You are on page 1of 2

Multicore LV Armoured Cables (Kahramaa)

4C x 35Sq.mm

Nexans Ref.: 24035EXZZDB09BA3

Multicore LV Armoured Cables (Kahramaa)

DESCRIPTION
Scope

This specification covers multi-core, XLPE insulated cables for use on the
KAHRAMMA low voltage Distribution System . These cables are complying with IEC
60502-1 and Kahramaa Standard specification No.EP-MS-P4/S3-040 issue : 3

Design

1. Conductor

Plain annealed high-conductivity Stranded ,Compacted Copper Class 2 conforming to STANDARDS


IEC 60228.
International IEC 60332-1;
2. Insulation IEC 60502-1
Extruded XLPE conforming to IEC 60502-1.

3.Innersheathing or Bedding

Extruded PVC suitable for the operating conditions and conforming to IEC 60502-1

5. Armour

Single layer of Galvanized Steel Wire Armour (SWA) + Tinned Copper Wires (TCWA)
with Non-conducting Water Blocking Tape above and below the armour layer The
conductivity of the copper wires alone is at least 50% of that of any phase conductor,
at their respective normal working temperatures.

6. Outer Sheath

Polyvinyl Chloride 'PVC' Type ST2

- Flame retardant : IEC60332-1

- Colour : Black

Marking

KAHRAMAA 600/1000V LV XLPE 4 X 35Sq. mm² IEC 60502-1 MADE IN QATAR


QICC-Nexans Years Meters

Conductor flexibility Rated Voltage Uo/U (Um) Mechanical resistance to impacts Max.conductor temp.in service Flame retardant Bending factor installed
Stranded class 2 0.6/1 kV - 90 °C Yes 15 (xD)

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/11/22 www.nexans.qa Page 1 / 2
Multicore LV Armoured Cables (Kahramaa)
4C x 35Sq.mm

CHARACTERISTICS
Construction characteristics
Conductor material Copper
Conductor flexibility Stranded class 2
Conductor shape Circular
Insulation XLPE (Cross-linked Polyethylene)
Inner sheath PVC
Armour type Galvanized steel wire + tin copper wire
Outer sheath PVC
Colour Black
Core identification Red,Yellow,Blue,Black
Dimensional characteristics
Number of cores 4
Conductor cross-section 35 mm²
Approximate weight 2500 kg/km
Nominal outer diameter 30.5 mm
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV
Max. DC resistance of the conductor at 20°C 0.524 Ohm/km
Permissible current rating in open air 141 A
Permissible current rating when buried 110 A
Mechanical characteristics
Mechanical resistance to impacts -
Usage characteristics
Max. conductor temperature in service 90 °C
Short-circuit max. conductor temperature 250 °C
Flame retardant Yes
Ambient air temperature 45 °C
Ambient ground temperature 35 °C
Bending factor when installed 15 (xD)
Max. pulling force during laying 50 N/mm2

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/11/22 www.nexans.qa Page 2 / 2