ELECTRICAL SYSTEMS & ENGINEERING CENTRE ABTS/ES&EC/FMT/47:B

TEST REPORT FOR PROTECTIVE RELAY Date: 01/11/2015


CUSTOMER :
SHEET OF
PROJECT :

TEST REPORT FOR MULTI FUNCTION RELAY

1. Date of Testing :

2. Eq u ip m ent D etai ls :
Location Make Type Serial No. Mfg. Date Aux.supply

VT Details CT Details
Burden(VA Frequency
Ratings Ratio Class Ratio Class Burden(VA)
)
-- -- --

3. Settings :
27 59
Protective IP>> (50) IP> (51) IE>> (50G) IE> (51G)
(Under (Over
function (Over current-HF) (Over current-LF) (Earth fault-HF) (Earth fault-LF)
voltage) voltage)
-- %
Set Value % ( A) %( A) -- % ( A) (V) -- (V)
( A)
Time Dial (sec) (sec) -- (sec) -- (sec) -- (sec) -- (sec)
Characteristic
curve

Test item Criteria


1. Time limit element : 1.1 Within ±5% of each setting value
1.1 Minimum operating value test & For EF - Within ±10% of each
Unit (A) setting value.
Phase R Y B EF Result
Operated value --
Criteria value ~ ~

1.2 Operating time test


Unit (sec) Unit (sec)
Input Setting tap and dial Input
200% 500% 1000%
Phase 200% 500% 1000% Chara.
R EI 26.66±12.5% 3.33±7.5% 0.80±5%
Y NI 3.0 10.12±12.5% 4.32±7.5% 3.00±5%
B NI 1.3 4.38±12.5% 1.87±7.5% 1.30±5%
Criteria value ~ ~ ~ VI 13.5±12.5% 3.37±7.5% 1.50±5%
EF -- -- -- LI 120.0±12.5% 30.0±7.5% 13.33±5%
Criteria value ~ ~ ~ DT 2.00±5% 2.00±5% 2.00±5%
Result:

2. Short time limit element :


2.1 Minimum operating value test 2.1 Within ±10% of each setting value
Unit (A)
Phase R Y B EF Result
Operated value --
Tested by Verified by Witnessed by
ELECTRICAL SYSTEMS & ENGINEERING CENTRE ABTS/ES&EC/FMT/47:B
TEST REPORT FOR PROTECTIVE RELAY Date: 01/11/2015
CUSTOMER :
SHEET OF
PROJECT :

Criteria value ~ ~
2.2 Operating time test
Unit (sec) 2.2 DT: 100 msec or less
Phase R Y B EF Result
Operated value --
Criteria value ~ ~

3. Under voltage element


3.1 Minimum operating value test 3.1 Within ±5% of each setting value
Unit (V)
Phase R-Y Y-B B-R Result
Operated value
Criteria value ~
3.2 Input:
3.2 Operating time test
Unit (sec) Rated Voltage → sudden change of 120% of
Phase R-Y setting value
Y-B B-R Result 0.1 to 0.2: Within±30msec
Operated value 0.5 or more: Within±10%
Criteria value ~

4. Over voltage element


4.1 Minimum operating value test
Unit (V)
Phase R-Y 4.1 Within ±5% of each setting value
Y-B B-R Result
Operated value
Criteria value ~
4.2 Input:
4.2 Operating time test
Unit (sec) 0(V) → sudden change of 120% of
Phase R-Y setting value
Y-B B-R Result 0.1 to 0.2: Within±30msec
Operated value 0.5 or more: Within±10%
Criteria value ~

4. Applicable Standards
 IEC 255

5. Testing instruments:

Calibration
Instrument Type Serial no Specification Manufacture
due date

6. Remarks:

Tested by Verified by Witnessed by