You are on page 1of 13

Technical Specification For Smart energy meters+cables 2023

ABC CABLE SPECIFICATION


1. DESIGN
1.1 GENERAL
The first part of the designation refers to the number and size (nominal cross sectional area) of the
phase conductor and the last part to size of the messenger.
The cable required should be compressed, stranded conductors of aluminium, with at least 6
strands.
The insulated messenger wire cable consists of three black, weather resistant, cross-linked
polyethylene insulated AAAC conductors twisted around an insulated aluminium alloy.
The cable shall have a symmetrical right hand lay with a length of lay of about 40 times the
diameter Do over the cores, laid up. In addition, the pitch of laying shall be such as to allow easy
separation of conductors when making connection but also maintain the bundle cohesion in line
angles.
The cable shall be rated for 600/1000V.
The cores shall be of the same length and lie close to each other.
The properties of individual cables and the bundle (such as lay pitch, Electrical and Mechanical
properties) shall conform to relevant Clauses in NFC 33-209.
1.2 ABC CONFIGURATIONS – SIZES

Type Phase conductor (mm2) Messenger (mm2)


4 3x25 25

4 3x35 35

4 3x50 50

1
Technical Specification For Smart energy meters+cables 2023

1.3 CONSTRUCTION OF CONDUCTORS


All conductors shall be constructed to IEC 61089. The properties of the Aluminium wires before
stranding shall be as below.

Tensile strength not less than 90 N/mm2


Resistivity at 20°C not exceeding 0.02845 ohm/mm²/m

The messenger, which is also the neutral conductor, takes all of the mechanical stresses.
1.4 MESSENGER (NEUTRAL CONDUCTOR):
The messenger shall be an All-Aluminium-Alloy conductor composed of wires drawn from rod,
which is manufactured in a continuous casting and rolling procedure. The properties for the
individual wires before stranding shall be

Tensile strength not less than 278 N/mm²


Resistivity at 20°C not exceeding 0.0328 ohm/mm²/m
Density at 20°C 2.7 kg/m³

No joints are allowed in the messenger except those made on the base rod or wire before final
drawing. The messenger shall be round, stranded and compacted to have smooth round surface.
The messenger takes all the mechanical stress and also serves as a neutral conductor.
In addition to the above the following specification shall apply:

1.5 INSULATION
The Insulating Material shall be of black weather resistant cross linked thermosetting polyethylene
(XLPE) conforming to NFC 32-020 and shall be suitable for climatic conditions of the country.
The mechanical strength and other mechanical properties such as tensile strength, minimum
elongation at break and physical/chemical properties shall conform to the relevant Clauses in NFC
32-020.

2
Technical Specification For Smart energy meters+cables 2023

The minimum tensile strength shall not be less than 14.5 Mpa and the minimum elongation at
break shall be 200%.
Adherence of the insulating sheath to the strain bearing neutral conductor shall be adequate
enough to prevent the slipping of the insulating sheath. The required adherence shall be achieved
by the use of paper material or other technique.
The insulating sheath shall be fully pressure extruded on the bare conductors of the phases / street
lamp / neutral messenger.

3
Technical Specification For Smart energy meters+cables 2023

Aerial Bundle Cable/Twisted bundle conductors 0.6/1 kV/

ABC 3* 25mm²+1*25mm²

Guaranteed value
Item No. Description Unit
Required Offered
1 Name of manufacturer
2 Country of manufacture
Year of manufacturer ----- 2023
3 Type ABC
4 Standard IEC60502
black extruded
5 Insulation
XLPE
I Cross section mm² 25
1 Rated voltage (phase/line) V 0.6/1
2 Maximum rated voltage V 0.44
3 One Minute voltage test KV 4
4 Impulse withstand Voltage 1.2/50Micro second KV 20
5 Current rating at 30°C A
6 Rated DC resistance at 20°C Ω/km 0.868
7 Core diameter mm 7
8 Inductive reactance Ω/km
9 Average insulatation thickness mm 1.4
10 Nominal diameter over insulation mm 9.8
11 Minimum breaking load KN 10.64
12 Length of cable per drum km
13 Gross weight of Cable Per drum Kg
14 Net weight of cable per drum Kg

