T.L. = 10.32 KVA T.L. = 4.19 KVA T.L. = 4.19 KVA T.L. = 3.61 KVA T.L. = 3.

KVA T.L. = 3.61 KVA T.L. = 3.61 KVA T.L. = 3.61 KVA T.L. = 3.61 KVA T.L. = 10.17 KVA T.L. = 2.92 KVA T.L. = 2.92 KVA T.L. = 2.92 KVA T.L. = 3.49 KVA T.L. = 3.49 KVA
D.L. = 8.26KVA D.L. = 3.35KVA D.L. = 3.35KVA D.L. = 2.89 KVA D.L. = 2.89 KVA D.L. = 2.89 KVA D.L. = 2.89 KVA D.L. = 8.13 KVA D.L. = 2.33 KVA D.L. = 2.33 KVA D.L. = 2.33 KVA D.L. = 2.79 KVA D.L. = 2.79 KVA
IN OFF-301 IN OFF-302 IN OFF-303 IN OFF-304 IN OFF-305 IN OFF-306 IN OFF-307 IN OFF-308 IN OFF-309 IN OFF-310 IN OFF-311 IN OFF-312 IN OFF-313
AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR

40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO.

2
4Cx16mm CU/PVC/PVC
2
+ 1Cx16mm CU/PVC/ECC SPARE

FOR OFF-301 FOR OFF-302 FOR OFF-303 FOR OFF-305 FOR OFF-306 FOR OFF-307 FOR OFF-310 FOR OFF-311 FOR OFF-312 FOR OFF-313 Note:-
FOR OFF-304 FOR OFF-308 FOR OFF-309
1- * WIRED AS SINGLE PHASE.
HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0
HWK 0000.0

2- THE CONTRACTOR SHALL VERIFY THE FINAL LOADS IN COORDINATION WITH OTHER
TRADES. ACCORDINGLY FINAL SIZES OF CABLES AND CIRCUIT BREAKERS SHALL
BE ADJUSTED.
3- ALL CIRCUIT BREAKER RATINGS SHOWN ON DRAWING ARE PRESENTING THE THERMAL
TRIP SETTING AND FRAME SIZE. CIRCUIT BREAKERS RATED 100A AND ABOVE SHALL BE
EQUIPPED WITH ADJUSTABLE TRIP SETTING.

4- THE CONTRACTOR SHALL SUBMIT THE FOLLOWING CALCULATIONS AND STUDIES


FOR APPROVAL :

40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP - LOAD SCHEDULES FOR ALL DISTRIBUTION BOARDS FOR RETAILS AND
AND SERVICES (IF ANY CHANGES)
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB - CABLE SIZING AND VOLTAGE DROP CALCULATIONS (IF ANY CHANGES)
- SHORT CIRCUIT CALCULATIONS AT EACH BUS (IF ANY CHANGES)
18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA - DISCRIMINATION STUDY & CIRCUIT BREAKERS SETTING VALUES
OBTAINED FROM THE MANUFACTURER.

100A TP
MCCB
18 KA

2 2

T.L. = 3.49 KVA T.L. = 3.49 KVA T.L. = 4.38 KVA T.L. = 5.54 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 6.1 KVA T.L. = 4.82 KVA
D.L. = 2.79 KVA D.L. = 2.79 KVA D.L. = 3.5 KVA D.L. = 4.43 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 4.88 KVA D.L. = 3.86 KVA
IN OFF-314 IN OFF-315 IN OFF-316 IN OFF-317 IN OFF-318 IN OFF-319 IN OFF-320 IN OFF-321 IN OFF-322 IN OFF-323 IN OFF-324 IN OFF-325 IN OFF-326
AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR AT THIRD FLOOR

40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO.

2
4Cx16mm CU/PVC/PVC
2
+ 1Cx16mm CU/PVC/ECC SPARE

FOR OFF-314 FOR OFF-315 FOR OFF-316 FOR OFF-317 FOR OFF-318 FOR OFF-319 FOR OFF-320 FOR OFF-321 FOR OFF-322 FOR OFF-323 FOR OFF-324 FOR OFF-325 FOR OFF-326
HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0
HWK 0000.0

40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA

100A TP
MCCB
18 KA

SMDB-TH-OFF1 SMDB-TH-OFF2 SMDB-TH-OFF3


2 2 IN ELEC. RM IN ELEC. RM IN ELEC. RM
AT THIRD FL AT THIRD FL AT THIRD FL
LIGHTING, S.POWER LIGHTING, S.POWER LIGHTING, S.POWER

2 SPARE

2 For Tender

T.L. = 3.58 KVA T.L. = 3.58 KVA T.L. = 3.58 KVA T.L. = 3.58 KVA T.L. = 3.58 KVA T.L. = 3.58 KVA T.L. = 3.58 KVA T.L. = 3.00 KVA T.L. = 3.01 KVA T.L. = 3.00 KVA T.L. = 3.01 KVA T.L. = 2.96 KVA
D.L. = 2.86 KVA D.L. = 2.86 KVA D.L. = 2.86 KVA D.L. = 2.86 KVA D.L. = 2.86 KVA D.L. = 2.86 KVA D.L. = 2.86 KVA D.L. = 2.4 KVA D.L. = 2.40 KVA D.L. = 2.40 KVA D.L. = 2.40 KVA D.L. = 2.37 KVA
IN OFF-327
AT THIRD FLOOR
IN OFF-328
AT THIRD FLOOR
IN OFF-329
AT THIRD FLOOR
IN OFF-330
AT THIRD FLOOR
IN OFF-331
AT THIRD FLOOR
IN OFF-332
AT THIRD FLOOR
IN OFF-333
AT THIRD FLOOR
IN OFF-334
AT THIRD FLOOR
IN OFF-335
AT THIRD FLOOR
IN OFF-336
AT THIRD FLOOR
IN OFF-337
AT THIRD FLOOR
IN OFF-338
AT THIRD FLOOR So a 2 O ICE BUILDING

40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 100A TP 100A TP 80A TP 100A TP
MCCB MCCB MCCB MCCB 24B. -

25 KA 25 KA 25 KA 25 KA
2
4Cx16mm CU/PVC/PVC
2
+ 1Cx16mm CU/PVC/ECC SPARE SPACE
250A TP MOBIL :01024440717
E-MAIL : m.amer@mod-eg.com
MCCB WEB SITE : WWW.mod-eg.com
25 KA 26 JULY CORRIDOR
AVENUE MALL, SHEIKH ZAYED, GIZA, EGYPT

FOR OFF-327 FOR OFF-328 FOR OFF-329 FOR OFF-330 FOR OFF-331 FOR OFF-332 FOR OFF-333 FOR OFF-334 FOR OFF-335 FOR OFF-336 FOR OFF-337 FOR OFF-338
HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0

2 2

40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA

80A TP
MCCB
18 KA

2 2

---- ---- N.T.S @ A1

REV-01 SLD-03