6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 4
c Shape Stranded Circular
e Max. DC resistance at 20⁰C Ω/km 4.610
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 0.8
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 6
c Shape Stranded Circular
e Max. DC resistance at 20⁰C Ω/km 3.080
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 0.8
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 10
c Shape Stranded Circular
e Max. DC resistance at 20⁰C Ω/km 1.830
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 1.0
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 16
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 1.150
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 1.0
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 25
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 0.727
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 1.2
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 35
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 0.524
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 1.2
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 50
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 0.387
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 1.4
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 95
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 0.193
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 1.6
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 120
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 0.153
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 1.6
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 150
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 0.124
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 1.8
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 185
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 0.0991
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 2.0
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 240
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 0.0754
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 2.2
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 300
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 0.0601
7 Insulation
a Material PVC Type C
b Nominal Thickness mm 2.4
c Colour Yellow-Green
11 Printing
POWER PLUS CABLE CO.L.L.C. XX MM² CU/PVC 450/750 V IEC 60227-3 MADE IN U.A.E. 2015
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 630
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 0.0283
7 Insulation
a Material XLPE
b Nominal Thickness mm 2.4
9 Bedding
a Material PVC
b Minimum Thickness mm 0.76
10 Armour
a Material Aluminium Round Wire
b Nominal diameter mm 2.0
11 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.64
c Color Black
16 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/AWA/PVC
1C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 2.5
c Shape Stranded Circular
e Max. DC resistance at 20⁰C Ω/km 7.41
7 Insulation
a Material XLPE
b Nominal Thickness mm 0.7
10 Bedding
a Material PVC
b Minimum Thickness mm 0.6
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 0.9
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.24
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
3C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 2.5
c Shape Stranded Circular
e Max. DC resistance at 20⁰C Ω/km 7.41
7 Insulation
a Material XLPE
b Nominal Thickness mm 0.7
10 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.43
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC
3C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 4
c Shape Stranded Circular
e Max. DC resistance at 20⁰C Ω/km 4.61
7 Insulation
a Material XLPE
b Nominal Thickness mm 0.7
10 Bedding
a Material PVC
b Minimum Thickness mm 0.6
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 0.9
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.24
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
3C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 6
c Shape Stranded Circular
e Max. DC resistance at 20⁰C Ω/km 3.08
7 Insulation
a Material XLPE
b Nominal Thickness mm 0.7
10 Bedding
a Material PVC
b Minimum Thickness mm 0.6
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 0.9
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.24
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
3C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 16
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 1.15
7 Insulation
a Material XLPE
b Nominal Thickness mm 0.7
10 Bedding
a Material PVC
b Minimum Thickness mm 0.6
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 1.25
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.24
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
3C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 50
c Shape Stranded Shaped Compacted
e Max. DC resistance at 20⁰C Ω/km 0.387
7 Insulation
a Material XLPE
b Nominal Thickness mm 1.0
10 Bedding
a Material PVC
b Minimum Thickness mm 0.6
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 1.6
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.32
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
3C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 70
c Shape Stranded Shaped Compacted
e Max. DC resistance at 20⁰C Ω/km 0.268
7 Insulation
a Material XLPE
b Nominal Thickness mm 1.1
10 Bedding
a Material PVC
b Minimum Thickness mm 0.76
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 2.0
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.4
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
3C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 120
c Shape Stranded Shaped Compacted
e Max. DC resistance at 20⁰C Ω/km 0.153
7 Insulation
a Material XLPE
b Nominal Thickness mm 1.2
10 Bedding
a Material PVC
b Minimum Thickness mm 0.76
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 2.0
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.64
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
3C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 185
c Shape Stranded Shaped Compacted
e Max. DC resistance at 20⁰C Ω/km 0.0991
7 Insulation
a Material XLPE
b Nominal Thickness mm 1.6
10 Bedding
a Material PVC
b Minimum Thickness mm 0.92
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 2.5
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.88
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
3C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 240
c Shape Stranded Shaped Compacted
e Max. DC resistance at 20⁰C Ω/km 0.0754
7 Insulation
a Material XLPE
b Nominal Thickness mm 1.7
10 Bedding
a Material PVC
b Minimum Thickness mm 1.08
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 2.5
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 2.04
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
3C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 10
c Shape Stranded Circular
e Max. DC resistance at 20⁰C Ω/km 1.83
7 Insulation
a Material XLPE
b Nominal Thickness mm 0.7
10 Bedding
a Material PVC
b Minimum Thickness mm 0.6
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.24
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
4C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 16
c Shape Stranded Circular Compacted
e Max. DC resistance at 20⁰C Ω/km 1.15
7 Insulation
a Material XLPE
b Nominal Thickness mm 0.7
10 Bedding
a Material PVC
b Minimum Thickness mm 0.6
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 1.6
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.24
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
4C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 25
c Shape Stranded Shaped Compacted
e Max. DC resistance at 20⁰C Ω/km 0.727
7 Insulation
a Material XLPE
b Nominal Thickness mm 0.9
10 Bedding
a Material PVC
b Minimum Thickness mm 0.6
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 1.6
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.24
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
4C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 35
c Shape Stranded Shaped Compacted
e Max. DC resistance at 20⁰C Ω/km 0.524
7 Insulation
a Material XLPE
b Nominal Thickness mm 0.9
10 Bedding
a Material PVC
b Minimum Thickness mm 0.6
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 1.6
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.32
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
4C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 50
c Shape Stranded Shaped Compacted
e Max. DC resistance at 20⁰C Ω/km 0.387
7 Insulation
a Material XLPE
b Nominal Thickness mm 1.0
10 Bedding
a Material PVC
b Minimum Thickness mm 0.6
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 1.6
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.4
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
4C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 95
c Shape Stranded Shaped Compacted
e Max. DC resistance at 20⁰C Ω/km 0.193
7 Insulation
a Material XLPE
b Nominal Thickness mm 1.1
10 Bedding
a Material PVC
b Minimum Thickness mm 0.76
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 2.0
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.64
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
4C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 150
c Shape Stranded Shaped Compacted
e Max. DC resistance at 20⁰C Ω/km 0.124
7 Insulation
a Material XLPE
b Nominal Thickness mm 1.4
10 Bedding
a Material PVC
b Minimum Thickness mm 0.92
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 2.5
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 1.88
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
4C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 185
c Shape Stranded Shaped Compacted
e Max. DC resistance at 20⁰C Ω/km 0.0991
7 Insulation
a Material XLPE
b Nominal Thickness mm 1.6
10 Bedding
a Material PVC
b Minimum Thickness mm 0.92
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 2.5
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 2.04
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
4C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.
TECHNICAL DATA SHEET
6 Conductor
a Material Annealed Plain Copper
b Nominal Size mm² 300
c Shape Stranded Shaped Compacted
e Max. DC resistance at 20⁰C Ω/km 0.0601
7 Insulation
a Material XLPE
b Nominal Thickness mm 1.8
10 Bedding
a Material PVC
b Minimum Thickness mm 1.08
11 Armour
a Material Galvanised Steel Round Wire
b Nominal diameter mm 2.5
12 Over Sheath
a Material PVC Type ST2
b Minimum Thickness mm 2.36
c Color Black
17 Embossing
ELECTRIC CABLE 0.6/1(1.2) kV CU/XLPE/PVC/SWA/PVC
4C x XX SQ.MM IEC 60502-1 POWER PLUS CABLE Co. L.L.C. MADE IN UAE 2015
* Depth of Laying = 50 cm
* Thermal Resistivity of Soil = 1.20 K-m/W
TECHNICAL DEPT.