4
Technical Specification For Smart energy meters+cables 2023

Aerial Bundle Cable/Twisted bundle conductors 0.6/1 kV/

ABC 3* 35mm²+1*35mm²

Guaranteed value
Item No. Description Unit
Required Offered
1 Name of manufacturer
2 Country of manufacture
Year of manufacturer ----- 2023
3 Type ABC
4 Standard IEC60502
black extruded
5 Insulation
XLPE
I Cross section mm² 35
1 Rated voltage (phase/line) V 0.6/1
2 Maximum rated voltage V 0.44
3 One Minute voltage test KV 4
4 Impulse withstand Voltage 1.2/50Micro second KV 20
5 Current rating at 30°C A Specify
6 Rated DC resistance at 20°C Ω/km Specify
7 Core diameter mm Specify
8 Inductive reactance Ω/km Specify
9 Average insulatation thickness mm Specify
10 Nominal diameter over insulation mm Specify
11 Minimum breaking load KN Specify
12 Length of cable per drum km Specify
13 Gross weight of Cable Per drum Kg Specify
14 Net weight of cable per drum Kg Specify

5
Technical Specification For Smart energy meters+cables 2023

Aerial Bundle Cable/Twisted bundle conductors 0.6/1 kV/

ABC 3* 50mm²+1*50mm²

Guaranteed value
Item No. Description Unit
Required Offered
1 Name of manufacturer
2 Country of manufacture
Year of manufacturer ----- 2023
3 Type ABC
4 Standard IEC60502
black extruded
5 Insulation
XLPE
I Cross section mm² 50
1 Rated voltage (phase/line) V 0.6/1
2 Maximum rated voltage V 0.44
3 One Minute voltage test KV 4
4 Impulse withstand Voltage 1.2/50Micro second KV 20
5 Current rating at 30°C A Specify
6 Rated DC resistance at 20°C Ω/km Specify
7 Core diameter mm Specify
8 Inductive reactance Ω/km Specify
9 Average insulatation thickness mm Specify
10 Nominal diameter over insulation mm Specify
11 Minimum breaking load KN Specify
12 Length of cable per drum km Specify
13 Gross weight of Cable Per drum Kg Specify
14 Net weight of cable per drum Kg Specify

6
Technical Specification For Smart energy meters+cables 2023

‫جدول الكميات‬

‫مالحظات‬ ‫الكمية‬ ‫الوحدة‬ ‫الصنف‬ ‫م‬


Smart energy meter .1
200 ‫عدد‬
)3 Ph , 90±20 A)
.2
200 ‫عدد‬ CB,MCB 63 A , 4 Pole

Meter Box ( Enclosure) .3


200 ‫عدد‬
‫ سم‬20*50*40 ‫صندوق عداد حديد‬
ABC Insulated Piercing Connector/
.4
1,000 ‫عدد‬ Clamp
‫ ) مم مسمار واحد‬50 – 25( ‫كونكتر ملس‬
Flexible round CU/ XLPE /PVC power cable 4 –
core,0.6/1KV, 90Co cupper .5
5000 ‫متر‬
2‫ مم‬16*4 ‫كابل نحاس فلكس‬
Non Flexible round CU/ XLPE /PVC power cable 4
–core,0.6/1KV, 90Co cupper .6
10000 ‫متر‬
2‫ مم‬16*4 ‫كابل نحاس صلب‬
.7
22000 ‫متر‬ ABC Cable 4*25mm2

.8
7000 ‫متر‬ ABC Cable 4*35mm2

.9
5000 ‫متر‬ ABC Cable 4*50mm2

7
Technical Specification For Smart energy meters+cables 2023

SMART ENERGY METER:


Scope of Supply
This specification covers the following for Three Phase 240 V, 20A-100A Static Watt hour smart
meters of accuracy class 1.0 with plug in communication modules (RF mesh only and RF +
Cellular technology) and integrated load control switches.
A. Design, manufacture, testing at manufacturer works before dispatch, packing, delivery and
submission of all documentation.
B. Any accessories / hardware required for installation and operation for the meter.

Smart energy meter required for measurement of active, active and reactive or active, reactive and apparent energy and
demand in three-phase four wire networks. It should be connected directly.
The meter can also be used in single phase two-wire networks. The meters must comply with both European (EN 50470-1 and
EN 50470-3) and international (IEC 62052-11 and IEC 62053-21) standards.
Calibration
Meter shall be software calibrated at factory and modification in calibration shall not be possible
at site by any means or external influence.
Limits of error due to influence quantities
Meter shall work within guaranteed accuracy as per IS 13779/
IEC62053-21/ CBIP325 (most stringent standard to be followed)
under and after influence of following :-
• Current Variation
• Ambient Temperature variation
• Voltage variation
• Frequency variation
• 10% third harmonic in current
• Reversed phase sequence
• Voltage unbalance

