Table 3.10.1.

16 Allowable Ampacities of Insulated Conductors


Rated 0 to 2000 Volts, 60⁰C through 90⁰C. Not More
Than Three Current-Carying Conductors in Raceway, Cable,
or Earth(Directly Burried), Based on Ambient Temparature of 30 ⁰C
Temparature Rating of Conductor (See Table 3.10.1.13.)
60⁰C 75⁰C 90⁰C 60⁰C 75⁰C 90⁰C

Types:
TBS, SA,
SIS, FEP,
FEPB, MI, Types:
RHH, TBS, SA,
RHW, SIS, RHH,
RHW-2, RHW-2,
THHN, THHN,
THHW, THHW,
Types: THW-2, Types: THW-2,
RHW, THWN-2, RHW, THWN-2,
THHW, USE-2, THHW, USE-2,
THW, XHH, THW, XHH,
THWN, XHHW, THWN, XHHW,
Types: XHHW, XHHW-2, Types: XHHW, XHHW-2,
TW, UF USE, ZW ZW-2 TW, UF USE, ZW ZW-2
Conduntor Size in Aluminum or Copper-Clad
Copper
sq. mm Aluminum
2.0 20 20 25 - - -
3.5 25 25 30 20 20 25
5.5 30 35 40 25 30 35
8.0 40 50 55 30 40 45
14 55 65 70 40 50 65
22 70 85 90 55 65 80
30 90 110 115 65 80 90
38 100 125 130 75 90 105
50 120 145 150 95 110 125
60 135 160 170 100 120 135
80 160 195 205 120 145 165
100 185 220 225 140 170 190
125 210 255 265 165 200 225
150 240 280 295 185 225 250
175 260 305 345 205 245 275
200 280 330 355 220 265 300
250 315 375 400 255 305 345
325 370 435 470 305 365 410
375 395 470 530 315 380 430
400 405 485 515 335 405 460
500 445 540 580 370 440 495