Technical Data P846/EN TD/A11

MiCOM P846

TD

TECHNICAL DATA

Date: 9th May 2008


Hardware Suffix: J
Software Version: 30
Connection Diagrams: 10P846xx (xx = 01 to 07)
P846/EN TD/A11 Technical Data

MiCOM P846

TD
Technical Data P846/EN TD/A11

MiCOM P846 (TD) 2-1

Technical Data Rear Communications Port


EIA(RS)485 signal levels, two wire
Connections located on general purpose block,
Mechanical Specifications M4 screw.
For screened twisted pair cable, multi-drop,
1000m max.
Design For K-Bus or DNP3 protocol (ordering options).
Modular MiCOM Px40 platform relay, P846 Isolation to SELV level.
80TE case. Mounting is front of panel flush
mounting, or 19“ rack mounted (ordering Optional Second Rear Communications
options). Port
EIA(RS)232, 9 pin D-type female connector,
socket SK4.
TD
Enclosure Protection
Courier protocol: K-Bus, EIA(RS)232, or
Per IEC 60529: 1989 EIA(RS)485 connection.
IP 52 Protection (front panel) against dust and Isolation to SELV level.
dripping water.
IP 30 Protection for sides of the case. Optional Rear IRIG-B Interface
IP 10 Protection for the rear. BNC plug
Isolation to SELV level.
Weight 50 ohm coaxial cable.

Case 80TE: approx. 13.1 kg Optional Rear Fiber Connection for


SCADA/DCS
Terminals BFOC 2.5 -(ST®)-interface for glass fiber, as
per IEC 874-10.
850nm short-haul fibers, one Tx and one Rx.
AC Current and Voltage Measuring Inputs For Courier, IEC-870-5-103, DNP3 or
Located on heavy duty (black) terminal block: MODBUS protocol (ordering options).
Threaded M4 terminals, for ring lug
connection.
CT inputs have integral safety shorting, upon Ratings
removal of the terminal block.
AC Measuring Inputs
General Input/Output Terminals Nominal frequency: 50 and 60 Hz (settable)
For power supply, opto inputs, output contacts Operating range: 45 to 65Hz
and COM1 rear communications. Phase rotation: ABC
Located on general purpose (grey) blocks:
Threaded M4 terminals, for ring lug AC Current
connection. Nominal current (In): 1 and 5 A dual rated.
(1A and 5A inputs use different transformer tap
Case Protective Earth Connection connections, check correct terminals are
Two rear stud connections, threaded M4. wired).
Must be earthed (grounded) for safety, Nominal burden per phase: < 0.15 VA at In
minimum earth wire size 2.5mm2. Thermal withstand:
continuous 4 In
for 10s: 30 In
Front Port Serial PC Interface
for 1s; 100 In
EIA(RS)232 DTE, 9 pin D-type female
Linear to 64 In (non-offset AC current).
connector.
Courier protocol for interface to MiCOM S1
software. AC Voltage
Isolation to ELV level. Nominal voltage (Vn): 100 to 120 V or 380 to
Maximum cable length 15m. 480V phase-phase.
Nominal burden per phase: < 0.02 VA at Vn.
Thermal withstand:
Front Download/Monitor Port
continuous 2 Vn
EIA(RS)232, 25 pin D-type female connector.
for 10s: 2.6 Vn
For firmware downloads.
Isolation to ELV level.
P846/EN TD/A11 Technical Data

(TD) 2-2 MiCOM P846

Power Supply Reset: approx. 64% of battery nominal set.


