INSTALLING YOUR TRANSTECTOR


TRANSIENT VOLTAGE SUPPRESSION
PRODUCT

CDD 2/1/07

JAH 2/1/07
MLH 2/5/07
01 PRE-PRODUCTION 6/11/2001
B ADD SHEET 11 OF 11 FOR AUX RLY WIRING 6602

! IMPORTANT SAFETY INSTRUCTIONS !

Read and understand all instructions

! IMPORTANT!
THIS PRODUCT SHOULD ONLY BE INSTALLED BY TRAINED,
QUALIFIED PERSONNEL. TO AVOID SHOCK, ALWAYS
DISCONNECT POWER BEFORE SERVICING OR INSTALLING
THIS PRODUCT.

! SAVE THESE INSTRUCTIONS !


01 PRE-PRODUCTION 6/11/2001
B ADD SHEET 11 OF 11 FOR AUX RLY WIRING 6602

1.

AUXILIARY 20 AMP BREAKER

NEUTRAL BUSS

CABINET INSTALL
L1
L2
L3
NEUTRAL

MAIN BREAKER

L1
I2R
L2
L3
NEUTRAL

AUXILIARY 20 AMP BREAKER

NEUTRAL BUSS

1. ENCLOSURE INSTALL
NOTE: 1. LEADS TO BE CUT AS SHORT AS POSSIBLE.
R



N/A
01 PRE-PRODUCTION 6/11/2001
B ADD SHEET 11 OF 11 FOR AUX RLY WIRING 6602

FASTENER-MOUNT INSTALL
MAIN BREAKER

L1
L2
L3
NEUTRAL INSTALL WITH 6mm or 41"
FASTENERS, USE WASHERS
AUXILIARY 20 AMP BREAKER
AS SHOWN.

NEUTRAL BUSS

1.

6mm or 41" BOLT


(TORQUE TO 2.7 Nm or 24 inlb)

SPLIT-LOCK OR
STAR-LOCK WASHER
RECOMMENDED

FLAT WASHER
RECOMMENDED

NOTE: 1. LEADS TO BE CUT AS SHORT AS POSSIBLE.



N/A
01 PRE-PRODUCTION 6/11/2001
B ADD SHEET 11 OF 11 FOR AUX RLY WIRING 6602

SINGLE PHASE MODELS

L1 L1 L1 L1

SINGLE SINGLE
+ BACK UP

L2 L2 L2 WITH L2
WITHOUT WITH WITHOUT
RELAY
RELAY RELAY RELAY

WIRE RANGE MAX: 1-0 AWG (8.25MM)


