YXC7V-A 20.3/35 kV Sales & Marketing


YXC7V-A 1X95 mm2 Phone: +90 212 266 0160
alper.altinok@nexans.com

International Designation: NA2XSY


Country Ref.: TR

20,3/35 kV XLPE insulated single core cables with aluminium conductor

DESCRIPTION
Application:
These are cables with low dielectric losses used in energy network with sudden load
changes. Laid in residental or industrial areas, underground or in ducts.

Construction:
1. Conductor:Copper
2. Conductor screen:Semiconducting compound(XLPE)
3. Insulation:XLPE
4. Insulation screen:Semiconducting compound(XLPE)
5. Semiconducting tape:Crape tape
6. Metallic screen:Concentric/Copper wires+copper tape
7. Outer sheath:PVC

CHARACTERISTICS
Construction characteristics
Conductor material Aluminum
Conductor shape Circular compacted
Material of the inner semi­conductor XLPE
Insulation XLPE (Cross­linked Polyethylene)
Material of the external semi­conductor XLPE
Screen Copper wire + copper tape
Outer sheath PVC
Sheath colour Red
Dimensional characteristics
Number of cores 1
Conductor cross­section 95 mm²
Nominal outer diameter 38.0 mm
Approximate weight 1500 kg/km
Delivery reel size for 1000m ­ cm

Rated Voltage Uo/U (Um) Operating temp. Flame retardant Bending factor when laying Max.conductor temp.in service


20.3 / 35 kV -20 - 60 °C IEC 60332-1-2 12 (xD) 90 °C

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/6/21 www.nexans.com.tr Page 1 / 2
Contact
YXC7V-A 20.3/35 kV Sales & Marketing
YXC7V-A 1X95 mm2 Phone: +90 212 266 0160
alper.altinok@nexans.com

Dimensional characteristics
Screen section 16 mm²
Electrical characteristics
Rated Voltage Uo/U (Um) 20.3 / 35 kV
Max. DC resistance of the conductor at 20°C 0.32 Ohm/km
Approx. inductance, at formation 0.61 mH/km
Approx. inductance, trefoil formation 0.43 mH/km
Nominal phase capacitance 0.14 µF / km
Perm. current rating buried 20°C ­ at formation 229 A
Perm. current rating buried 20°C ­ trefoil formation 221 A
Perm. current rating in air 30°C ­ at formation 338 A
Perm. current rating in air 30°C ­ trefoil formation 280 A
Permissible short circuit current conductor 1s 8.9 kA
Permissible short circuit current screen 1s 2.08 kA
Usage characteristics
Operating temperature, range ­20 ­ 60 °C
Short­circuit max. conductor temperature 250 °C
Flame retardant IEC 60332­1­2
Bending factor when laying 12 (xD)
Max. conductor temperature in service 90 °C

SELLING AND DELIVERY INFORMATION


Marking
TSEK NEXANS YXC7V­R 1 X 70/16 20,3/35 kV 2009 (Meter)

Rated Voltage Uo/U (Um) Operating temp. Flame retardant Bending factor when laying Max.conductor temp.in service


20.3 / 35 kV -20 - 60 °C IEC 60332-1-2 12 (xD) 90 °C

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 9/6/21 www.nexans.com.tr Page 2 / 2