Recognition time:
<2ms with long filter removed,
Auxiliary Voltage (Vx) <12ms with half-cycle ac immunity filter on.
Three ordering options:
(i) Vx: 24 to 48 Vdc
(ii) Vx: 48 to 110 Vdc, and 30 to Output Contacts
100Vac (rms)
(iii) Vx: 110 to 250 Vdc, and 100 to Standard Contacts
240Vac (rms) General purpose relay outputs for signaling,
tripping and alarming:
Operating Range Continuous Carry Ratings (Not Switched):
TD (i) 19 to 65V (dc only for this variant) Maximum continuous current: 10A
(ii) 37 to 150V (dc), 24 to 110V (ac) Short duration withstand carry: 30A for 3s
(iii) 87 to 300V (dc), 80 to 265V (ac) 250A for 30ms
With a tolerable ac ripple of up to 12% for a dc Rated voltage: 300 V
supply, per IEC 60255-11: 1979.
Make & Break Capacity:
Nominal Burden DC: 50W resistive
Quiescent burden: 11W. (Extra 1.25W when DC: 62.5W inductive (L/R = 50ms)
fitted with second rear Courier) AC: 2500VA resistive (cos φ = unity)
Additions for energized binary inputs/outputs: AC: 2500VA inductive (cos φ = 0.7)
Per opto input:
0.09W (24 to 54V), Make, Carry:
0.12W (110/125V), 30A for 3 secs, dc resistive, 10,000
0.19W (220/120V). operations (subject to the above limits of
Per energized output relay: 0.13W make / break capacity and rated voltage)

Make, Carry & Break:


Power-up Time 4A for 1.5 secs, dc resistive, 10,000
Time to power up < 11s. operations (subject to the above limits of
make / break capacity & rated voltage)
Power Supply Interruption
Per IEC 60255-11: 1979 0.5A for 1 sec, dc inductive, 10,000
The relay will withstand a 20ms interruption operations (subject to the above limits of
in the DC auxiliary supply, without make / break capacity & rated voltage)
de-energizing.
Per IEC 61000-4-11: 1994 10A for 1.5 secs, ac resistive / inductive,
The relay will withstand a 20ms interruption 10,000 operations (subject to the above
in an AC auxiliary supply, without limits of make / break capacity & rated
de-energizing. voltage)

Durability:
Battery Backup
Front panel mounted Loaded contact: 10 000 operations
Type ½ AA, 3.6V (SAFT advanced battery minimum,
Unloaded contact: 100 000 operations
reference LS14250)
Battery life (assuming relay energized for 90% minimum.
time) >10 years Operate Time (Total circuit response):
Less than 5ms
Field Voltage Output
Reset Time (Total circuit response):
Regulated 48Vdc
Current limited at 112mA maximum output Less than 5ms
High Speed / High Break Contacts
Digital (“Opto”) Inputs Continuous Carry Ratings (Not Switched):
Universal opto inputs with programmable Maximum continuous current: 10A
voltage thresholds. May be energized from the Short duration withstand carry: 30A for 3s
48V field voltage, or the external battery 250A for 30ms
supply. Rated voltage: 300 V
Rated nominal voltage: 24 to 250Vdc
Operating range: 19 to 265Vdc Make & Break Capacity:
Withstand: 300Vdc. DC: 7500W resistive
Nominal pick-up and reset thresholds: DC: 2500W inductive (L/R = 50ms)
Pick-up: approx. 75% of battery nominal set, Make, Carry:
Technical Data P846/EN TD/A11

MiCOM P846 (TD) 2-3

30A for 3 secs, dc resistive, 10,000 Environmental Conditions


operations (subject to the above limits of
make / break capacity & rated voltage)
Ambient Temperature Range
Make, Carry & Break: Per IEC 60255-6: 1988
30A for 3 secs, dc resistive, 5,000 Operating temperature range:
operations (subject to the above limits of -25°C to +55°C (or -13°F to +131°F).
make / break capacity & rated voltage) Storage and transit:
-25°C to +70°C (or -13°F to +158°F).
30A for 200 ms, dc resistive, 10,000
operations (subject to the above limits of Ambient Humidity Range
make / break capacity & rated voltage) Per IEC 60068-2-3: 1969:
56 days at 93% relative humidity and +40°C TD
10A (*), dc inductive, 10,000 operations Per IEC 60068-2-30: 1980:
(subject to the above limits of make / break Damp heat cyclic, six (12 + 12) hour cycles,
capacity & rated voltage) 93% RH, +25 to +55°C

