tipped steel chairs. 2mm clearance unless noted otherwise. AS 3700.

GENERAL FOOTING 9. Curing of the concrete shall be carried out 10. All bolts, nuts and washers are to be 6. Non load bearing walls are to be kept TIMBER
1. Thesedrawnigsshalbereadni 1. The footings have been designed for a by keeping surfaces continuously wet for a hot dip galvanised in accordance with 20mm clear of the soffit of the slab and1. All workmanship and materials are to be
conujncotinwthialrchteictural maximum allowable bearing capacity of period of 7 days. The use of a plastic AS/NZS 4680 unless noted otherwise. beams. The 20mm gap is to be filled with in accordance with AS 1684, AS1720 and
drawnigsandother min. 500kPa to ROCK. Assumed Class M in sheeting and/or hessian placed over the 11. The ends of all hollow steel members are approved compressible filler and sealant. AS 3959.
consutlants drawnigsandspecfaciotins. accordance with AS2870. The soil concrete surface and held down firmly is to be sealed with 5mm thick end plates The filler and sealant are to provide the
2. All members are to be H2 or T2 treated
Aldsicrepanecisshalbereferedto conditions and bearing capacity of the recommended for aid in curing concrete welded all around unless noted otherwise. appropriate fire rating if required. unless noted otherwise.
thearchteictand/orengnieerporito foundations are to be confirmed by a surfaces where no floor finishes are 12. All gusset, fin and end plates are to be 7. The tops of non load bearing masonry 3. All external above ground members are
proceednigwthianywork. geotechnical engineer prior to works proposed. 10mm thick welded all around unless walls are to be supported by appropriate
2. Dmiensoinsshalnotbeobtaniedby commencing on site. 10. All conduits in slabs shall not be placed noted otherwise. ties which allow vertical movement but to be H3 treated unless noted
scnaiglthesedrawnigs. 2. In all locations where excavated surfaces within the zone of the clear concrete cover 13. Fillet welds shall be full length do not allow lateral movement. The ties otherwise.
Aldmiensoinsshownonthese become softened by exposure to the to the steel reinforcement. Conduits shall continuous welds, denoted CFW on the shall be placed at a maximum of 800mm 4. All external and in ground member are
drawnigsarenmim
ileitresunelss weather or by ground water seepage, be placed above the bottom reinforcement drawings. The size of the fillet weld centres. to be H5 treated unless noted
notedotherwsieA .elveslshown the footing shall be further excavated and below the top reinforcement. Any refers to the leg size of the weld. All 8. Masonry wall ties shall be provided in otherwise.
arenimetres. to reach a bearing capacity as specified conduits larger than 25 mm in diameter fillet welds are to be 6mm unless noted accordance with AS 3700. 5. All holes for bolts to be a snug fit.
3. Alworkmanshpiandmatearsilshalbe in 1 and as approved by the geotechnical shall not be placed in the concrete element otherwise. 9. Dry pressed masonry only to be used Washers are to be provided under all
niacordancewthithecurentSAA engineer. without the prior approval from the 14. Butt welds shall be complete penetration for retaining walls, not extruded. bolts and nuts and to be a minimum of
codesandbyalwso,rdniancesorother 3. All top soil and soil containing organic engineer. full length continuous welds denoted 10. Two layers of approved graphite greased 2.5 times the diameter of the bolt
requreimentsoftherelvantbdnulig matter shall be removed from the area 11. Stripping of formwork and back propping of CPBW on the drawings. metal based slip joint material is to be unless noted otherwise.
authoetris. of proposed slab on ground and a soffits shall not take place until concrete 15. Prior to the fabrication of structural provided between load bearing brick
minimum 30mm layer of compacted sand is has reached 75% of the specified 28 day steel work, two (2) copies of shop walls and the underside of concrete 6. All bolted connections to be 2M16 bolts
4. Unelssnotedotherwsiew ,aterproonfig
ofalelmentsitherespotnyisbloif to be provided under a waterproof characteristic compressive strength. drawings shall be submitted to the slabs and beams. The slip joint is to be unless noted otherwise.
thearchteictandtobeniacordance membrane. 12. 'N' denotes deformed bars, grade D500N engineer for review and approval. placed on smooth brickwork or a smooth 7. All bolts, nails, clouts and screws are
wthithearchteicst'andmanufacturesr' 'S' denotes deformed bars, grade 250S Fabrication shall not commence without trowelled mortar finish. to be hot dip galvanised in accordance
specfaciotin. CONCRETE 'R' denotes round bars, grade 250R written approval from the engineer. 11. The cores of all concrete block work are with AS 4680.
5. Dunrigthecourseofconstrucotinthe 1. All materials and workmanship is to be in 'SL' denotes square mesh, grade 500L 16. All structural steel work to be encased to be filled with 32MPa concrete U.N.O.,8. All cut ends of members are to be
contractorshalberesponsbeilfor accordance with AS 3600. 13. All reinforcement shall be in accordance in concrete is to be hot dip galvanised in of 10mm aggregate and 230mm slump. The treated to achieve the required hazard
manitanigthestructureniastabel 2. Concrete quality shall be as shown below with AS 4671. accordance with AS/NZS 4680 unless concrete is to be compacted and protection level.
conodtinandforensunrigthatnopart unless otherwise noted on the drawings: 14. N12-200 4N24 noted otherwise. mechanically vibrated during placement. 9. All hold downs to roof, wall and floor
ofthestructuresiover-stressed. Element Max. Slump Aggregate Concrete 17. Protective coatings and surface 12. Clean out holes are to be provided at framing to be in accordance with AS
6. Temporarybrancigandshonrigshalbe (mm) Size (mm) Grade (MPa) SPACING (mm) BAR SIZE (mm) treatments shall be as follows: the base of all cores. Care shall be
taken to ensure that the internal cores 1684.
provdiedbythecontractortoensure Footings 80 20 25 BAR SIZE (mm) REINFORCEMENT
thatthestructureandexcavaotinsare Element Surface Protective and clean out holes are clean and free FOUNDATION & FILLING
Core Fill REINFORCEMENT GRADE
stabelatam ltiesF.oraltemporary 80 20 25 location Preparation Coating or from any mortar prior to grouting. 1. Strip topsoil & pther organic matter to
Brick Pier GRADE NUMBER OF BARS in accordance Treatment a depth of 100mm & stockpile.
excavaotinbaterst,hecontractorsi with AS 1627 13. The vertical reinforcement is to be
toobtanigeotechncailadvcei. Ground Floor 80 20 32 15. Reinforcement shown on the drawings is 2. Fill used to support the slab shall be
accurately placed and tied to the starter
7. Nopenetraotinsh,oelsorchasesshal Slab represented diagrammatically, and is not Hand or Two coats (2) of bars at the clean out holes. The vertical rolled fill or controlled fill as follows:
necessarily shown in its true projection. Internal reinforcement is to be placed and tied
bemadethroughthestructural Garage Slab 80 20 32 power tool inorganic zinc (a). Rolled fill consist of material
elmentswthioutthewtrienapproval 16. Welding of reinforcement shall not be cleaned to silicate primer off to the horizontal reinforcement as compacted in layers by repeated
fromtheengnieer. Ground Floor 80 20 32 permitted unless shown on the drawings. minimum DFT 70 microns courses are laid to ensure that the
Class 2 rolling with an excavator or similar
8. DesginvieloladsniacordancewthiAS Slab 17. Splices in the reinforcement shall only be location of the vertical reinforcement is equipment. The depth shall not exceed
1701a.sfolws: made in locations as shown on the drawings. External -not Blast clean Hot dip maintained during grouting.
Column 80 20 40 18. requiring to minimum galvanised in 14. The minimum cover to all reinforcement 600mmm compacted in layers not more
All cogs to be standard cogs unless noted painting and Class 2.5 accordance
Area Type LvieLoadkPa otherwise. from the internal face of the concrete than 300mm thick for sand or 300mm
more than with AS/NZS
