3. Description ..................................................................................................................................5
• General requirement empty enclosures for low-voltage switchgear and control gear as-
semblies IEC 62208
(2265 x 834 x 860 mm/89,173 x 32,835 x 33,858” single cubicle with cover sheets)
• Can be assembled and shipped in multiple cubicle combinations of max. four cubicles
• Are supplied with a swing frame for installing 19" racks and modules
• Have standard protection conforming to protection class IP 54, but are also avail- able with
protection class IP 40 and IP 21
• Are designed to provide good low impedance grounding as one of preconditions for proper
functionality of equipped cubicle from EMC point of view
•= standard O = optional * customized width dimensions available, see catalog or on demand
Standard:
Optional :
Type RESP07
Material thickness Standard - Base frame (C-profiles, roof, floor): 2.5 mm/0,098” sheet steel
- Doors: 2.0 mm/0,079” sheet steel
- Cover sheets: 1.5 mm/0,059” sheet steel
Optional - Cover sheets: 2.0 mm/0,079” sheet steel
Ambient conditions Standard For indoor installations, normal service conditions IEC 61439-1
Dimensions (mm) Standard 2200 x 800 x 800 mm/ 86,614 x 31,496 x 31,496 “
H xW xD Optional
2000 mm/78,74”
- Height
600 mm/23,622”, 700 mm/27,559”, 1000 mm/39,37”,
- Width
others see catalog or on demand
- Depth 600 mm/23,622”
Protection class Standard IP 54: dust-proof, additionally proof against splashed/sprayed IEC 60529
water
Optional IP 40: proof against wire-shaped foreign bodies >1 mm/0,039”
Standard IK 10 for metal parts of cabinets IK 08 for glass door IEC 62262
Front door Standard Door with safety glass window DIN 1249-12
Door without ventilation outlets
Hinged on the left or right side
Opening angle up to 245° (free standing)
Color: RAL7035
Heater & thermo- Standard 55 W, thermostat-controlled for cubicle width 800 mm/31,496”
stat 125 W, thermostat-controlled for cubicle width 1600 mm/62,992”
Earthing bar Standard Horizontal copper earthing bar at bottom-rear of the cubicle.
Section of earthing bar 30 x 5 mm/1,181 x 0,197”.
Approbations General requirements Empty enclosures for low-voltage switchgear and controlgear assem- Test report
blies no.
Tested by EZU (Electrotechnical Test Institute), Prague, CZ 501115-01/06
IP Protection class Protection class test acc. IEC 62208 / IEC 60529 Certificate no.
Empty enclosures for low-voltage switchgear and controlgear assem- 1180620
blies - General requirement Test report
Tested by EZU (Electrotechnical Test Institute), Prague, CZ no.
00191B/2015
703119-01/01
703119-01/02
Corrosion Protection class test acc. IEC 60068-2-6 Test report
Empty enclosures for low-voltage switchgear and controlgear assem- no.
blies - General requirement 501115-01/03
Tested by EZU (Electrotechnical Test Institute), Prague, CZ
Transport Vibration tests in vertical and horizontal positions Test report
- Dynamic vibration acc. to EN 60068-2-6 no.
- Random vibration acc. to AECTP-400 and MIL-STD-810E 6430-22-2009
- Bump (repeated shocks) acc. to EN 60068-2-29
Tested by VOP-026 Šternberk s.p., division VTUPV, Vyskov, CZ 6430-30-2009
Seismic High required response spectrum, 0,5 g acc. to IEEE Std. 693-2005 Test report
Fig. A.1 no.
Tested by VTUPV, Vyskov, CZ 194200-87/2019
Floor deformation Stepping with a load up to 170 kg on floor without deformation
Fig. 9 Temperature rise in middle and upper part of cubicle: Free standing
Fig. 10 Temperature rise in middle and upper part of cubicle: Middle of row surrounded by other cubicles
Fig. 12 Temperature rise in middle and upper part of cubicle: Free standing IP21 (without front door)