*Typical for repetitive shots – 2 minutes idle


for thermal dissipation
Type Tests

Voltage Current L/R No of Insulation


shots in Per IEC 60255-5: 2000,
1 sec Insulation resistance > 100MΩ at 500Vdc
65V 10A 40ms 5 (Using only electronic/brushless insulation
tester).
150V 10A 40ms 4
250V 10A 40ms 2 Creepage Distances and Clearances
250V 10A 20ms 4 IEC 60255-5: 2000
Pollution degree 3,
MOV protection: Max Voltage 330V dc Overvoltage category III,
Impulse test voltage 5 kV.
Durability:
Loaded contact: 10 000 operations
minimum, High Voltage (Dielectric) Withstand
Unloaded contact: 100 000 operations EIA(RS)232 ports excepted.
minimum. (i) Per IEC 60255-5: 2000, 2 kV rms
AC, 1 minute:
Operate Time (Total circuit response): Between all case terminals connected
Less than 0.2ms together, and the case earth.
Reset Time (Total circuit response): Also, between all terminals of independent
Less than 8ms circuits.
1kV rms AC for 1 minute, across open
(Note that these contacts are polarity sensitive. watchdog contacts.
Refer to the external connection diagram for 1kV rms AC for 1 minute, across open
details.) contacts of changeover output relays.
(ii) Per ANSI/IEEE C37.90-1989 (reaffirmed
Watchdog Contacts 1994):
Non-programmable contacts for relay 1.5 kV rms AC for 1 minute, across open
healthy/relay fail indication: contacts of changeover output relays.
Breaking capacity:
DC: 30W resistive
DC: 15W inductive (L/R = 40ms) Impulse Voltage Withstand Test
AC: 375VA inductive (cos φ = 0.7) Per IEC 60255-5: 2000
Front time: 1.2 µs, Time to half-value: 50 µs,
Peak value: 5 kV, 0.5J
IRIG-B Interface Between all terminals, and all terminals and
External clock synchronization per IRIG case earth.
standard 200-98, format B.
Input impedance 6kΩ at 1000Hz
Modulation ratio: 3:1 to 6:1
Input signal, peak-peak: 200mV to 20V
P846/EN TD/A11 Technical Data

(TD) 2-4 MiCOM P846

Electromagnetic Compatibility Immunity to Radiated Electromagnetic


(EMC) Energy
Per IEC 60255-22-3: 2000, Class III:
Test field strength, frequency band 80 to 1000
1 MHz Burst High Frequency Disturbance MHz:
Test 10 V/m,
Per IEC 60255-22-1: 1988, Class III, Test using AM: 1 kHz / 80%,
Common-mode test voltage: 2.5 kV, Spot tests at 80, 160, 450, 900 MHz
Differential test voltage: 1.0 kV, Per IEEE/ANSI C37.90.2: 1995:
Test duration: 2s, Source impedance: 200Ω 25MHz to 1000MHz, zero and 100% square
EIA(RS)232 ports excepted. wave modulated.
Field strength of 35V/m.
TD 100kHz Damped Oscillatory Test
Per EN61000-4-18: 2006 Level 3 Radiated Immunity from Digital
2.5kV peak between independent circuits and Communications
case earth. Per EN61000-4-3: 2002, Level 4:
1.0kV peak across terminal of the same circuit. Test field strength, frequency band 800 to 960
MHz, and 1.4 to 2.0 GHz:
30 V/m,
Immunity to Electrostatic Discharge
Test using AM: 1 kHz / 80%.
Per IEC 60255-22-2: 1996, Class 4,
15kV discharge in air to user interface,
display, and exposed metalwork. Radiated Immunity from Digital Radio
Per IEC 60255-22-2: 1996, Class 3, Telephones
8kV discharge in air to all communication Per ENV 50204: 1995
ports. 10 V/m, 900MHz and 1.89GHz.
6kV point contact discharge to any part of the
front of the product. Immunity to Conducted Disturbances
Induced by Radio Frequency Fields
Electrical Fast Transient or Burst Per IEC 61000-4-6: 1996, Level 3,
Requirements Disturbing test voltage: 10 V
Per IEC 60255-22-4: 2002. Test severity
Class III and IV: Power Frequency Magnetic Field Immunity
Amplitude: 2 kV, burst frequency 5kHz Per IEC 61000-4-8: 1994, Level 5,
(Class III), 100A/m applied continuously,
Amplitude: 4 kV, burst frequency 2.5kHz 1000A/m applied for 3s.
(Class IV). Per IEC 61000-4-9: 1993, Level 5,
Applied directly to auxiliary supply, and 1000A/m applied in all planes.
applied to all other inputs. EIA(RS)232 Per IEC 61000-4-10: 1993, Level 5,
ports excepted. 100A/m applied in all planes at
100kHz/1MHz with a burst duration of 2s.
Surge Withstand Capability
IEEE/ANSI C37.90.1:2002: Conducted Emissions
4kV fast transient and 2.5kV oscillatory applied Per EN 55022: 1998: Class A
common mode and differential mode to opto 0.15 - 0.5MHz, 79dBμV (quasi peak)
inputs (filtered), output relays, CTs, VTs, 66dBμV (average)
power supply, field voltage.
0.5 - 30MHz, 73dBμV (quasi peak) 60dBμV
4kV fast transient and 2.5kV oscillatory applied
(average).
common mode to communications, IRIG- B.