General 51. 3. Clear concrete cover to reinforcement shall 19. All reinforcement laps to be as follows 3km from sea 4680 block shall be 20mm unless noted compacted in layers not more than
Balcony 2 be as follows, unless noted otherwise: unless noted otherwise: water otherwise. 150mm for other material.
Garage 25. External - Refer to 15. The maximum pour height for (b). Controlled fill shall be placed, tested
Element Interior Exterior Cast against Reinforcement N12 N16 N20 N24 N28 N32 N36 requiring architect and unrestrained block work is to be 2000mm. & certifierd by a qualified geotechnical
ground Bar painting and/ paint
9. Thefolwnigabbrevaoitnsdenote: Lap Length 500 650 800 1000 1150 1300 1450 or less than manufacturer for 16. All concrete blocks used are to be of engineer as defined in AS3798. This is
Strip Footing N/A N/A 50 3km from sea the Double U type.
ARCH - Architect (mm) specifications. deemed to be adequate to support the
Pad Footing N/A N/A 50 water 17. Waterproofing and drainage to the back footing.
BEL - Bulk Excavation Level
BL - Boundary Line Pier N/A N/A 50 20. Fabric reinforcement is to be lapped 300mm of retaining walls is to be provided in 10. Where fill consists of reactive clay, the
CL - Centre Line Column N/A at ends and sides unless noted otherwise. 18. All paint specifications listed in 17 are to accordance with the architect and other fill shall be placed in a moist condition.
40 45 be applied in strict accordance with the consultants specifications.
COS - Confirm on Site Wall 25 45 N/A 11. Any fill shall continue past the edge of
DPM - Damp Proof Membrane STRUCTURAL STEEL manufacturers recommendations and 18. Reinforced concrete block work retaining
Beam 25 45 N/A 1. All structural steel work is to be in specifications. walls shall not be backfilled until 14 the building by at least 1m & shall be
EF - Each Face retained or battered beyond this point
EW - Each Way Slab 25 45 50 accordance with AS 4100. 19. Hot dip galvanised steel work that is site days after the wall has been grouted, or
2. All welding is to be in accordance with welded or sustains any other type of if applicable, until after the slab over by a slope not steeper than 1:2.
EX - Existing 4. The concrete shall be tested for 12. Except for sites with aggresive soil, a
FGL - Finished Ground Level AS/NZS 1554 damage is to be prepared to a Class 3 the retaining wall has been poured and
compliance in accordance with AS 3600. 3. All hot rolled structural steel sections are standard and painted with two (2) coats cured for 7 days. building is not required. where used, the
FSL - Finished Surface Level Test results are to be submitted to the
INV - Invert to be grade 300PLUS and in accordance with of zinc rich paint. building layer of snad shall comply with
engineer for review and approval. AS/NZS 3679. EXCAVATION rolled fill requirements.
NGL - Natural Ground Level 5. The sizes of concrete elements do not
SW - Stormwater 4. All rectangular hollow sections (RHS) are to MASONRY 1. Temporary excavations in the area of DAMP PROOFING MEMBRANE
include the thickness of finishes. be grade C350L0 in accordance with AS 1163. 1. All masonry work is to be in accordance the footing shall be carried out only
TBA - To Be Advised 6. Construction joints other than those 1. A 0.2mm min. polyethylene damp-proofing
U.N.O - Unless Noted Otherwise 5. All square hollow sections (SHS) are to be with AS 3700. where adequate support for the footing high impact resistant membrane shall be
specified on the drawings shall not be grade C350L0 in accordance with AS 1163. 2. All bricks to have a minimum compressive system is maintained such as piering
WPM - Water Proof Membrane made without approval from the engineer. placed beneath the slab so that the
6. All circular hollow sections (CHS) are to strength of 20MPa. beneath the expected excavation level or
10. Counlacind/orPCAApprovalforal 7. Beam depths are written first and include grade C250L0 and grade C350L0 as 3. All concrete blocks to have a minimum underpinning. bottom surface is entirely underlaid and
Workscontaniednithefolwnig the slab thickness, if any. applicable to their size in accordance with compressive strength of 15MPa. 2. Permannet excavations of any vertical or terminate at ground level.
drawnigsitobeobtaniedporito 8. Cover to all reinforcement, as specified in AS1163. 4. Masonry shall not be constructed on near vertical structure within 2m of the 2. The membrane shall be branded
commencementofconstrucotin. 3 or otherwise shown on the drawings, 7. All bolts shall be high strength structural suspended concrete slabs and beams until building & differ than 0.6m in the continuously 'AS2870 concrete underlay,
shall be provided and maintained during the bolts, grade 8.8 unless noted otherwise. all formwork and back propping is material other than rock shall be 0.2mm high impact resistance', together
concrete pour by the use of bar chairs. 8. All bolts are to be M16 and a minimum of removed. adequately retained or battered. with manufacturer or distrubutors name,
The bar chairs are to be at a maximum of two (2) bolts per connection unless noted 5. Vertical expansion and/or articulation 3. Excavations shall not extend below a line trademark or code.
750mm centres in both directions. Bar otherwise. joints shall be provided in all brickwork drawn at 30 degree for the sand & 45 3. Lapping shall be 200mm at joints and
chairs are to be either plastic or plastic 9. All bolt holes are to have a minimum of and block work walls in accordance with degree for the clay to the horizontal
tipped steel chairs. taped or sealed at plumbing
2mm clearance unless noted otherwise. AS 3700. from the bottom edge of the penetrations with continuous close
footing/pier without prior consent.
fitting sleeve or made continuous with
the vapour barrier.
STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY GENERAL NOTES - 1
REV. DATE REVISION DESCRIPTION BY A S0001
PILLING NOTES
1. Piles are to be designed in accordance with AS2159 by the LEVEL BEING FORMED LEVEL BEING FORMED
Contractor for the axial loads and moments listed in the
piling schedule and all requirements of the specification.
2. Any additional geotechnical investigation work deemed
necessary shall be at the Contractor's expense.
3. Pile spacing and pile cap design is based on [600 diameter FULLY FORMED FULLY FORMED
grout injected auger piles]. Alternative pile systems may be
used subject to approval. Any necessary re-design of pile
caps to suit alternative systems shall be at the expense
LEVEL CONSTRUCTED AND POURED LEVEL CONSTRUCTED AND POURED
of the Contractor. For single piles under columns the
GAINED FULL STRENGTH
minimum pile diameter shall be [600mm].
4. All piles or pile groups are to be centred under columns
and wall U.N.O. PROVIDED THIS LEVEL HAS ACHIEVED ITS
FULL STRENGTH & IS FULLY GROUTED
5. Prior to commencing on site, the Contractor must submit for 100% BACKPROPPING
approval:
(a) pile type proposed
(b) pile size (s), reinforcement details, founding 50% BACKPROPPING
depths and desiign certificate. The design LEVEL CONSTRUCTED AND POURED LEVEL CONSTRUCTED AND POURED
certificate is to certify the pile design is in GAINED FULL STRENGTH GAINED FULL STRENGTH
accordance with AS2159 for the loads listed
in the piling schedule and be signed by a
NPER registered engineer experienced in
the type of piling proposed.
(c) a shop drawing setting out all pile locations
from the grid 50% BACKPROPPING 50% BACKPROPPING
6. The Contractor is to coordinate the location of all
underground services and to be responsible for ensuring LEVEL CONSTRUCTED AND POURED LEVEL CONSTRUCTED AND POURED
that these are either avoided or relocated as appropriate. GAINED FULL STRENGTH GAINED FULL STRENGTH
7. The Contractor shall provide a NPER registered engineer to
supervise the pile installation. TYPICAL BACK PROPPING SEQUENCE
TYPICAL BACK PROPPING SEQUENCE FOR REINFORCED CONCRETE SLABS FOR POST TENSIONED CONCRETE SLABS
8. At the satisfactory completion of the work the Contractor
shall provide an inspection certificate signed by a NPER (PROVIDED LOWER SLAB HAVE BEEN GROUTED)
registered engineer.

