You are on page 1of 6

Wood-frame walls and floors

offer designers a unique


opportunity to provide structures
with economy as well as proven
energy performance. Where these
assemblies are required by the
building codes to achieve a
minimum fire endurance rating, a
wide range of options for design
exists.

BUILDING CODE
REQUIREMENTS
For both new and existing
construction, many building codes
require structural elements such as
exterior walls, load bearing
partitions, floor/ceiling assemblies
and roofs to achieve a minimum
fire endurance rating. Historically,
these “protected” assemblies have
been tested in accordance with the
standard fire test and assigned an
hourly fire endurance rating based
on time to failure. The ASTM
Standard E119 “Standard Method
of Fire Tests of Building
Construction and Materials” is
normally used.
Many sources are available for
obtaining information on the fire
endurance of assemblies.
Generally, publications from
recognized testing laboratories are
the source for fire endurance
ratings of assemblies that have
been tested. Building codes and
regulators accept assemblies
included in these publications as
having the identified fire endurance “Ten Rules” provided a method for
rating. Until recently, building combining the individual In developing the
officials did not recognize methods contributions to obtain the fire methodology, the Fire Test Board
for determining the fire endurance endurance rating of the assembly. broke down the fire endurance of
rating other than through testing. the assembly into the fire
This has resulted in non- Use and Application endurance contribution of the
acceptance of many assemblies Combining results of the fire exposed membrane and the time
for which an experimental fire tests and basis provided by the ten to destruction of the framing
endurance rating was not rules, a methodology for members. As a result, the
available. calculating fire endurance ratings calculated fire endurance would
To permit use of “non-listed” was developed. The review of full- equal the sum of 1) the
assemblies, a methodology for scale wood-framed assembly fire contribution of the fire exposed
calculating the fire endurance of tests by the Fire Test Board membrane, 2) the time to failure of
load bearing and non-load bearing validated the methodology. These the framing members, and if
floor, wall, ceiling and roof tests included both load bearing applicable 3) any additional
assemblies has been adapted for and non-load bearing assemblies protection due to use of cavity
use. A number of building codes with wood, gypsum wallboard and insulation or reinforcement of the
now accept fire endurance ratings other membranes. Fire endurance membrane.
developed by this “Component ratings ranged from 20 to 90 The times assigned to
Additive Method” (CAM) minutes. protective wall and ceiling
calculation methodology. coverings are given in Table 1.
These times are based on the
COMPONENT ADDITIVE ability of the membrane to remain
METHOD (CAM) in place during fire tests. This
“assigned time” should not be
History confused with the “finish” rating of
The original methodology for the membrane. The “finish rating”
calculating fire endurance ratings is the time it takes for the
of assemblies by CAM was temperature to rise 250°F on the
developed in the early Sixties by unexposed surface of a material
the Fire Test Board of the National when the material is exposed to a
Research Council of Canada. The heat source following the ASTM E
methodology resulted from their 119 Time-Temperature curve. As
detailed review of 135 standard fire shown in Table 1, some pairs of
test reports on wood stud walls membranes have been tested
and 73 test reports on wood-joist resulting in greater fire endurance
floor assemblies and the “Ten times than the sum of the ratings
Rules of Fire Resistance Rating” of the individual membranes, in
by Tibor Harmathy, an eminent fire accordance with Harmathy’s rule
researcher from the National #1.
Research Council of Canada (see The times assigned to wood
Rules). Review of the fire tests studs and joists were determined
provided assigned time values for based upon the time it takes for
contribution to fire endurance the framing members to fail after
ratings for each separate failure of the protective membrane.
component of an assembly. The The fire endurance time assigned
TEN RULES OF FIRE ENDURANCE RATING

