltage protection level Up (line-earth) : ≤ 700 V (B2 - 4 kV / 100 A)
Connection method IN : RJ45 Socket
Connection methoud OUT: RJ45 Socket
Standards regulations: IEC 61643-21/A1 2008
Certification / Approval: UL Listed

7 Two Wire Transducers (Hook Load, SPP, Drawworks Brake etc)


Surge protection, consisting of protective plug and base element, with
a integrated status indicator and disconnect knife for a 2-wire floating Ex i
signal circuit, e.g., 0(4) ... 20 mA current loop
IEC Test Classification: -
C1
b C2
C3
D1
c Nominal Voltage Un: 24 V DC
Direction of action: Line-Line & Line-Signal Ground/Shield & optional
d Signal
Ground/Shield-Earth Ground
e Maximum Continous Operating Voltage: 30V DC
f Rated Current 600mA
Nominal discharge current In
g (8/20) µs (line-line) : 5kA
h Nominal discharge current In (8/20) µs (line-ground): 5kA
i Pulse discharge current Iimp (10/350) µs (line-line): 0.5kA
j Pulse discharge current Iimp (10/350) µs (line-earth): 0.5 kA
k Total discharge current Itotal (8/20) µs: 10kA
Voltage protection level Up
l
(line-line): ≤ 55 V (C1 - 1 kV / 500 A)
Voltage protection level Up
m (line-earth): ≤ 900 V (C1 - 1 kV / 500 A)
n Impulse durability (line-line) : C2 - 10 kV / 5 kA
o Impulse durability (line-earth): C2 - 10 kV / 5 kA
IEC Standard: IEC 61643-21 / 2000 + corrigendum 2001 + A1:2008,
p
modified + A2:2012
q Approvals: UL Listed, IECEx, ATEX, DVN GL

8 Anti collision Sensors (Proximity Sensors)


Surge protection, consisting of protective plug and base element, with
a integrated status indicator and disconnect knife for a 2-wire Ex i signal
circuit with common reference potential, e.g., Digital IN/OUT
IEC Test Classification
C1
b C2
C3
D1
c Nominal voltage Un: 24 V DC
d lammability rating according to UL 94 V0
Direction of action: Line-Line & Line-Signal Ground/Shield & optional
e Signal
Ground/Shield-Earth Ground
f Maximum continuous voltage Uc: 30V DC
g Rated current: 600 mA
h Nominal discharge current In (8/20) µs (line-ground) : 5kA
i Pulse discharge current Iimp (10/350) µs (line-earth) : 0.5kA
j Total discharge current Itotal (8/20) µs: 10kA
k Voltage protection level Up (line-earth): ≤ 140 V (C1 - 1 kV / 500 A)

l Voltage protection level Up static (line-earth) ≤ 55 V (C1 - 1 kV / 500 A)

m Impulse durability (line-earth): C1 - 1 kV / 500 A


Standard Specification: IEC 61643-21 / 2000 + corrigendum 2001 +
n
A1:2008, modified + A2:2012
o Approvals: UL Listed, IECEx, ATEX, DVN GL
cification
SPD Article SPD Description
FLT-SEC-H-T1-3C-
2907260
440/25-FM

2906389 FLT-BK 350/3+1-FM

2906390 FLT-BK-350/1+1-FM
2859181 VAL-MS 320/3+1/FM

2804393 VAL-MS 320/1+1-FM


2800763 D-LAN-CAT 5-HC

TTC-6P-1X2-M-EX-
2906824
24DC-UT-I
TTC-6P-2X1-M-EX-
2906825
24DC-UT-I