DURABILITY
1. Corrosion coatings (eg. galvanising) cannot be guaranteed to
be effective in the long term - Can get scratched off during FIRE RATING DESIGN CRITERIA
installation, even in soft clay.
2. Typical corrosion allowance in Sydney (uncontaminated) are RESIDENTIAL 90 MINUTES
0.02~0.03mm per year = 1.5 mm over 50yrs.
3. If piles are not concrete filled, corrosion must be allowed for
COMMERCIAL 180 MINUTES
on the inside of the tube too.
SUPERVISION CAR PARK 120 MINUTES
The Piling Supervisor shall be responsible for ensuring that all
piling operations comply with the requirements of the Australian
Standards, and all referenced publications. The Piling Supervisor NOTES:
shall also ensure that all monitoring and pile records are
maintained up to date, and are available for inspection by the SOIL CLASS FOR EARTHQUAKE DESIGN TO BE
Engineer. CONFIRMED BY GEOTECHNICAL CONSULTANT AND TO
INFORM THE STRUCTURAL ENGINEER IF OTHERWISE.

WIND LOADING PARAMETERS


NOTES:
TERRAIN 3
1. 50% BACKPROPPING DENOTES PROPS AT NO
REGION CLASSIFICATION A2 GREATER THAN 3.6m CENTERS.
2. ENSURE ANY UNSTRESSED DECK NEEDS TO
REGIONAL WIND SPEED 46 BE SUPPORTED BY TWO FULLY STRESSED
CONCRETE DECKS.
3. ALL FORMWORK TO BE CERTIFIED BY STRUCTURAL
AVERAGE RECURRENCE INTERVAL 500 YEARS ENGINEER BEFORE EACH CONCRETE POUR.
DESIGN WORKING LIFE OF 50 YEARS
STRUCTURE
STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY GENERAL NOTES - 2
REV. DATE REVISION DESCRIPTION BY A S0002
900 DENOTES 200 DINCEL WALL OVER
ZONE OF NO PIERS
900
1075 ZONE OF NO PIERS
ZONE OF INFLUENCE
DW1 DW1 LINE 1075

2
ZONE OF INFLUENCE
DENOTES PROPOSED BRICKWORK WALLS OVER

5
FP

112
LINE
DW1 DW1 PF1
RW1 RW1
I.J. DENOTES CONCRETE PIER UNDER

DW1
ALL PIERS 6
TO BE FP2 U.N.O. S0101
110 110 THICK SLAB ON GROUND, SL82 TM TOP.

DW2
80
125 125 THICK SLAB ON GROUND, SL82 TM TOP.
DW1

110

I.J.
110 110 RFB1 400 DEEP x 450 WIDE RAFT FOOTING BEAM.
125

TE
4N12 TOP & BOTTOM, N10-300 TIES.
ALL RAFT FOOTINGS PF1 450 DEEP x 700 LONG x 700 WIDE PAD FOOTING.
TO BE RFB1 U.N.O.

DW2
5N12 TOP & BOTTOM & 5N12 TOP & BOTTOM.
DW2 DW2 4 DW1 200 WIDE DINCEL WALL, N16-333 CENTRAL VERTICAL &
S0101 N12-300 HORIZONTAL.

DW1
DW2 110 WIDE DINCEL WALL, N12-333 CENTRAL VERTICAL &
I.J. DW1 N12-300 HORIZONTAL.
110 110 110 FP1 ∅600 PIER TO SUPPORT RAFT FOOTING BEAM. MIN.
300mm SOCKET INTO 500KPa SOIL LAER, 4N16 VERTICAL

DW1
1000 BAR IF PIER MORE THAN 1.5m & LESS THAN 2.5m DEEP.
DW2 DW2
DW2

6N16 WITH R10-300 HELICAL TIE BAR @300 TO BE

20
REQUIRED IF PIER MORE THAN 2.5m DEEP.

DW2
DW1

80 FP2 ∅600 PIER TO SUPPORT RAFT FOOTING BEAM. MIN.


DW2 DW2 DW2 1000 1400mm SOCKET INTO 500KPa SOIL LAER, 4N16
VERTICAL BAR IF PIER MORE THAN 1.5m & LESS THAN
110

DW2
2.5m DEEP. 6N16 WITH R10-300 HELICAL TIE BAR @300
20 TO BE REQUIRED IF PIER MORE THAN 2.5m DEEP.

DW2
110 110 110 110
DENOTES FLOOR STEP
20
DW2
1 2
S0101 S0101 5 CONCRETE QUALITY
3

DW1
S0101 S0101
ELEMENT SLUMP AGGREGATE CEMENT f'c
(MAX. SIZE) TYPE
INTERNAL SLABS 80mm 20mm A 32 MPa U.N.O.
DW1 DW1 DW1 DW1
EXTERNAL SLABS 80mm 20mm A 32 MPa U.N.O.
BASEMENT FOOTING PLAN
BEAMS 80mm 20mm A 32 MPa U.N.O.
1:100
REINFORCEMENT COVER SCHEDULE
COVER (mm) EXPOSURE
ELEMENT
NOTES: TOP BOTTOM SIDES CLASSIFICATION
ALL FOOTING PIERS MIN. 300mm INTERNAL SLABS 30mm 35mm 35mm A1
SOCKET INTO LAYER WITH 500 Kpa
S.B.V. EXTERNAL SLABS 40mm 40mm 40mm B1
FOOTING BEAMS 40mm 40mm 40mm A1

REINFORCEMENT NOTES: NOTES:


1. ALL REINFORCEMENT SHOWN IS TO BE 3. TYPICAL TRIMMERS AT RE-ENTRANT CORNERS 1. ALL STEPS, FALLS AND LEVELS TO ARCHITECTURAL
DETIALS.
ADDITIONAL TO STANDARD REINFORCEMENT. REFER 2N12-1200LG
TO SECTIONS ON THIS DRAWING FOR STANDARD TIED UNDER TOP 2. AL EXPOSED SLABS TO BE WATERPROOFING WITH
REINFORCEMENT. MESH TYPICAL ALL APPROVED SYSTEM.
RE-ENTRANT 3. CHAMFER, FILLET AND DRIP GROOVE TO ARCHITECTURAL'S
2. TYPICAL TRIMMERS AT PENETRATION DETAIL: CORNERS SPECIFICATIONS AND TO BUILDER REQUIREMENTS.
600 TYP.
4. ALL GLAZING REBATES AND HOB DETAILS REFER TO
ARCHITECTURAL CONCRETE SETOUT DRAWINGS AND DETAILS.
5. DO NOT SCALE ANY DIMENTIONS FROM STRUCTURAL
DRAWINGS FOR SETTING OUT PURPOSES.

GEOTECHNICAL ENGINEER TO CERTIFY MINIMUM BEARING


2N12-100, TOP & BTM CAPACITY OF 500KPa UNDER ALL PIERS HAS BEEN ACHIEVED
STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
LOWER GROUND FOOTING & SLAB CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY
PLAN A S01
110 110
200
110 DINCEL WALL 110 DINCEL WALL
N12-333 CENTRAL VERTICAL N12-333 CENTRAL VERTICAL
200 DINCEL WALL N12-300 HORIZONTAL N12-300 HORIZONTAL
N16-333 CENTRAL VERTICAL
N12-300 HORIZONTAL N12 STARTER BAR N12 STARTER BAR
N12 STARTER BAR COG 200 INTO FOOTING COG 200 INTO FOOTING
COG 200 INTO FOOTING 600 OVERLAP IN DINCEL WALL 600 OVERLAP IN DINCEL WALL
600 OVERLAP IN DINCEL WALL (TYPICAL) (TYPICAL)
(TYPICAL)

SEALANT AS REQUIRED SL82 TOP (TYP)


SL82 TOP (TYP)
SL82 TOP (TYP)

110
110

110

110
MIN. 400
MIN. 400

MIN. 400
200 COG 200 COG
RFB1 RFB1 RFB1

450 4N12 TOP & BOTTOM 450 450 200 COG


600 WITH N10-300 TIES 600 4N12 TOP & BOTTOM 600 4N12 TOP & BOTTOM
WITH N10-300 TIES WITH N10-300 TIES
FP1 FP1 FP1

SECTION 1 SECTION 2 SECTION 3


1:20 S01 1:20 S01 200 1:20 S01
200 DINCEL WALL 200 DINCEL WALL
N16-333 CENTRAL VERTICAL N16-333 CENTRAL VERTICAL
N12-300 HORIZONTAL N12-300 HORIZONTAL CORE FILL
200 N12 STARTER BAR
COG 200 INTO FOOTING N12 STARTER BAR N16 400 COG.
600 OVERLAP IN DINCEL WALL COG 200 INTO FOOTING
10mm ABLEFLEX
(TYPICAL) 600 OVERLAP IN DINCEL WALL
JOINT FILLER
(TYPICAL)
SL82 TOP (TYP)
10mm ABLEFLEX
SEALANT AS REQUIRED