The ten rules with a brief encased by wall coverings adds to Walls which do not have the
explanation are set forth below: the fire endurance rating of these same panel materials on both
assemblies. faces will demonstrate different fire
Rule 1. The "thermal" fire endurance ratings depending upon
endurance of a construction Rule 4. The farther an air gap or which side is exposed to fire. This
consisting of a number of parallel cavity is located from the exposed rule results as a consequence of
layers is greater than the sum of surface, the more beneficial its Rules 4 and 6, which point out the
the "thermal" fire endurance effect on the fire endurance. importance of location of air gaps
characteristics of the individual In cases where cavities are or cavities and of the sequence of
layers when exposed separately formed by joists or studs and different layers of solids.
to fire. protected by 2-inch thick panel
Where two layers of panel materials against fire exposure, the Rule 8. The presence of moisture,
materials, such as gypsum beneficial effect of such air cavities if it does not result in explosive
wallboard or plywood, are fastened is greater than if the protection is spalling, increases fire resistance.
to studs or joists separately, their only ½-inch thick. Materials having a 15 percent
combined effect is greater than the moisture content will have greater
sum of their individual Rule 5. The fire endurance of an fire endurance than those having 4
contributions to the fire assembly cannot be increased by percent moisture content at the
endurance rating of the increasing the thickness of a time of fire exposure.
assembly. For example, the fire completely enclosed air layer.
endurance time assigned to 1/2 Increasing stud or joist depths Rule 9. Load-supported
inch gypsum wallboard is 15 from 4 inches to 6 inches, or even elements, such as beams, girders
minutes (see Table 1). Two layers to 12 inches, does not increase the and joists, yield higher fire
of 1/2 inch gypsum wallboard have level of fire endurance. endurance when subject to fire
an endurance rating greater than endurance tests as parts of floor,
15+15=30 minutes. Rule 6. Layers of materials of low roof, or ceiling assemblies than
thermal conductivity are better they would when tested
Rule 2. The fire endurance of a utilized on the side of the separately.
construction does not decrease construction on which fire is more A wood joist performs better
with the addition of further layers. likely to happen. when it is incorporated in a
This is almost the converse of A building material made of floor/ceiling assembly, than tested
Rule 1. It says that any additional wood fiber is more effective by itself under the same load.
layers of wallboard or other panel against thermal transfer than is a
materials will add to fire endurance material having relatively high Rule 10. The load-supporting
no matter how many layers are thermal conductivity, such as elements (beams, girders, joists,
added. metal. Wood will be more effective etc.) of a floor, roof, or ceiling
in protecting against excessive rise assembly can be replaced by such
Rule 3. The fire endurance of in temperature on the opposite other load-supporting elements
constructions containing face of assemblies. This which, when tested separately,
continuous air gaps or cavities is temperature rise can lead to failure yielded fire endurance not less
greater than the fire endurance of under test acceptance criteria. than that of the assembly.
similar constructions of the same A joist in a floor assembly may
weight, but containing no air gaps Rule 7. The fire endurance of be replaced by another type of joist
or cavities. asymmetrical constructions having a fire endurance rating not
Wall and ceiling cavities formed depends on the direction of heat less than that of the assembly.
by studs and joists protected and flow.
to framing members is given in on the unexposed side of an ROOFS AND FLOOR/CEILING
Table 2. These times are based exterior wall is to keep the ASSEMBLIES
on the ability of framing members insulation in place and prevent the In the case of a roof or
to provide structural support when transmission of heat. Fire floor/ceiling assembly, fire testing
subjected to the ASTM E 119 fire is normally done with exposure
endurance test without the benefit from below the assembly. To
of a protective comply with this calculation
methodology, floor and roof
assemblies must have a protective
membrane in conformance with
Table 1. The upper membrane
must consist of a subfloor or roof
deck and finish in conformance
with Table 5. Alternatively, any
combination of membranes listed
in Table 1, with a fire endurance
rating of at least 15 minutes, may
be used on the unexposed (upper)
membrane. These time values are side. If the proposed assembly is
in part the result of full-scale tests a ceiling with an attic above, most
of unprotected wood studs and building codes allow elimination of
floor joists where the structural the upper membrane.
elements were loaded to design
capacity. They apply to all framing endurance of wall assemblies is EXAMPLE CALCULATIONS
members and do not increase if, consistently dependent upon the Example 1: Determine the fire
for example, 2 by 6 inch studs are fire exposed-side membrane. As a endurance rating of a wall assembly
used rather than 2 by 4 inch studs result, it is considered very having one layer of 5/8 inch Type X
as implied by Harmathy’s rule #5. gypsum wallboard attached to wood
reasonable to substitute various studs on the fire exposed side (interior,
exterior cladding materials as the see Figure 1).
WALLS membrane on the unexposed side