8
Technical Specification For Smart energy meters+cables 2023

• Harmonic components in current and voltage circuit


• DC and even harmonics in AC current circuit
• Odd harmonics in AC current circuit.
• Sub harmonics in AC current circuit
• Continuous (DC) “stray” magnetic induction of 67mT+/-
• 5%.
• Continuous (DC) “abnormal” magnetic induction of
• 0.27T+/-5%.
• Alternating (AC) “stray’ magnetic induction of 0.5mT+/-
• 5%
• Alternating (AC) “abnormal’ magnetic induction of
• 10mT.
• External magnetic field 0.5 T
• Electromagnetic HF fields
• Radio frequency interference
Main Properties

■ Fast and easy installation procedure, indications of correct connection


■ Multi-phasing connection (all-in-one: poly- and single-phase meter)
■ Universal current terminal for all types of conductors
■ Indications of meter operation status
■ Internal real time clock
■ Powerful load profile recorder .
■ Protection against water and dust: IP 54 at least.

Energy Measurement

9
Technical Specification For Smart energy meters+cables 2023

• Active, active and reactive or active, reactive and apparent energy


• Maximum demand and instantaneous power
• One or two energy flow directions or always positive registration
• Internal real time clock
• Measurement of phase voltages, currents, power factors and frequency
• Load profile registration.

Smart Energy Meter Box:

• General purpose type, suitable for relevant ambient conditions, flush or surface mounted as shown on
the comprising of box, trim and door to approved manufacturer’s standards and sizes.
• Box, trim and doors should be electro-galvanized steel sheet more than 1.5mm thickness according to
the standards.
• Inner and outer surfaces of cabinet/boxes, trims, doors etc, should be cleaned, phosphatized, chrome
passivated and treated with final thermosetting epoxy powder modified by polyester resins providing
high resistance with mechanical injury, heat, acids and alkalis solvents, grease, ageing, corrosion and
with standard grey color.
• The enclosure dimensions should be (W x D x H) = 400 x 200 500 mm.

10
Technical Specification For Smart energy meters+cables 2023

N
Item Unit Requirement Offered

1. Smart energy meter:


1.1 Model ------ Specify
1.2 Manufacturer ------ Specify
1.3 Country of Origin ------ Specify
1.4 Standard ------ European
1.5 Enclosure IP ------ 54
1.6
Dimension (L*W*D) : Mm Specify

Site Conditions:

Republic of Yemen
Site

Up to 2500 m above
Altitude
sea Level
Up to 95%
Relative humidity
Operation range: -10
Deg C to 55 Deg C Limit
range of operation: -25
Temperature
to 60 Deg C Limit range
of storage / transport : -
25 to 70 Deg C

Distribution System Data

3 Phase AC, 4 wire


Supply

415 V ± 6%
Voltage

50 Hz ± 5%
Frequency

11
Technical Specification For Smart energy meters+cables 2023

System Neutral Specify

Connection 3 Phase 3 Wires


3 Phase 4 Wires Direct / whole current

Voltage range Specify

Current range Specify

Freqency range Specify

Voltage overload Specify

Voltage accuracy class 1

Current overload Specify

Display LCD display

Power supply consumption Specify

Working environment Specify

1.7 Energy Measurement ------


1.7.1 Active, active and reactive or active,
Specify
reactive and apparent energy
1.7.2 Maximum demand and instantaneous
Specify
power
1.7.3 One or two energy flow directions or
Specify
always positive registration
1.7.4 Internal real time clock Specify
1.7.5 Measurement of phase voltages,
Specify
currents, power factors and frequency
1.7.6 Load profile registration. Specify

12
Technical Specification For Smart energy meters+cables 2023

2. Meter Box ( Enclosure)


2.1 Enclosure Model ------ Specify
2.2 Enclosure Manufacturer ------ Specify
2.3 Country of Origin ------ Specify
2.4 Standard ------ European
2.5 Enclosure IP ------ 54
2.6 Dimension (L*W*D) : Mm 500*400*200
2.7 Color ------ Grey
3.
Load Circuit Breaker

3.1 Type ------ MCB


3.2 No. of Poles 4
3.3 Manufactures ------ ------
3.4 Country Of Origin ------ ------
3.5 Model ------ ------
3.6 Number of Poles V 4Poles
3.7 Rated Capacity Current A 63
3.8 Breaking Capacity Current KA 16
3.9 MCB Type Class C
4. ABC Insulated Piercing Connector/
Clamp
4.1 Type ------ 1 Bolt
4.2 Manufactures ------ Specify
4.3 Country Of Origin ------ Specify
4.4 Model ------ Specify
4.4 Cable range Mm 25 ͠ 50
4.5 Applied Voltage V 1000

13