125
JOINT FILLER
80

SL82 TOP (TYP) SL82 TOP (TYP)


SL82 TOP (TYP)
110
110
125

MIN. 400

450
MIN. 400

200 COG
PF1
RFB1 5N12 TOP & BOTTOM
RFB1 700
450 4N12 TOP & BOTTOM 4N12 TOP & BOTTOM 450 5N12 TOP & BOTTOM
WITH N10-300 TIES WITH N10-300 TIES 600
600 600
FP1
FP1 FP1

SECTION 4 SECTION 5 SECTION 6


1:20 S01 1:20 S01 1:20 S01

STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY
FOOTING & SLAB DETAILS - 1
A S0101
1N12 CONER BAR TOP & 4N12
N.G.L. VARIES TO SUIT BOT 600 LEGS. EXTRA

200
4N12 4N12

200

MAX.
800
1 C/S 4N12 Z-BARS

4N12 4N12
4N12
4N12
600
FOR SLOPES < 1:10 4N12 Z-BARS
STEPS TO OCCUR AT FP1
LOCATIONS

TYPICAL FOOTING CONER 600


TYPICAL STEP FOOTING DETAIL-3 & INTERSECTION DETAILS 4N12
1:20 N.T.S. STEPS TO OCCUR AT FP1
LOCATIONS

TYPICAL STEP FOOTING DETAILS


1:20

REINFORCED CONCRETE SLAB REFER


DETAILS.
REINFORCED CONCRETE
SLAB REFER DETAILS.
0.2mm IMPERVIOUS MEMBRANE 0.2mm IMPERVIOUS
MEMBRANE

30mm COMPACTED SAND BLINDING LAYER. 30mm SAND


BLINDING LAYER.
FILLING IF REQUIRED SHALL BE GRANULAR LOOSE FORM FILL GRANULAR
MATERIAL COMPACTED IN NOT MORE THAN MATERIAL SHALL BE FREE OF
NOTE: 150mm LAYERS TO A MINIMUM DRY DENSITY ALL DELETERIOUS MATTER
SAND BLINDING, SUB-BASE, FILLING AND SUB RATIO OF 98% TO AS 1289/E4.2 1982.
SUB GRADE SHALL BE
GRADE TO BE MECHANICALLY COMPACTED TO STRIPPED OF ALL TOPSOIL,
A DRY DENSITY RATIO OF NOT LESS THAN SUBGRADE SHALL BE STRIPPED OFF ALL
DELETERIOUS MATTER AND
98% STANDARD MAXIMUM DRY DENSITY. TOPSOIL AND DELETERIOUS MATTER.
APPROVAL SHALL BE OBTAINED FROM TYPICAL SLAB PREPARATION UNCONTROLLED FILL
ALL AREAS TO BE TESTED BY GEOTECHNICAL
ENGINEER AND RESULTS FORWARDED TO THE ENGINEER PRIOR TO PLACING FILL. SUSPENDED SLAB ON FORM FILL
STRUCTURAL ENGINEER PRIOR TO POURING TYPICAL
SLAB PREPARATION NTS
CONCRETE.
SLAB ON GRADE
NTS

STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY
TYPICAL PAD FOOTING DETAILS
A S0102
FILL WITH APPROVED FLEXIBLE
SEALANT WITH BACKING ROD TO
MANUFACTURERS
SPECIFICATIONS
BRICK WALL LINTEL SCHEDULE

20
SILICONE RUBBER FLEXIBLE MAXIMUM OPENING LINTEL SIZE
STOP MESH EACH SIDE OF JOINT SEALANT 10-15mm THICK SIZE (mm)
10 NOTE: PROVIDE FIREJOINT
16mm SQUARE GALVANISED MEDIUM DUTY VENEER SEALANT WHERE FIRE RATING 1500 90 × 90 × 6 EA
DOWEL BARS (450 LONG) @ 400 TIES SPACED AT 600 20 REQUIRED BY ARCHITECT
2000 90 × 90 × 8 EA
MAS CTS, COAT MATING SURFACES CTS. VERT. & HORIZ PERMANENT, CIRCULAR
WITH APPROVED BOND BREAKER, POLYETHYLENE BACKING ROD 2500 150 × 90 × 8 EA
PROVIDE RECTANGULAR DANLEY
DOWELMASTER SLEEVES 3000 150 × 90 × 10 EA
STICTLY TO MANUFACTURERS SEALANT DETAIL 2
SPECIFICATIONS SCALE 1:2 BRICK LINTEL NOTES:
INTERNAL 1. PROVIDE 200mm MINIMUM BEARING EACH END.
BRUNSWICK SALES ''MFA3/3'' TIES AT STUD WALL 2. LONG LEG OF ANGLE VERTICAL.
MIN'M. 4 COURSE CENTRES. VERT. 3. LINTEL SIZES PROVIDED ASSUME MASONRY
ARCHING IS POSSIBLE, AND NO OTHER VERTICAL
LOADS ON WALL EXCEPT FOR SELF WEIGHT.
4. LINTELS EXCEPT FOR INTERNAL WALLS TO BE
HOT DIP GALV.
DOWEL JOINT - DJ
SCALE 1:20 BRICK WALL ARTICULATION JOINT
NOT TO SCALE
1N12 TRIMMER NOTE: ARTICULATION JOINTS SPACED 5000 MAXIMUM CENTRES
LAP 500 AS REQ'D & 10 GAP 1N12 TRIMMER 10 GAP
AT CORNERS. LAP 500 AS REQ'D &
AT CORNERS. SL82 TOP
150

110
300
10 ABLEFLEX
10 ABLEFLEX JOINT FILLER. TE
JOINT FILLER.
FACE OF SLAB 300
FACE OF SLAB 3-L12TM BOTTOM
OR WALL WITH R10-600 TIES
OR WALL

ISOLATION JOINT - I.J.


DRAWINGS MAX. 50

TYPICAL TE DETAIL
REFER TO ARCH

SCALE 1:20
1:20
REFER ARCH
DRAWINGS

N12-300 'U' BARS REFER TO ARCH


SL82 FABRIC TOP DRAWINGS
1-N12 CONT.
3N12-75x1200 LONG
TYPICAL AT ALL
RE-ENTRANT CORNERS.

N12-300 'L' BAR


NOTE: REFER ARCHITECTS & 1-N12 CONT. RE-ENTRANT (INTERNAL) CORNERS
DRAWINGS FOR LOCATIONS.
NOTE: REFER ARCHITECTS SCALE 1:20
DRAWINGS FOR LOCATIONS.
TYPICAL TOPPING SLAB DETAIL
SCALE 1:20 TYPICAL HOB DETAIL
SCALE 1:20

STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY
FOOTING & SLAB DETAILS - 2
A S0103
1200

7N12

SL82 MESH

REFER TO SLAB
N12-200
SLAB REO NOT

PLAN
SHOWN FOR CLARITY
AP
0 0 L ICAL
6 P
TY
N12-300 N12-200

170
N12-300

600 7N12 STARTER 7N12


ABLEFLEX PLUS BARS
SEALANT

170
100

REFER TO
SLAB PLAN 7N12 SCABBLE 7N12
REFER TO CONCRETE
SLAB PLAN
4L11-TM 0
60

7N16 STARTER
BARS
REFER TO 150 400 150
LANDING DETAILS

200
450
'X' BARS

TYPICAL STAIR ON GROUND


500 TYP. STAIR F1
1:20 TYPICAL STAIR DETAIL
N.T.S.
'L' AP 16
L -N
0
50 LAP
0
60 'X' BARS REFER TO
LANDING DETAILS

THROAT THK.
'T'
'L'
'X' BARS
'Y' BARS
'X' BARS

SCABBLE THROUGHLY

TYPICAL STAIR DETAIL - 3


P
SLAB LA -N16 1:20
0 P
50 L A
0
60
500 TYP.
600(N16)
1000 TYP. STATUS DATE
ISSUE FOR REVIEW ONLY MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
CLIENT DRAWING A3 DRAWING NUMBER
CHECKED REVISION

REV.
1 24.03.21 ISSUE FOR REVIEW ONLY
DATE REVISION DESCRIPTION BY
TYPICAL STAIRS DETAILS-1
1 S0104
7N12
500 TYP.