Radiated Emissions
Surge Immunity Test
Per EN 55022: 1998: Class A
EIA(RS)232 ports excepted.
30 - 230MHz, 40dBμV/m at 10m
Per IEC 61000-4-5: 2002 Level 4
measurement distance
Time to half-value: 1.2/50 µs,
Amplitude: 4kV between all groups and case 230 - 1GHz, 47dBμV/m at 10m
earth, measurement distance.
Amplitude: 2kV between terminals of each
group.
Technical Data P846/EN TD/A11

MiCOM P846 (TD) 2-5

EU Directives

EMC Compliance
Per 2004/108/EC:
Compliance to the European Commission
Directive on EMC is claimed via the Technical
File route. Product Specific Standards were
used to establish conformity:
EN50263: 2000
Product Safety
Per 2006/95/EC: TD
Compliance with European Commission Low
Voltage Directive.
Compliance is demonstrated by reference to
product safety standards:
EN60255-27: 2005

2004/108/EC

Mechanical Robustness

Vibration Test
Per IEC 60255-21-1: 1996
Response Class 2
Endurance Class 2

Shock and Bump


Per IEC 60255-21-2: 1995
Shock response Class 2
Shock withstand Class 1
Bump Class 1

Seismic Test
Per IEC 60255-21-3: 1995
Class 2

Px40 Third Party Compliances


(UL/CUL)

File Number: E202519 Original Issue Date: 21-


04-2005 (Complies with Canadian and US
requirements).
P846/EN TD/A11 Technical Data

(TD) 2-6 MiCOM P846

Protection Functions 6000Ω


External clock synchronization:
Conforms to IRIG standard 200-98, format B
Open Line Detector Protection
Disturbance Records
Performance
Fast Operation: ≤35ms
Accuracy
Magnitude and relative phases:
Voltage Transformer Supervision ±5% of applied quantities
Duration: ±2%
Trigger position: ±2% (minimum Trigger
TD Accuracy
Fast block operation: <25ms 100ms)
Fast block reset: <30ms Line length: 0.01…1000kn
Time delay: Setting ±2% or 20ms whichever is Line impedance (100/110V):100mΩ...500Ω
greater Line impedance (380/480V):
Line angle: 20°…90°
KZN residual: 0…10.00
Programmable Scheme Logic KZN res. angle: -180º ... +90º

Accuracy
Output conditioner timer: Setting ±2% or 50ms
whichever is greater Settings, Measurements and
Dwell conditioner timer: Setting ±2% or 50ms Records List
whichever is greater
Pulse conditioner timer: Setting ±2% or 50ms
whichever is greater Settings List