Additional fire endurance can 1 Table 1 shows that 5/8 inch
or exterior wall assemblies . Type X gypsum wallboard has a
be provided to wall assemblies by Therefore, where a fire endurance
the use of high density rockwool or fire endurance time of 40 minutes.
rating for an exterior wall is to be Table 2 shows that wood studs
paper or foil-faced glass fiber determined using CAM, any
insulation batts. The time spaced 16 inches on center have a
combination of sheathing, paper, fire endurance time of 20 minutes.
assigned to each type of insulation and exterior finish listed in Table 4
as contributing additional fire (Adding additional membranes to
may be used, or the outer the framing would also be
endurance to the assembly is membrane may consist of any
presented in Table 3. For a wall or permitted according to Harmathy’s
membrane combination that is rule #2.
partition where only plywood is assigned a time for contribution to
used as the membrane on the side fire endurance of at least 15
assumed to be exposed to the fire, minutes in Table 1.
insulation shall be used within the
assembly.
In developing this methodology
it was also determined that the
primary function of the membrane
1
For examples of fire rated exterior walls see “Design for Code Acceptance No. 3: Fire Rated Wood Wall Assemblies, “ American Forest & Paper Association, 2000.
If the wall is assumed to be
exposed to fire from both sides
(e.g., for interior fire rated
partitions), each surface of the
framing member would be required
to be fire protected with at least 40
minutes of membrane coverings in
Table 1. If the proposed wall is
assumed to be exposed to fire
from one side only, as is required
of an exterior wall, the fire
exposure is assumed to be from
the interior, which would require a
total contribution of 40 minutes
from the membrane coatings from
Table 1. It should be noted that to
achieve the assigned fire
endurance rating, the exterior side
must be protected in accordance
with Table 4 or any membrane that
is assigned a time of at least 15
minutes as listed in Table 1.
If wall cavities between studs
had been filled with rockwool
insulation adding 15 minutes of fire
endurance, as noted in Table 3,
the 5/8” Type X gypsum wallboard
could be replaced by ½” Type X
gypsum wallboard. Thus, adding
the fire endurance contribution Example 2: Determine the fire
times for the ½ inch gypsum Table 1 shows that the fire
endurance rating of a floor/ceiling endurance time for each layer of ½
wallboard, wood studs, and assembly having wood joists spaced
insulation (25 minutes + 20 inch Type X gypsum wallboard is
16 inches on center and protected on
minutes + 15 minutes) the the bottom side (ceiling side) with two
25 minutes. The fire endurance
resultant fire endurance rating for layers of ½ inch Type X gypsum time assigned for wood joists, as
the wall would also equal 60 wallboard and having a ½ inch shown in Table 2, is 10 minutes.
minutes. plywood subfloor on the upper side Adding the assigned times of two
(floor side). layers of gypsum wallboard and
According to Table 3, the glass CONCLUSION
fiber does not contribute to the fire Assemblies of wood
endurance of a load bearing wall. construction are used increasingly
Thus, the fire endurance rating of in architectural designs because of
the exterior wall of the residence their adaptability to a variety of
equals 35 minutes. style preferences, economies of
construction, and the energy
saving performance of such
systems. These assemblies can
now be evaluated to determine
their fire endurance rating by a
wood joists, a fire endurance Component Additive Method,
rating of 60 minutes or one hour is avoiding expensive fire testing.
calculated. Designers are also encouraged
In order to upgrade the wall to
to review AF&PA’s Code
one hour, a protective membrane
Conforming Wood Design
should be added on the inside, 2
software for additional
contributing 25 minutes or more to
information.
the assembly rating. For example,
a ½ inch Type X gypsum wallboard
adds 25 minutes according to
Table 1, leading to a total of 60
minutes.
Example 3: A private residence is The procedure described in this
being changed to an office. The load publication is intended to assist the
bearing exterior walls of the residence designer of wood-frame structures
consist of 2 by 4 inch studs spaced 16 in meeting specified fire endurance
inches on center, ½ gypsum wallboard requirements. Special effort has
on the inside, and 5/16 inch exterior been made to insure the accuracy
grade plywood, sheathing paper and ¼
of the information presented.
inch hardboard siding on the outside.
The cavities between the wood studs However, AF&PA does not
are filled with ¼ lb/sq.ft. glass fiber assume responsibility for particular
batts. The code requires the exterior designs or calculations prepared
wall of the structure to be upgraded to from this publication.
one hour fire endurance with fire
exposure from the inside only. What
modifications can be made to comply
with the code requirement? For additional information or
assistance contact:
Table 1 shows the ½ inch American Forest & Paper Association
gypsum wallboard has a American Wood Council
contribution to the assembly fire th
1111 19 Street NW, Suite 800
rating of 15 minutes. According to Washington, D.C. 20036
Table 2, the studs have an (202) 463-4713
assigned time of 20 minutes. www.awc.org

COPYRIGHT 2004
American Forest & Paper Association, Inc.
2
Code Conforming Wood Design: Free Windows-based software providing summary of allowable wood uses, including height and area
requirements. Available at http://www.awc.org.

You might also like