' P
'L LA N16
0 -
50 LAP GROUND FLOOR SLAB
0
60 REINFORCEMENT REFER
REFER TO SLAB DREWINGS
REO PLAN

N12-200

170
7-N12
N12-300
7-N12

SCABBLE THROUGHLY

LAP 700 WITH MAIN N12-300 CROSSRODS


STAIR REINF.

N12-200 EPOXY
SET 100 INTO SLAB N12-200

TYPICAL STAIR DETAIL - 1


1:20

TYPICAL STAIR DETAIL - 2


1:20

STATUS DATE
ISSUE FOR REVIEW ONLY MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
CLIENT DRAWING A3 DRAWING NUMBER
CHECKED REVISION
1
REV.
24.03.21 ISSUE FOR REVIEW ONLY
DATE REVISION DESCRIPTION BY
TYPICAL STAIRS DETAILS-2
1 S0105
55mm COVER TO 55mm COVER TO VERTICAL
R.L. TOP OF WALL 190 VERTICAL REINFORCEMENT R.L. TOP OF WALL 190 REINFORCEMENT
55mm COVER TO VERTICAL 55mm COVER TO TO ARCHITECTS TO ARCHITECTS
REINFORCEMENT VERTICAL REINFORCEMENT DETAILS DETAILS
190 R.L. TOP OF WALL 190 R.L. TOP OF WALL
GROUND LEVEL VARIES GROUND LEVEL VARIES
TO ARCHITECTS TO ARCHITECTS
DETAILS DETAILS
GROUND LEVEL VARIES GROUND LEVEL VARIES

N16 FOR TOP N16 FOR TOP WATER PROOF MEMBRANE GEOFABRIC
COURSE COURSE AS REQUIRED TO 'K' BARS 'K' BARS

HEIGHT IN 190 BLOCK


COARSE

HEIGHT IN 190 BLOCK


BLUEMETAL
AGGREGATE ARCHITECTS DETAILS COARSE AGGREGATE
N12 AT 400 N12 AT 400 AGGREGATE BACKFILL
WATER PROOF MEMBRANE
HORIZONTAL AS REQUIRED TO HORIZONTAL ATLANTIS DRAINAGE WATER PROOF
CELL WITH STRIP DRAIN 600 LAP 600 LAP MEMBRANE
N12 AT 400 ARCHITECTS DETAILS N12 AT 400 AS REQUIRED
AT BASE - CONNECT TO WATER PROOF TO
VERTICAL FOR GEOFABRIC VERTICAL FOR
SW SYSTEM MEMBRANE ARCHITECTS
WALL HEIGHT UP WALL HEIGHT UP AS REQUIRED TO DETAILS
TO 1400. TO 1400. N16 AT 400 N16 AT 400
HORIZONTAL ARCHITECTS HORIZONTAL AT BASE -
FOR ABOVE 1400, FOR ABOVE 1400, DETAILS

'H'
CONNECT TO

'H'
BARS TO BE N16 BARS TO BE N16
SW SYSTEM
'H'

'H'
AT 400 AT 400
500 LAP 500 LAP
290 290
CLEAN OUT BLOCK SUBSOIL DRAINAGE CLEAN OUT BLOCK

HEIGHT IN 290 BLOCK


HEIGHT IN 290 BLOCK
REFER HYDRAULIC GEOFABRIC
ENGINEER'S DETAILS 'K' BARS 'V' BARS 'K' BARS
HOT DIP
NGL NGL CLEAN OUT GALVANIZED CLEAN OUT BLOCK 'V' BARS
BLOCK HOT DIP
Ø90mm AGG. GALVANIZED
150

150
N16 AT 400 LINE N16 AT 400
NGL TO DRAINAGE NGL
200

200

150
150

100
100
'D'

'D'
SL82 TOP SL82 TOP

300
300
N16 AT 400 N16 AT 400 N16 AT 400 N16 AT 400
'V' BARS 'W' 'V' BARS 'W'
N16-400 N16-400
'B' 'L' BARS 'B' 'L' BARS
N16 AT 400 N16 AT 400
TYPICAL RETAINING WALL (TYPE 1) DETAIL-1 TYPICAL RETAINING WALL (TYPE 1) DETAIL-2
'W' 'W'
1:20 1:20
RETAINING WALL FOOTING
WPM TO ARCH DETAILS TYPICAL RETAINING WALL (TYPE 2) DETAIL-1 TYPICAL RETAINING WALL (TYPE 2) DETAIL-2
55 N12-400 E.W.
& REINFORCEMENT SCHEDULE - TYPE 1
GROUND LEVEL VARIES 1:20 1:20
TOTAL
WALL 'B' 'D' 'W' 'V'
HEIGHT BARS RETAINING WALL REINFORCEMENT SCHEDULE - TYPE 2
190 RC BLOCKWORK 900
'H' MAX.
TOTAL HEIGHT HEIGHT
800 600 500 450 N12 AT 400 WALL IN IN 'V' 'K'
SUBSOIL 'B' 'D' 'W'
1000 700 500 450 N12 AT 400 DRAINAGE REFER HEIGHT 190 290 BARS BARS
HYDRAULIC 'H' BLOCK BLOCK
1200 800 500 450 N12 AT 400 ENGINEER'S
PAVEMENT DETAILS
1400 950 500 450 N16 AT 400 2200 1400 800 2000 800 600 N16 AT 200 N16 AT 400

1600 1100 600 450 N16 AT 400 N12-400 'L' 2400 1600 800 2200 900 600 N16 AT 200 N16 AT 400
STARTER BARS -
1800 1400 700 450 N16 AT 400 300 COG INTO 2600 1600 1000 2400 900 900 N16 AT 200 N16 AT 400
FOOTING
300

2000 1600 700 600 N16 AT 200 2800 1800 1000 2600 900 900 N20 AT 200 N16 AT 400
NOTE: BASE DIMENSIONS FOR LEVEL 3000 2000 1000 2800 1000 900 N20 AT 200 N16 AT 200
BACKFILL ONLY.
500 4-L18 TM 3200 2000 1200 3000 1100 900 N20 AT 200 N16 AT 200
TOP & BOTTOM
R6-900 TIES 3400 2000 1400 3200 1200 900 N20 AT 200 N20 AT 200
TYPICAL 140 RETAINING WALL DETAIL NOTE: BASE DIMENSIONS FOR LEVEL BACKFILL ONLY.
1:20
STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY
TYPICAL RETAINING WALL DETAILS
A S0106
5 6 DENOTES PROPOSED BRICKWORK WALLS OVER
S0201 450W x 290D S0201
DENOTES LOAD BEARING WALLS UNDER

450W x 320D 450W x 320D


NOTES & MEMBER SCHEDULE
1 30 270 30
110 110 THICK SLAB ON GROUND, SL82 TM TOP.
S0201
2 450W x 320D
190 190 THICK SUSPENDED REINFORCED CONCRETE SLAB,
300 S0201 85 REFER TO REO PLANS.
200 200 THICK SUSPENDED REINFORCED CONCRETE SLAB,

30
450W x 320D 235
REFER TO REO PLANS.
300
)
(o

7 215 215 THICK SUSPENDED REINFORCED CONCRETE SLAB,


GC
1

S0201 REFER TO REO PLANS.


PF2 235 250 THICK SUSPENDED REINFORCED CONCRETE SLAB,
TE 235 REFER TO REO PLANS.
1
FP

270 270 THICK SUSPENDED REINFORCED CONCRETE SLAB,


REFER TO REO PLANS.
85 300W x 285D
110 300 300 THICK SUSPENDED REINFORCED CONCRETE SLAB,
TE

REFER TO REO PLANS.