120T/240 SPLIT
MIN: 14 AWG (1.63MM)
L1 L2
L2 L1
120T/240 SPLIT
+ BACK UP
L2
L1
L2 L1

N N
WITHOUT WITH
RELAY RELAY

N N

WITHOUT WITH
RELAY RELAY
R



N/A
01 PRE-PRODUCTION 6/11/2001
B ADD SHEET 11 OF 11 FOR AUX RLY WIRING 6602

THREE PHASE MODELS

L1 L3
L2 L2
L3 L1
3PHASE WYE
WITHOUT WITH
RELAY RELAY

N N
L3
L1
L2
L2
L1
L3

WITH
WITHOUT 3PHASE WYE RELAY
RELAY + BACKUP

N N
WIRE RANGE MAX: 1-0 AWG (8.25MM)
MIN: 14 AWG (1.63MM)
L1 L3
L2 L2
L3 L1

3PHASE DELTA

WITHOUT WITH
RELAY RELAY
R
R


01 PRE-PRODUCTION 6/11/2001
B ADD SHEET 11 OF 11 FOR AUX RLY WIRING 6602

COMMON MODE MODEL WIRING

L1 L1

WITHOUT WITH
SINGLE
RELAY + COMMON MODE RELAY

GND L2
L2 GND
WITHOUT WITH
RELAY RELAY
L1 L2
L2 L1

WITHOUT 120T/240 SPLIT WITH


RELAY RELAY
+ COMMON MODE

GND N
N GND
L1 WIRE RANGE MAX: 1-0 AWG (8.25MM) L2
L2 MIN: 14 AWG (1.63MM) L1

120T/240 SPLIT
+ BACK UP
+ COMMON MODE

GND N
N GND



N/A
01 PRE-PRODUCTION 6/11/2001
B ADD SHEET 11 OF 11 FOR AUX RLY WIRING 6602

COMMON MODE MODEL WIRING


L1 L3
L2 L2
L3 L1

3 PHASE WYE
+ COMMON MODE

GND
N
N
GND
WITHOUT WITH
RELAY RELAY

WIRE RANGE MAX: 1-0 AWG (8.25MM)


MIN: 14 AWG (1.63MM)
L3
L1 L2
L2
L1
L3
3 PHASE WYE
+ BACK UP
+ COMMON MODE

GND N
N GND

WITHOUT WITH
RELAY RELAY


01 PRE-PRODUCTION 6/11/2001
B ADD SHEET 11 OF 11 FOR AUX RLY WIRING 6602

COMMON

PLUG-IN SUPPRESSION NORMALLY


RELAY MODULE
MODULES AS SHOWN. CLOSED
CONTACTS
NOTE THEY CAN ONLY NORMALLY
BE INSTALLED ONE WAY. OPEN
ALL PRIMARY MODULES MUST
BE INSTALLED AND WORKING
FOR RELAY MODULE TO
FUNCTION NOTE: CONTACTS
CHANGE
STATE WITH
LABEL SIDE OUT LOSS OF POWER

L1 L2 L3

RELAY CONTACTS

NEUTRAL



N/A
01 PRE-PRODUCTION 6/11/2001
B ADD SHEET 11 OF 11 FOR AUX RLY WIRING 6602

POWER ON POWER OFF -OR-


PRIMARY MODULES OK PRIMARY MODULE FAIL

RELAY CONTACTS PROVIDE 3000 VAC ISOLATION


RELAY CONTACTS ARE RATED FOR 3AMPS 30VDC -OR- 3AMPS 220VAC
RELAY CONTACTS DO NOT MONITOR BACK UP OR COMMON MODE MODULES
RELAY CONNECTOR ACCEPTS 0.5MM to 1.6MM (28 TO 14 AWG) WIRE

PRIMARY MODULES
(MONITORED)

NOT MONITORED BY RELAY



N/A
01 PRE-PRODUCTION 6/11/2001
B ADD SHEET 11 OF 11 FOR AUX RLY WIRING 6602

FOR I2R 120T/MOV W/ENCL/AUX RELAY (1101-814)

DIAGRAM FOR MONITORING TWO RELAYS WITH ONE PAIR OF


RELAY WIRES

JUMPER COIL DE-ENERGIZED COIL ENERGIZED


14
14 NO
14
NO 11
11 A1 12 11
C NO RELAY NC C
C JUMPER
ALARM WIRES A2 JUMPER 12
NC 12 NC
11 14 A1 12 ALARM WIRES 14
C NO NC ALARM WIRES 14
11 NO
RELAY NO
A2 11
C
C 12
NC 12 NC

FOR MONITORING OPEN CONTACT UPON POWER LOSS FOR MONITORING OPEN CONTACT UPON POWER LOSS

COIL DE-ENERGIZED COIL ENERGIZED


14
NO
14
JUMPER JUMPER 11 NO 11

11 14 A1 12 JUMPER C 12 JUMPER C
C 12
NC
RELAY NC
A2 NO JUMPER NO
14 14 JUMPER
ALARM WIRES 11 14 A1 12 11 11
C RELAY
C C
A2 12 12
NC ALARM WIRES NC
ALARM WIRES

FOR MONITORING CLOSED CONTACT UPON POWER LOSS FOR MONITORING CLOSED CONTACT UPON POWER LOSS

CDD 2/1/01

JAH 2/1/01
MLH 2/5/01
N/A

©2015 Transtector. All rights reserved