ELECTRICAL SYSTEMS & ENGINEERING CENTER ABTS/ES&EC/FMT/32:B

TEST REPORT FOR HT CABLE/ /CONDUCTOR Date: 01/11/2013

CUSTOMER :
SHEET OF
PROJECT :

TEST REPORT FOR HT CABLE/ CONDUCTOR


0
Weather Condition: Temperature: C Humidity: %

1. Date of Testing :

2. Equipment Details
Make :
Voltage grade :
Type of cable :
No of core :
Nominal Cross sectional :
No of strands :
Mfg Year :
3. Location & Cable ID :
Source & Destination :

4. Insulation Resistance Test:

Used Megger : 5000V Duration: 60Sec

Before Hi-pot After Hi-pot


Phases
Values in GΩ Values in GΩ
R–E
Y–E
B–E
R–Y
Y–B
B–R

5. High Pot Test :

Applied Voltage Phases Time Leakage Current Result


(Vdc) (mA)
R – E (Y & B Short to Earth) 1 min
Y – E (R & B Short to Earth) 1 min
B – E (R & Y Short to Earth) 1 min

6. Visual inspection:

Check the cable for any insulation damage


Check for any Core damages

Tested by Verified by Witnessed by


ELECTRICAL SYSTEMS & ENGINEERING CENTER ABTS/ES&EC/FMT/32:B

TEST REPORT FOR HT CABLE/ /CONDUCTOR Date: 01/11/2013

CUSTOMER :
SHEET OF
PROJECT :

7. Continuity check:

FROM TO
PHASE R PHASE Y PHASE B
PHASE R
PHASE Y
PHASE B
RESULT

8. Applicable Standards
 IEC 60840 IS 7098 (P-3) HV Cable.

Testing Calibration
Type Serial no Specification Manufacture
instruments due date
DIGITAL MEGGER

AC/DC LEAKAGE
TESTER

Hi-pot Test Kit

9. Remarks

CRITERIA FOR CABLES

Application Test Item Acceptance criteria Reference Standard/


(Panel/Area Reference document
/component )

2 X Rated Voltage+1 Indian Electricity rules,


Insulation resistance test
i.e. 2 X 11+1 ≥23Mohms Act 1956_1
11KV Cable Withstood
1.5 X Rated Voltage/1 Min IS 7098 Rec-xx 1993/
Hi-pot
i.e. 1.5 *11 ≥ 18.7kV/1min

Tested by Verified by Witnessed by