(o)
2 200 CC- DENOTES REINFORCED CONCRETE COLUMN, REFER TO
GC

TE COLUMN DETAILS
CC

1
PF2 300 450W x 320D GC- DENOTES 100x100x6 SHS STEEL COLUMN.
1
FP

3 BP DENOTES 330x330 CORE FILL BRICK PIER.


S0201 FP1 ∅450 PIER TO SUPPORT RAFT FOOTING BEAM. MIN.
4 300mm SOCKET INTO 500KPa SOIL LAER, 4N16
S0201 235 VERTICAL BAR IF PIER MORE THAN 1.5m & LESS THAN
2.5m DEEP. 6N16 WITH R10-300 HELICAL TIE BAR @300
RW

300W x 285D TO BE REQUIRED IF PIER MORE THAN 2.5m DEEP.


85

110 200 300 85


DENOTES STEP IN SLAB
10 9
S0201 S0201 NOTES:
2

CC
450W x 320D
3

1. ALL STEPS, FALLS AND LEVELS TO ARCHITECTURAL


CC

DETIALS.

BP
2. AL EXPOSED SLABS TO BE WATERPROOFING WITH
(o)
PF

RW
FP RFB2

110 APPROVED SYSTEM.


1

3
1
FP

GC

3. CHAMFER, FILLET AND DRIP GROOVE TO ARCHITECTURAL'S


1
1
FP

8 RFB2 SPECIFICATIONS AND TO BUILDER REQUIREMENTS.


)
(o
4

S0201
GC

4. ALL GLAZING REBATES AND HOB DETAILS REFER TO


ARCHITECTURAL CONCRETE SETOUT DRAWINGS AND DETAILS.
GROUND FLOOR SLAB PLAN 5. DO NOT SCALE ANY DIMENTIONS FROM STRUCTURAL
DRAWINGS FOR SETTING OUT PURPOSES.
1:100
6. ALL HOB DETAILS REFER TO ARCHITECTURAL CONCRETE
SET OUT DRAWINGS.
PAD FOOTING SCHEDULE
REINFORCEMENT COVER SCHEDULE
MARK SIZE (LxWxD mm) REO (LB & WB) SBV
COVER ( mm ) EXPOSURE
PF1 950x950x500 N12-200 TOP & BTM, E.W. 500KPa ELEMENT
TOP BOTTOM SIDES CLASSIFICATION
PF2 650x650x500 N12-200 TOP & BTM, E.W. 500KPa INTERNAL SLABS 25mm 25mm 25mm A1
LINTEL SCHEDULE COLUMN 40mm 40mm 40mm B1
SPAN (mm) SIZE/TYPE BEAMS 40mm 40mm 40mm A1

0-1000 2/85x8 GALINTELS CONCRETE QUALITY


1001-2000 ELEMENT SLUMP AGGREGATE CEMENT f'c
2/150x100 GALINTELS (MAX. SIZE) TYPE
2001-3000 2/150x100 GALINTELS INTERNAL SLABS 80mm 20mm A 32MPa U.N.O.
COLUMN 80mm 20mm A 32MPa U.N.O.
3001-4000 240 GALINTEL CAVI-T-BAR
BEAMS 80mm 20mm A 32MPa U.N.O.
4001-5000 240 GALINTEL CAVI-T-BAR STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
GROUND FLOOR FOOTING & CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY SLAB PLAN A S02
REINFORCEMENT NOTES:
1. ALL REINFORCEMENT SHOWN IS TO BE ADDITIONAL
TO STANDARD REINFORCEMENT. REFER TO SECTIONS
ON THIS DRAWING FOR STANDARD REINFORCEMENT.

1000
2. TYPICAL TRIMMERS AT PENETRATION DETAIL:

1000 BAR LAYING SEQUENCE


NTS

A2
A1 3. TYPICAL TRIMMERS AT RE-ENTRANT CORNERS

1000
1000

4. PROVIDE TOP & BOTTOM BARS ON ALL WALL


OPENINGS
AS PER THE SCHEDULE BELOW:
TOP & BTM REINFORCEMENT SCHEDULE
MARK BAR SIZE BAR SPACING LAYER
1000 A1 N12 200 1
A2 N12 200 2
A2

1000 A3 N12 200 3


A4 N12 200 4
1000

1000 A1

BAR DIA. A B
N12 500 - D 500
PF
1

N16 800 - D 800


N20 1200 - D 1200
N24 1600 - D 1600
N28 2100 - D 2100
GROUND FLOOR SLAB BOTTOM REINFORCEMENT PLAN N32 2600 - D 2600
1:100 N36 3100 - D 3100

TOP SURFACE STEP

A B

D
A B

D
BOTTOM SOFFIT STEP
TYPICAL REINFORCEMENT
BAR LAP AT STEPS U.N.O.
NTS

STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
GROUND FLOOR SLAB BOTTOM CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY REINFORCEMENT PLAN A S0201
REINFORCEMENT NOTES:
1. ALL REINFORCEMENT SHOWN IS TO BE ADDITIONAL
TO STANDARD REINFORCEMENT. REFER TO SECTIONS
ON THIS DRAWING FOR STANDARD REINFORCEMENT.
2. TYPICAL TRIMMERS AT PENETRATION DETAIL:

BAR LAYING SEQUENCE

A2
NTS

A1 3. TYPICAL TRIMMERS AT RE-ENTRANT CORNERS

1000
1000

4. PROVIDE TOP & BOTTOM BARS ON ALL WALL


OPENINGS
AS PER THE SCHEDULE BELOW:
TOP & BTM REINFORCEMENT SCHEDULE
MARK BAR SIZE BAR SPACING LAYER
1000 A1 N12 200 1
A2 N12 200 2
A2

1000
A3 N12 200 3
A4 N12 200 4
1000

1000 A1

BAR DIA. A B
N12 500 - D 500
PF
1

N16 800 - D 800


N20 1200 - D 1200
N24 1600 - D 1600
N28 2100 - D 2100
GROUND FLOOR SLAB TOP REINFORCEMENT PLAN N32 2600 - D 2600
1:100 N36 3100 - D 3100

TOP SURFACE STEP

A B

D
A B

D
BOTTOM SOFFIT STEP
TYPICAL REINFORCEMENT
BAR LAP AT STEPS U.N.O.
NTS

STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
GROUND FLOOR SLAB TOP CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY
REINFORCEMENT PLAN A S0202
FLASHING PLATE
PROVIDE 2N16 TOP FLASHING PLATE
& BTM WITHIN SLAB REO REFER TO SLAB REO REFER TO PROVIDE 2N16 TOP
CORBEL JOINT REINFORCEMENT PLAN & BTM WITHIN

30
REINFORCEMENT PLAN SLAB REO REFER TO
450 450 COG. CORBEL JOINT REINFORCEMENT PLAN

REFER TO ARCH
450 450 COG.
85

300

270
300
SLAB REO REFER TO

85
320
REINFORCEMENT PLAN

270
200

85

290
235
SECTION 2

300

320
1:20 S02
N12-200 'Z' BARS SLAB REO REFER TO 4N20 TOP & BTM
3N16 TOP & BTM REINFORCEMENT PLAN S.J. 2N12 S.J. S.J. 4 LEGS N12-250 TIES.
450
N12-200 'U' BARS LONGITUDINAL,
200 DINCEL WALL 3N16 TOP & BTM R10-400 'L' N12-200 'U' BARS
200

N16-333 CENTRAL VERTICAL BARS 200 DINCEL WALL

300
N12-300 HORIZONTAL
2N12-400 'Z' BAR
N16-333 CENTRAL VERTICAL
N12-300 HORIZONTAL
SECTION 1 S.J. SECTION 4
1:20 S02 1:20 S02 SECTION 5
1:20 S02
C.J.
SL82 TOP (TYP)
SECTION 3

110

200
1:20 S02

80
MIN. 400
FLASHING PLATE FLASHING PLATE 1000 LESS THAN 200
PROVIDE 2N16 TOP SLAB REO REFER TO SLAB REO

REFER TO ARCH
N12-200 LONGITUDINAL BARS
& BTM WITHIN REINFORCEMENT PLAN & N12-200 VERTICAL BARS REFER TO
SLAB REO REFER TO
CORBEL JOINT REINFORCEMENT PLAN 400 COG. REINFORCEMENT
450 COG. 510 4N12 TOP & BOTTOM 1000 C.J. 450 COG. PLAN
450 450 COG. 450
450 WITH N10-300 TIES C.J.