Measurements and Recording Global Settings (System Data)


Facilities Language: English/French/German/Spanish
Frequency: 50/60Hz
Measurements
Current: 0.05… 3In Circuit Breaker Control
Accuracy: ±1.0% of reading (CB Control)
Voltage: 0.05…2Vn CB Control by:
Accuracy: ±1.0% of reading Disabled
Power (W): 0.2…2Vn 0.05…3In Local
Accuracy: ±5.0% of reading at unity power Remote
factor Local+Remote
Reactive Power (Vars): Opto
0.2…2Vn, 0.05…3In Opto+local
Accuracy: ±5.0% of reading at zero power Opto+Remote
factor Opto+Rem+local
Apparent Power (VA): 0.2…2Vn 0.05…3In Close Pulse Time: 0.10…10.00s
Accuracy: ±5% of reading Trip Pulse Time: 0.10…5.00s
Energy (Wh): 0.2…2Vn 0.2…3In Man Close t max: 0.01…9999.00s
Accuracy: ±5% of reading at zero power factor Man Close Delay: 0.01…600.00s
Energy (Varh): 0.2…2Vn 0.2…3In CB Healthy Time: 0.01…9999.00s
Accuracy: ±5% of reading at zero power factor Check Sync. Time: 0.01…9999.00s
Phase accuracy: 0°…360° Reset Lockout by: User Interface/CB Close
Man Close RstDly: 0.10…600.00s
Accuracy: ±0.5%°
CB Status Input:
Frequency: 45…65Hz
None
Accuracy: ±0.025Hz
52A
52B
Performance 52A & 52B
Year 2000: Compliant
Real time clock accuracy: <±2 seconds/day
Modulation ratio: 1/3 or 1/6
Input signal peak-peak amplitude:
200mV…20V
Input impedance at 1000Hz:
Technical Data P846/EN TD/A11

MiCOM P846 (TD) 2-7

Date and Time Oscillography (Disturb. Recorder)


IRIG-B Sync.: Disabled/Enabled Duration: 0.10…10.50s
Battery Alarm: Disabled/Enabled Trigger Position: 0.0…100.0%
Trigger Mode: Single/Extended
Analog Channel 1:
Configuration (up to):
Setting Group: Analog Channel 8:
Select via Menu Disturbance channels selected from:
Select via Opto IA/IB/IC/IN/VA/VB/VC/VND/IA2/IB2/IC2/IN2
Active Settings: Group 1/2/3/4 and a series of internal variables pertaining
Setting Group 1: Disabled/Enabled to the DLO algorithm
Setting Group 2: Disabled/Enabled Digital Input 1:
Setting Group 3: Disabled/Enabled (up to):
TD
Setting Group 4: Disabled/Enabled Digital Input 32:
Supervision: Disabled/Enabled Selected binary channel assignment from
Fault Locator: Disabled/Enabled any DDB status point within the relay (opto
Input Labels: Invisible/Visible input, output contact, alarms, starts, trips,
Output Labels: Invisible/Visible controls, logic…).
CT & VT Ratios: Invisible/Visible Input 1 Trigger: No Trigger/Trigger L/H/Trigger
Record Control: Invisible/Visible H/L
Disturb Recorder: Invisible/Visible (up to):
Measure’t Setup: Invisible/Visible Input 32 Trigger: No Trigger/Trigger L/H/
Comms Settings: Invisible/Visible Trigger H/L
Commission Tests: Invisible/Visible
Setting Values: Primary/Secondary
Control Inputs: Invisible/Visible Measured Operating Data
Ctrl I/P Config: Invisible/Visible (Measure't. Setup)
Ctrl I/P Labels: Invisible/Visible Default Display:
Direct Access: 3Ph + N Current
Disabled 3Ph Voltage
Enabled Power
Hotkey only Date and Time
CB Cntrl. only Description
LCD Contrast: (Factory pre-set) Plant Reference
Frequency
CT and VT Ratios Access Level
Main VT Primary: 100V...1MV Local Values: Primary/Secondary
Main VT Sec'y: 80...140V Remote Values: Primary/Secondary
Phase CT Primary: 1A…30kA Measurement Ref: VA/VB/VC/IA/IB/IC
Phase CT Sec'y: 1A/5A Measurement Mode: 0/1/2/3
Phase CT2 Primary: 1A…30kA Fix Dem. Period: 1…99mins
Phase CT2 Sec'y: 1A/5A Roll Sub Period: 1…99mins
CVT Enable: Disabled/Enabled Num. Sub Periods: 1…15
CVT Threshold: 0.00…100.00% Distance Unit: Miles/Kilometers
Tie-Line Factor: Disabled/Enabled Fault Location:
Base Power: 0W…5GW Distance
Line charging: 0Var…5GVar Ohms
% of Line
Remote2 Values: Primary/Secondary
Sequence of Event Recorder
(Record Control) Communications
Alarm Event: Disabled/Enabled RP1 Protocol:
Relay O/P Event: Disabled/Enabled Courier
Opto Input Event: Disabled/Enabled DNP 3.0
General Event: Disabled/Enabled RP1 Address:
Fault Rec. Event: Disabled/Enabled 0…255
Maint. Rec. Event: Disabled/Enabled RP1 InactivTimer: 1…30mins
Protection Event: Disabled/Enabled RP1 Parity:
DDB 31 - 0: (up to): Odd/Even/None
DDB 1022 - 992: RP1 Meas Period: 1…60s
Binary function link strings, selecting which RP1 PhysicalLink:
DDB signals will be stored as events, and Copper
which will be filtered out Fiber Optic ( DNP3.0, Courier)
P846/EN TD/A11 Technical Data

