You are on page 1of 4

Reiri DCPF04 Technical Data Sheet

Reiri for Office (Touchscreen Controller)


Model DCPF04
Power Supply 100-240 V, 50/60 Hz
Power Consumption Max. 11.8 W
Controller power input 5.0 V, 3.0A
Dimension (W x D x H) 272.2 x 36.1 x 181.6 mm
Weight 1.10 kg
Processor FreeScale iM X 6 (Cortex A9)
Memory 1GB
Display 10 Inch Touch Panel
Reiri for Office (Touchscreen Controller) is high performance smart controller that provides versatile smart solution
to office building and office space. It offers full control of Daikin air-conditioning system & other connected smart
devices with the dedicated touch panel.
Compatible air-conditioning system: VRV, RA, SA, PA
Highlight: Integrate air-conditioner with other devices, control, and program output for regular routine
Advance solution: Energy management with Smart Meter, IAQ monitoring with IAQ Multi sensor
Total Management point: 500
Communication module: 750-362,
750-862: for DALI, power measurement module
System module: 750-601; 750-602; 750-600; 750-613
753-620 (for DALI)
WAGO I/O
IO module
System
(Up to 10 nodes,
Di: 750-400,430,432,436,1405
each node up to Do: 750-504, 750-513, 750-513/000-001, 750-1504
64 modules Ai: 750-454, 455, 459, 479, 460, 460/000-003, 460/000-005,
LAN port x 1 including power 461, 461/000-003, 461/000-004, 461/000-005,461/020-000
supply and end
Ao: 750-554, 555, 559, 560
module)
Pulse counter module^: 750-638
DALI: 753-647 ^ Use with 750-362 only.
Not applicable with 750-862.
Power measurement: 750-495
Power Supply: 787-712; 787-1112
Connectivity Daikin Mobile Interface Adaptor (max. 50 modules):
Wi-Fi
(RA)BRP072B42, BRP072C42, (SA) BRP072C42-1
(up-to 256 indoor units with 4 adaptors) VRV series, HRV,
DCPA01 SA (with DTA102A52 or DTA112BA51),
RS485 port x 2
(Each port up to RA (with KRP928BB2S),
2 DCPA01) PA (with DTA107A55),
DIIIDi (DEC101A51), DIIIDio (DEC102A51)
DAMA Interface Adaptor (max. 20 modules) NetPro Dual Modbus Gateway
Smart Meter (up-to 30 smart meters): Schneider Smart Meters
[METSEPM5110, METSEPM5111*, METSEPM5310, METSEPM5330,
USB Port x 2 METSEPM5331*, METSEPM5350, METSEPM5560, METSEPM5561*,
(With USB- RS485
METSEPM5563, METSEPM5570, METSEPM5580, A9MEM3150, A9MEM3155*,
Converter)
A9MEM3250, A9MEM3255*] *Can be used for P.P.D. function as well
IAQ Sensor (up-to 30 IAQ sensors): Reiri (DCPE01S, DCPE02S)
PM2.5, CO2, Temperature, Humidity, TVOC monitoring

DHOS-CS-DS-21-002C
Page | 1
Reiri DCPF04 Technical Data Sheet

Standard Features
Control & monitoring History
Setpoint Range Operation Report
AC control
RC Prohibition Data Analysis Error Report
Setback Energy Graph
Schedule Trend Graph
Off timer Operation data
Automatic control Scene control Data Export Energy Data
Interlock Trend data
Automatic changeover Mobile app notification
Icon View Notification
Email Alert
Monitoring Screen
Layout View ※ Mobile app
Access
Web App
Optional Features
※ Engineering Optional Function
DCPN003 PPD Calculation
Tenant
P.P.D. & Tenant
Billing Management
Billing PPD Billing for VRV
DCPN004 Data
Real-time Energy Real Time Energy Display
Monitoring (R.E.M.)
Analysis

Product Dimension:

DHOS-CS-DS-21-002C
Page | 2
Reiri DCPF04 Technical Data Sheet

Wiring diagram:

Type of Communication Cable Type Cable Thickness Max. Distance


2
AWG 24 (0.25 mm ) to
Modbus Twisted pair cable 200 meters
AWG 18 (0.75mm2)
CAT 5/5e/6
LAN N.A. N.A.
(Connector Standard: RJ-45)

Note: Reiri Mobile App is available in iOS App Store and Google Play Store

DHOS-CS-DS-21-002C
Page | 3
Reiri DCPF04 Technical Data Sheet

Adaptor diagram:

Maximum Connection
Reiri for Office 1 adaptor 10 Outdoor Units 64 Indoor Units
RS485 Port 1
(Touchscreen Controller) 1 adaptor 10 Outdoor Units 64 Indoor Units
(DCPF04) 1 adaptor 10 Outdoor Units 64 Indoor Units
RS485 Port 2
1 adaptor 10 Outdoor Units 64 Indoor Units
Total 4 Adaptors 40 Outdoor Units 256 Indoor Units

DHOS-CS-DS-21-002C
Page | 4