110
85

85
300

300

C.J.
320

SECTION 8
320

C.J.

235
1:20 S02
4N20 TOP & BTM
SLAB REO REFER TO 4 LEGS N12-250 TIES.
REINFORCEMENT PLAN
4N20 TOP & BTM 4N20 TOP & BTM N12-200 'Z' BARS
4 LEGS N12-250 TIES. 4 LEGS N12-250 TIES. 3N16 TOP & BTM N12-200 'U' BARS
200 DINCEL WALL
N16-333 CENTRAL VERTICAL

200
N12-200 'U' BARS RETAINING

285
WALL REFER N12-300 HORIZONTAL

200
200 DINCEL WALL
N16-333 CENTRAL VERTICAL TO TYPICAL
N12-300 HORIZONTAL 300 DETAILS

SECTION 6 SECTION 7 SECTION 9 SECTION 10


1:20 S02 1:20 S02 1:20 S02 1:20 S02

STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY
GROUND FLOOR SLAB DETAILS
A S0203
COLUMN SCHEDULE
SIZE
VERTICAL REINF.
TIES and TYPE
ROOF DETAIL NUMBER
SIZE
VERTICAL REINF.
TIES and TYPE
f'c=32MPa

FIRST FLOOR DETAIL NUMBER 2 2 2


350
SIZE 500x300 500x300 350x350 500
VERTICAL REINF. 8N16 8N16 8N16
TIES and TYPE N10-240, 1 N10-240, 1 N10-240, 2

350
300
GROUND FLOOR DETAIL NUMBER 1 1 3
SIZE
VERTICAL REINF.
TIES and TYPE
BASEMENT DETAIL NUMBER 8N16 8N16
STARTER BARS 8N16 8N16 8N16 2 SETS N12-240 CLOSED TIES 2 SETS N12-240 CLOSED TIES
COLUMN LOADS(KN)(WORKING) - - - TYPE 1 TYPE 2
1:20 1:20
COLUMN MARK C1 C2 C3

DETAIL - 1 DETAIL - 2 DETAIL - 3


1:20 1:20 1:20

STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY
COLUMN SCHEDULE & DETAILS
A S0204
DENOTES BRICKWORK WALLS
OVER

DENOTES LOAD BEARING


WALLS UNDER

375
250 DENOTES NON LOAD BEARING
250 250 WALLS UNDER

85
85

85
375
30 30 30 85 NOTES & MEMBER SCHEDULE

2 220 250 220 250 250 THICK SUSPENDED REINFORCED CONCRETE SLAB,
REFER TO REO PLANS.
S0303 250 220 220 THICK SUSPENDED REINFORCED CONCRETE SLAB
1 FOR WET AREA, REFER TO REO PLANS.
S0303 250

30
u) CC- DENOTES REINFORCED CONCRETE COLUMN, REFER TO
COLUMN DETAILS

30
2(
GC

1B1 230PFC+PLATE CURVED BEAM.

DENOTES STEP IN SLAB


85 375
375 250 4
250
3 S0303 NOTES:
S0303 1. ALL STEPS, FALLS AND LEVELS TO ARCHITECTURAL
u)

DETIALS.
2(

1
CC
GC

2. AL EXPOSED SLABS TO BE WATERPROOFING WITH


APPROVED SYSTEM.
5
S0303 3. CHAMFER, FILLET AND DRIP GROOVE TO ARCHITECTURAL'S
250 SPECIFICATIONS AND TO BUILDER REQUIREMENTS.

85 4. ALL GLAZING REBATES AND HOB DETAILS REFER TO


ARCHITECTURAL CONCRETE SETOUT DRAWINGS AND DETAILS.

375
250 250 5. DO NOT SCALE ANY DIMENTIONS FROM STRUCTURAL

2
DRAWINGS FOR SETTING OUT PURPOSES.

CC

85
6. ALL HOB DETAILS REFER TO ARCHITECTURAL CONCRETE
SET OUT DRAWINGS.

)
&o
) 250

2(u
3
&o

CC REINFORCEMENT COVER SCHEDULE

GC
(u
2
GC

COVER ( mm ) EXPOSURE
ELEMENT
TOP BOTTOM SIDES CLASSIFICATION
1B1 INTERNAL SLABS 20mm 25mm 25mm A1
COLUMN 40mm 40mm 40mm B1
o)
&
2(u

BEAMS 40mm 40mm 40mm A1


GC

CONCRETE QUALITY
FIRST FLOOR SLAB PLAN ELEMENT SLUMP AGGREGATE CEMENT f'c
1:100 (MAX. SIZE) TYPE
INTERNAL SLABS 80mm 20mm A 32MPa U.N.O.
COLUMN 80mm 20mm A 32MPa U.N.O.
REINFORCEMENT NOTES:
4. PROVIDE TOP & BOTTOM BARS ON ALL WALL OPENINGS BEAMS 80mm 20mm A 32MPa U.N.O.
1. ALL REINFORCEMENT SHOWN IS TO BE ADDITIONAL TO AS PER THE SCHEDULE BELOW:
STANDARD REINFORCEMENT. REFER TO SECTIONS ON THIS LINTEL SCHEDULE
DRAWING FOR STANDARD REINFORCEMENT. TOP & BTM REINFORCEMENT SCHEDULE
SPAN (mm) SIZE/TYPE
2. TYPICAL TRIMMERS AT PENETRATION DETAIL: MARK BAR SIZE BAR SPACING LAYER
A1 N12 200 1 0-1000 2/85x8 GALINTELS
1001-2000 2/150x100 GALINTELS
A2 N12 200 2
A3 N12 200 3 2001-3000 240 GALINTEL CAVI-T-BAR
BAR LAYING SEQUENCE
A4 N12 200 4 NTS 3001-4000 240 GALINTEL CAVI-T-BAR

4001-5000 240 GALINTEL CAVI-T-BAR


3. TYPICAL TRIMMERS AT RE-ENTRANT CORNERS

STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
4. PROVIDE TOP & BOTTOM BARS ON ALL WALL OPENINGS ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
CHECKED REVISION

REV.
1 24.03.21 ISSUE FOR REVIEW ONLY
DATE REVISION DESCRIPTION BY
FIRST FLOOR SLAB PLAN
A S03
DENOTES BRICKWORK WALLS
OVER

DENOTES LOAD BEARING


WALLS UNDER
DENOTES NON LOAD BEARING
WALLS UNDER

A1
NOTES & MEMBER SCHEDULE

A2
A2
A2
250 250 THICK SUSPENDED REINFORCED CONCRETE SLAB,
REFER TO REO PLANS.
220 220 THICK SUSPENDED REINFORCED CONCRETE SLAB
FOR WET AREA, REFER TO REO PLANS.
CC- DENOTES REINFORCED CONCRETE COLUMN, REFER TO
COLUMN DETAILS
1B1 230PFC+PLATE CURVED BEAM.

DENOTES STEP IN SLAB

NOTES:
1000

1. ALL STEPS, FALLS AND LEVELS TO ARCHITECTURAL


A1 DETIALS.
2. AL EXPOSED SLABS TO BE WATERPROOFING WITH
APPROVED SYSTEM.
3. CHAMFER, FILLET AND DRIP GROOVE TO ARCHITECTURAL'S
SPECIFICATIONS AND TO BUILDER REQUIREMENTS.
4. ALL GLAZING REBATES AND HOB DETAILS REFER TO
ARCHITECTURAL CONCRETE SETOUT DRAWINGS AND DETAILS.
5. DO NOT SCALE ANY DIMENTIONS FROM STRUCTURAL
DRAWINGS FOR SETTING OUT PURPOSES.
6. ALL HOB DETAILS REFER TO ARCHITECTURAL CONCRETE
SET OUT DRAWINGS.