(TD) 2-8 MiCOM P846

K-Bus (Courier only) 50% - 70%


RP1 Time Sync: Disabled/Enabled
RP1 Port Config. (Courier):
K Bus
Control Inputs into PSL
EIA(RS)485 (Ctrl. I/P Config.)
Hotkey Enabled:
Binary function link string, selecting which of
Optional Additional Second Rear the control inputs will be driven from
Communication (Rear Port2 (RP2)) Hotkeys.
RP2 Protocol: Courier (fixed) Control Input 1: Latched/Pulsed
RP2 Port Config: (up to):
Courier over EIA(RS)232 Control Input 32: Latched/Pulsed
TD Courier over EIA(RS)485 Ctrl Command 1:
K-Bus (up to):
RP2 Comms. Mode: Ctrl Command 32:
IEC60870 FT1.2 Frame ON/OFF
10-Bit NoParity SET/RESET
RP2 Address: 0…255 IN/OUT
RP2 InactivTimer: 1…30mins ENABLED/DISABLED
RP2 Baud Rate:
9600 bits/s Control Input User Labels
19200 bits/s
(Ctrl. I/P Labels)
38400 bits/s
Control Input 1:
(up to):
Commission Tests Control Input 32:
Monitor Bit 1: User defined text string to describe the
(up to): function of the particular control input
Monitor Bit 8:
Binary function link strings, selecting which
Settings in Multiple Groups
DDB signals have their status visible in the
Note: All settings here onwards apply for
Commissioning menu, for test purposes
setting groups # = 1 to 4.
Test Mode:
Disabled
Test Mode
Blocked Contacts
Test Pattern: Protection Functions
Configuration of which output contacts are to
be energized when the contact test is Fuse Failure (VT Supervision)
applied. VTS Status:
Static Test Mode: Disabled/Enabled Blocking/Indication
VTS Reset Mode: Manual/Auto
Optocoupled Binary Inputs VTS Time Delay: 1.0…10.0s
VTS I> Inhibit: 0.08…32.00 In
(Opto Config.) VTS I2> Inhibit: 0.05…0.50 In
Global threshold:
24 - 27V
30 - 34V Fault Locator
48 - 54V Line Length (km): 0.001…1000.000km
110 - 125V Line Length (mi): 0.20…625.00mi
220 - 250V Line Impedance: 0.10…250.00Ω
Custom Line Angle: 20…85 o
Opto Input 1: KZN Residual: 0.00…7.00
(up to): KZN Res. Angle: -90…90 o
Opto Input #. (# = max. opto no. fitted):
Custom options allow independent
thresholds to be set per opto, from the same Opto Input Labels
range as above. Opto Input 1:
Filter Control: (up to):
Binary function link string, selecting which Opto Input 24:
optos will have an extra 1/2 cycle noise filter, User defined text string to describe the
and which will not. function of the particular opto input.
Characteristics:
Standard 60% - 80%
Technical Data P846/EN TD/A11

