com/hq/products/2838775
Protective plug PT with HF protective circuit for 4 signal wires. Nominal voltage: 12 V DC
GTIN
GTIN 4017918480646
Custom tariff number 85363010
Technical data
Dimensions
Height 45 mm
Width 17.7 mm
Depth 52 mm
Horizontal pitch 1 Div.
Complete module height 90 mm
Complete module width 17.7 mm
Complete module depth 65.5 mm
Ambient conditions
06/04/2018 Page 1 / 9
https://www.phoenixcontact.com/hq/products/2838775
General
Housing material PA 6.6
Flammability rating according to UL 94 V-0
Color jet black RAL 9005
Overvoltage category III
Degree of pollution 2
Mounting type on base element
Type Male
Number of positions 5
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-
Direction of action
Earth Ground
Arrester can be tested with CHECKMASTER from software version: From SW rev. 1.10
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage UN 12 V DC
Maximum continuous voltage UC 14 V DC
9.8 V AC
Rated current 450 mA (45°C)
Operating effective current IC at UC ≤ 5 µA
Residual current IPE ≤ 5 µA (with PT 2X2-BE)
≤ 1 µA (with PT 2X2+F-BE)
Nominal discharge current In (8/20) µs (Core-Core) 10 kA
Nominal discharge current In (8/20) µs (core-earth) 20 kA (in total)
Pulse discharge current Iimp (10/350) µs 2.5 kA
Total discharge current Itotal (8/20) µs 20 kA
Max. discharge current Imax (8/20) µs maximum (Core-Core) 10 kA
Max. discharge current Imax (8/20) µs maximum (Core-Earth) 20 kA (in total)
Nominal pulse current Ian (10/1000) µs (Core-Core) 67 A
Output voltage limitation at 1 kV/µs (core-core) spike ≤ 55 V
Output voltage limitation at 1 kV/µs (core-earth) spike ≤ 55 V (with PT 2X2-BE)
≤ 700 V (with PT 2X2+F-BE)
Output voltage limitation at 1 kV/µs (core-core) static ≤ 25 V
Output voltage limitation at 1 kV/µs (core-earth) static ≤ 25 V (with PT 2X2-BE)
06/04/2018 Page 2 / 9
https://www.phoenixcontact.com/hq/products/2838775
Connection data
Connection method Screw connection (in connection with the base element)
Screw thread M3
Tightening torque 0.8 Nm
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
06/04/2018 Page 3 / 9
https://www.phoenixcontact.com/hq/products/2838775
Drawings
90 17,7
600
I [mA]
400
200
65,5
0 51,5
30 40 50 60 70 80 90
T [°C]
Circuit diagram
1 2
5 6
7 8
IN OUT
11 12
9 10
*
3 4
06/04/2018 Page 4 / 9
https://www.phoenixcontact.com/hq/products/2838775
Classifications
eCl@ss
ETIM
UNSPSC
Approvals
Approvals
06/04/2018 Page 5 / 9
https://www.phoenixcontact.com/hq/products/2838775
Approvals
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 138168
Nominal current IN 0.45 A
Nominal voltage UN 12 V
EAC
EAC-Zulassung
RU C-
EAC
DE.A*30.B01561
Accessories
Accessories
Device marking
Zack marker strip, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type:
snap into tall marker groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm
06/04/2018 Page 6 / 9
https://www.phoenixcontact.com/hq/products/2838775
Zack Marker strip, flat, Strip, white, labeled, printed horizontally: consecutive numbers 1 - 10, 11 - 20, etc. up to 491 -
500, mounting type: snap into flat marker groove, for terminal block width: 5 mm, lettering field size: 5.15 x 5.15 mm
Zack Marker strip, flat, Strip, white, labeled, printed horizontally: consecutive numbers 2 - 20, 22 - 40, etc. up to 82 -
100, mounting type: snap into flat marker groove, for terminal block width: 5 mm, lettering field size: 5.15 x 5.15 mm
Zack Marker strip, flat, Strip, white, labeled, printed horizontally: Odd numbers 1 - 19, 21 - 39, etc. up to 81 - 99,
mounting type: snap into flat marker groove, for terminal block width: 5 mm, lettering field size: 5.15 x 5.15 mm
Zack Marker strip, flat, Strip, white, labeled, Printed vertically: consecutive numbers 1 - 10, 11 - 20, etc. up to 91 -
100, mounting type: snap into flat marker groove, for terminal block width: 5 mm, lettering field size: 5.15 x 5.15 mm
Marker pen
Marker pen without ink cartridge, for manual labeling of markers, labeling extremely wipe-proof, line thickness 0.35
mm
Terminal marking
06/04/2018 Page 7 / 9
https://www.phoenixcontact.com/hq/products/2838775
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type:
snap into flat marker groove, for terminal block width: 5 mm, lettering field size: 5.1 x 5.2 mm
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type:
snap into flat marker groove, for terminal block width: 5 mm, lettering field size: 5.15 x 5.15 mm
Base element for protective plug PT with protective circuit for two 2-wire floating signal circuit, bridge between the
connections 3-4 (GND) and 9-10, for mounting on NS 35/7.5 and NS 35/15, housing width: 17.5 mm
Base element for protective plug PT with protective circuit for two 2-wire floating signal circuit, gas-filled surge
arrester between the connections 3-4 (GND) and 9-10, for mounting on NS 35/7.5 and NS 35/15, housing width: 17.5
mm
Additional products
Shield fast connection for 3 ... 6 mm cable diameter. Potential connecting cable: 200 mm, 1 mm², color: black
06/04/2018 Page 8 / 9
https://www.phoenixcontact.com/hq/products/2838775
Shield fast connection for 5 ... 10 mm cable diameter. Potential connecting cable: 200 mm, 1 mm², color: black
06/04/2018 Page 9 / 9