REINFORCEMENT COVER SCHEDULE


COVER ( mm ) EXPOSURE
ELEMENT
TOP BOTTOM SIDES CLASSIFICATION
INTERNAL SLABS 20mm 25mm 25mm A1
COLUMN 40mm 40mm 40mm B1
FIRST FLOOR SLAB BOTTOM REINFORCEMENT PLAN BEAMS 40mm 40mm 40mm A1
1:100
CONCRETE QUALITY
REINFORCEMENT NOTES: ELEMENT SLUMP AGGREGATE CEMENT f'c
4. PROVIDE TOP & BOTTOM BARS ON ALL WALL OPENINGS (MAX. SIZE) TYPE

1. ALL REINFORCEMENT SHOWN IS TO BE ADDITIONAL TO AS PER THE SCHEDULE BELOW: INTERNAL SLABS 80mm 20mm A 32MPa U.N.O.
STANDARD REINFORCEMENT. REFER TO SECTIONS ON THIS COLUMN 80mm 20mm A 32MPa U.N.O.
DRAWING FOR STANDARD REINFORCEMENT. TOP & BTM REINFORCEMENT SCHEDULE
BEAMS 80mm 20mm A 32MPa U.N.O.
2. TYPICAL TRIMMERS AT PENETRATION DETAIL: MARK BAR SIZE BAR SPACING LAYER
A1 N12 200 1 LINTEL SCHEDULE
A2 N12 200 2 SPAN (mm) SIZE/TYPE

A3 N12 200 3 BAR LAYING SEQUENCE


0-1000 2/85x8 GALINTELS
A4 N12 200 4 NTS 1001-2000 2/150x100 GALINTELS
2001-3000 240 GALINTEL CAVI-T-BAR
3. TYPICAL TRIMMERS AT RE-ENTRANT CORNERS
3001-4000 240 GALINTEL CAVI-T-BAR

4001-5000 240 GALINTEL CAVI-T-BAR

STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
4. PROVIDE TOP & BOTTOM BARS ON ALL WALL OPENINGS ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
FIRST FLOOR SLAB BOTTOM CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY REINFORCEMENT PLAN A S0301
DENOTES BRICKWORK WALLS
OVER

DENOTES LOAD BEARING


WALLS UNDER
DENOTES NON LOAD BEARING
WALLS UNDER

A4
NOTES & MEMBER SCHEDULE
250 250 THICK SUSPENDED REINFORCED CONCRETE SLAB,

A3

A3

A3
REFER TO REO PLANS.
220 220 THICK SUSPENDED REINFORCED CONCRETE SLAB
FOR WET AREA, REFER TO REO PLANS.
CC- DENOTES REINFORCED CONCRETE COLUMN, REFER TO
COLUMN DETAILS
1B1 230PFC+PLATE CURVED BEAM.

DENOTES STEP IN SLAB

NOTES:
1000

1. ALL STEPS, FALLS AND LEVELS TO ARCHITECTURAL


DETIALS.
A4
2. AL EXPOSED SLABS TO BE WATERPROOFING WITH
APPROVED SYSTEM.
3. CHAMFER, FILLET AND DRIP GROOVE TO ARCHITECTURAL'S
SPECIFICATIONS AND TO BUILDER REQUIREMENTS.
4. ALL GLAZING REBATES AND HOB DETAILS REFER TO
ARCHITECTURAL CONCRETE SETOUT DRAWINGS AND DETAILS.
5. DO NOT SCALE ANY DIMENTIONS FROM STRUCTURAL
DRAWINGS FOR SETTING OUT PURPOSES.
6. ALL HOB DETAILS REFER TO ARCHITECTURAL CONCRETE
SET OUT DRAWINGS.

REINFORCEMENT COVER SCHEDULE


COVER ( mm ) EXPOSURE
ELEMENT
TOP BOTTOM SIDES CLASSIFICATION
INTERNAL SLABS 20mm 25mm 25mm A1
COLUMN 40mm 40mm 40mm B1
FIRST FLOOR SLAB TOP REINFORCEMENT PLAN BEAMS 40mm 40mm 40mm A1
1:100
CONCRETE QUALITY
REINFORCEMENT NOTES: ELEMENT SLUMP AGGREGATE CEMENT f'c
4. PROVIDE TOP & BOTTOM BARS ON ALL WALL OPENINGS (MAX. SIZE) TYPE

1. ALL REINFORCEMENT SHOWN IS TO BE ADDITIONAL TO AS PER THE SCHEDULE BELOW: INTERNAL SLABS 80mm 20mm A 32MPa U.N.O.
STANDARD REINFORCEMENT. REFER TO SECTIONS ON THIS COLUMN 80mm 20mm A 32MPa U.N.O.
DRAWING FOR STANDARD REINFORCEMENT. TOP & BTM REINFORCEMENT SCHEDULE
BEAMS 80mm 20mm A 32MPa U.N.O.
2. TYPICAL TRIMMERS AT PENETRATION DETAIL: MARK BAR SIZE BAR SPACING LAYER
A1 N12 200 1 LINTEL SCHEDULE
A2 N12 200 2 SPAN (mm) SIZE/TYPE

A3 N12 200 3 BAR LAYING SEQUENCE


0-1000 2/85x8 GALINTELS
A4 N12 200 4 NTS 1001-2000 2/150x100 GALINTELS
2001-3000 240 GALINTEL CAVI-T-BAR
3. TYPICAL TRIMMERS AT RE-ENTRANT CORNERS
3001-4000 240 GALINTEL CAVI-T-BAR

4001-5000 240 GALINTEL CAVI-T-BAR

STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
4. PROVIDE TOP & BOTTOM BARS ON ALL WALL OPENINGS ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
FIRST FLOOR SLAB TOP CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY REINFORCEMENT PLAN A S0302
BALUSTRADE REFER
FLASHING TO ARCH TO ARCH
DETAIL REFER TO REO
REFER TO REO PLANS FLASHING TO ARCH

85
REFER TO

85
REFER TO REO PLANS DETAIL
30

REO PLAN PLANS

250

250
250

250
250
220

250
S.J. S.J. S.J. 375 S.J.

3N16 TOP & BTM


N12-300 TIES
2N12-500 'Z' BAR
SECTION 1 SECTION 2 SECTION 3 SECTION 4
1:20 S02 1:20 S02 1:20 S02 1:20 S02

- ALL PLATES 12mm THICK


- 2M12 CHEMSET INJECTION 801 ANCHORS

161
200

200

178
161 178
161 178 161

TYPICAL COLUMN BASEPLATE DETAILS U.N.O.


1:10
1B1 STEEL BEAM
10mm BASE4 PL.

200
REFER TO 2M16 CHEMSET INJECTION
1000 C.J. REO PLAN ANCHORS, 125mm EMBEDMENT 250x250x10 TOP PLATE
EMBEDED INTO SLAB
WITH 4N12 'L' BAR,
250

250

200 COG INTO SLAB 10 CAP PLATE


FLOOR LEVEL
& 4M16 BOLTS
EMBEDMENT

GC
125 MIN

STEEL COLUMN
POUR 2 POUR 1 6mm C.F.W.
PROVIDE ADEQUATE
SUPPORT UNDER POST. STEEL POST

SECTION 5 TYPICAL STEEL BEAM TO STEEL


TYPICAL BASE PLATE DETAIL TYPICAL STEEL POST & SLAB CONNECTION DETAIL
1:20 S02 N.T.S COLUMN CONNECTION DETAIL
1:20
1:10

STATUS DATE
ISSUE FOR CONSTRUCTION MAR. 2021
ARCHITECT PROJECT DESIGNED SCALE PROJECT NUMBER
REFER
A 19.08.21 ISSUE FOR CONSTRUCTION
AS ARCHITECTURE DRAWN
DWG
PAGE SIZE 210216
2 15.08.21 ISSUE FOR REVIEW ONLY CLIENT DRAWING A3 DRAWING NUMBER
CHECKED REVISION
1 24.03.21 ISSUE FOR REVIEW ONLY
REV. DATE REVISION DESCRIPTION BY
FIRST FLOOR SLAB DETAILS
A S0303