MiCOM P846 (TD) 2-9

Output Labels Independent power factor measurements


Relay 1: for all three phases (ϕ = A, B, C)
(up to): 3Ph WHours Fwd
Relay 32: 3Ph WHours Rev.
User defined text string to describe the 3Ph VArHours Fwd
function of the particular relay output contact. 3Ph VArHours Rev.
3Ph W Fix Demand
3Ph VArs Fix Dem.
Measurements List Iϕ Fixed Demand
Maximum demand currents measured on a
Measurements 1 per phase basis (ϕ = A, B, C)
3Ph W Roll Dem.
Iϕ Magnitude
3Ph VArs Roll Dem.
TD
Iϕ Phase Angle
Iϕ Roll Demand
Per phase (ϕ = A, B, C) current
Maximum demand currents measured on a
measurements
per phase basis (ϕ = A, B, C)
IN Derived Mag.
3Ph W Peak Dem.
IN Derived Angle
3Ph VAr Peak Dem.
I1 Magnitude
I2 Magnitude Iϕ Peak Demand
I0 Magnitude Maximum demand currents measured on a
Iϕ RMS per phase basis (ϕ = A, B, C)
Reset Demand: Yes/No
Per phase (ϕ = A, B, C) RMS current
measurements
Vϕ-ϕ Magnitude Fault Record Proforma
Vϕ-ϕ Phase Angle The following data is recorded for any
Vϕ Magnitude relevant elements that operated during a
Vϕ Phase Angle fault, and can be viewed in each fault record.
All phase-phase and phase-neutral voltages Time & Date
(ϕ = A, B. C) Event Text
VN Derived Mag. Event Value
VN Derived Ang. Select Fault: [0...n]
V1 Magnitude. Breaker Fail:
V2 Magnitude CB Fail 1
V0 Magnitude Supervision
Vϕ RMS VTS
All phase-neutral voltages (ϕ = A, B, C) Start Elements:
Frequency Trip Elements:
Iϕ Magnitude Binary data strings for fast polling of which
protection elements started or tripped for the
Iϕ Phase Angle
fault recorded.
Per phase (ϕ = A2, B2, C2) current
Fault Alarms:
measurements
Binary data strings for fast polling of alarms
Heartbeat
for the fault recorded.
DMA Beat
Fault Time:
Band used
Active Group: 1/2/3/4
Iϕ RMS System Frequency: Hz
Per phase (ϕ = A2, B2, C2) RMS current Fault Duration: s
measurements CB Operate Time: s
Relay Trip Time: s
Measurements 2
Fault Location: km/miles/Ω/%
ϕ Phase Watts
The current magnitudes and phase angles
ϕ Phase VArs stored before the fault inception.
ϕ Phase VA Iϕ
All phase segregated power
Vϕ:
measurements, real, reactive and apparent
Per phase record of the current and voltage
(ϕ = A, B, C) magnitudes during the fault.
3 Phase Watts IN Derived
3 Phase VArs VAN
3 Phase VA VBN
Zero Seq. Power VCN
3Ph Power Factor VN Derived
ϕPh Power Factor
P846/EN TD/A11 Technical Data

(TD) 2-10 MiCOM P846

TD