Risers over 3' must have a 4-way brace no more than 25' apart with flex couplings at the top and bottom. Branch lines must have seismic bracing at maximum spacing of 18'-53' at a minimum angle of 45 degrees within 6" of hangers. Restraints are required at the end of branch lines and for sprinklers over 4'. C-clamps and powder actuated fasteners cannot be used for bracing. Bracing must attach to the top of structure members.
Risers over 3' must have a 4-way brace no more than 25' apart with flex couplings at the top and bottom. Branch lines must have seismic bracing at maximum spacing of 18'-53' at a minimum angle of 45 degrees within 6" of hangers. Restraints are required at the end of branch lines and for sprinklers over 4'. C-clamps and powder actuated fasteners cannot be used for bracing. Bracing must attach to the top of structure members.
Risers over 3' must have a 4-way brace no more than 25' apart with flex couplings at the top and bottom. Branch lines must have seismic bracing at maximum spacing of 18'-53' at a minimum angle of 45 degrees within 6" of hangers. Restraints are required at the end of branch lines and for sprinklers over 4'. C-clamps and powder actuated fasteners cannot be used for bracing. Bracing must attach to the top of structure members.
-Risers exceeding 3’-0” in length to be provided with a 4 way brace,
- The 4 way can provide longitudinal and lateral bracing for adjacent mains (within 24”), -4 way maximum 25’-0” apart vertically, - Flex couplings at the top and bottom. Exception: -riser nipples -risers penetrating intermediate floors in multistory buildings (with flex cplgs within 1’-0” of floors) NEVER EVER EVER - Use C- type clamps to attach sway braces to structure (even with retaining straps), - Use powder-driven fasteners to attach sway braces to structure, - Brace a length of pipe to 2 different sections of the building, - Attach a seismic brace to bar joist web members. (TOP OF STRUCTURE MEMBER) ALWAYS - Seismic bracing shall be attached to building structure (top of beams and bar joists), - Look details on plans.
Branch line Restraints
- All branch lines at maximum spacing from 18ft. to 53 ft. (table on drawings), - Hanger not less than 45 degrees from vertical, installed within 6” of the vertical hanger (rod hanger= tight to the pipe). 3/8 rod maximum 22” long. If it is impossible to fulfill both requirements for the angle and the rod length, install rods on both sides of pipe, or: - Wire restraint (n#12, 440lb installed at least 45 degrees from vertical plane both sides of pipe) located within 2ft of a hanger (hanger= rod tight to pipe). - The end sprinkler on a branch line needs to be restrained, - Sprigs 4ft. or longer need to be restrained. Exception: - Armovers (1 head) & drops, - Pipes supported by rods less than 6 in. measured between the top of the pipe and the point of attachment to the building structure.
ALWAYS - Install restraining straps (need to wrap around the beam flange not less than 1 in.), - Look details on plans.