Solenoid valves

Contents Page

Solenoid valves, type PKVD 12 - 20


Introduction ................................................................................................................................ 5
Features ..................................................................................................................................... 5
Technical data ........................................................................................................................... 5
Ordering ..................................................................................................................................... 5
Capacity ..................................................................................................................................... 6
Sizing ......................................................................................................................................... 7
Valve selection .......................................................................................................................... 7
Design/Function ........................................................................................................................ 8
Dimensions and weights ........................................................................................................... 8

Solenoid valves, type EVR 2 ® 40 - NC / NO


Introduction ................................................................................................................................ 9
Features ..................................................................................................................................... 9
Approvals ................................................................................................................................... 9
Technical data ........................................................................................................................... 9
Ordering ................................................................................................................................... 11
Capacity ................................................................................................................................... 14
Liquid capacity Qe kW ........................................................................................................ 14
R 22 .............................................................................................................................. 14
R 134a .......................................................................................................................... 14
R 404A/R 507 ............................................................................................................... 14
R 407C ......................................................................................................................... 15
Suction vapour capacity Qe ...................................................................................................................................................................... 15
R 22 .............................................................................................................................. 15
R 134a .......................................................................................................................... 16
R 404A/R 507 ............................................................................................................... 16
R 407C ......................................................................................................................... 17
Hot gas capacity Qh kW ...................................................................................................... 18
R 22 .............................................................................................................................. 18
R 134a .......................................................................................................................... 19
R 404A/R 507 ............................................................................................................... 20
R 407C ......................................................................................................................... 21
Hot gas capacity Gh kg/s .................................................................................................... 22
R 22 .............................................................................................................................. 22
R 134a .......................................................................................................................... 22
R 404A/R 507 ............................................................................................................... 23
R 407C ......................................................................................................................... 23
Design/Function ...................................................................................................................... 24
Material specifications ............................................................................................................. 25
Dimensions and weights ......................................................................................................... 26
EVR (NC) 2 → 15, flare connection ................................................................................... 26
EVR (NC) 2 → 22, solder connection ................................................................................ 27
EVR (NC) 25, 32 og 40, solder connection ....................................................................... 28
EVR (NC) 15 and 20, flange connection ........................................................................... 28
EVR (NO) 6 → 22, flare or solder connection ................................................................... 29

 Danfoss A/S (RC-CM/hbs), 04 - 2002 RK0YC102 1


Solenoid valves

Contents Page

Solenoid valves, type EVRC 10 ® 20 - NC


Introduction .............................................................................................................................. 31
Technical data ......................................................................................................................... 31
Approvals ................................................................................................................................. 31
Ordering ................................................................................................................................... 31
Material specifications ............................................................................................................. 32
Dimensions and weight ........................................................................................................... 32

Stainless steel solenoid valves type EVRS 3 ® 20 and EVRST 10 ® 20


Introduction .............................................................................................................................. 33
Features ................................................................................................................................... 33
Technical data ......................................................................................................................... 33
Ordering ................................................................................................................................... 34
Capacity ................................................................................................................................... 34
Liquid capacity Qe kW ........................................................................................................ 34
R 717 (NH3) .................................................................................................................. 34
R 22 .............................................................................................................................. 34
R 134a .......................................................................................................................... 34
R 404A ......................................................................................................................... 34
Suction vapour capacity Qe kW .......................................................................................... 35
R 717 (NH3) .................................................................................................................. 35
R 22 .............................................................................................................................. 35
R 134a .......................................................................................................................... 35
R 404A ......................................................................................................................... 35
Hot gas capacity Qe kW ...................................................................................................... 36
R 717 (NH3) .................................................................................................................. 36
R 22 .............................................................................................................................. 36
R 134a .......................................................................................................................... 37
R 404A ......................................................................................................................... 37
Hot gas capacity Gh kg/s .................................................................................................... 38
R 717 (NH3) .................................................................................................................. 38
R 22 .............................................................................................................................. 38
R 134a .......................................................................................................................... 38
R 404A ......................................................................................................................... 38
Design/Function ...................................................................................................................... 39
Material specification ............................................................................................................... 40
Dimensions and weights ......................................................................................................... 41

2 RK0YC102  Danfoss A/S (RC-CM/hbs), 04 - 2002


Solenoid valves

Contents Page

Coils for solenoid valves


Introduction .............................................................................................................................. 43
Features ................................................................................................................................... 43
Technical data ......................................................................................................................... 43
Connection .............................................................................................................................. 43
Ordering ................................................................................................................................... 44

Coils for use in EX zone 2 EEx nA II T3 ................................................................................... 46


Introduction ........................................................................................................................ 46
Features ............................................................................................................................. 46
Approval ............................................................................................................................. 46
Technical data .................................................................................................................... 46
Connections ....................................................................................................................... 46
Ordering ............................................................................................................................. 47

UL - approved coil, type GP .................................................................................................... 48


Introduction ........................................................................................................................ 48
Features ............................................................................................................................. 48
Approvals ........................................................................................................................... 48
Technical data .................................................................................................................... 48
Ordering ............................................................................................................................. 48

 Danfoss A/S (RC-CM/hbs), 04 - 2002 RK0YC102 3


Solenoid valves
Type PKVD 12 - 20

Introduction

PKVD solenoid valve is open at 0 bar differential systems, or in systems that are electronically
pressure, a characteristic that saves energy controlled by, for example, Danfoss ADAP-
costs. KOOL®.
PKVD is a normally open valve, and is designed PKVD is used in suction lines in refrigeration
for use in traditionally controlled refrigeration systems with hot gas defrosting.

Features • For all CFC, HCFC and HFC • Filter in pilot connection
• Minimal pressure drop with fully open valve • Internal relief passage
• Large range of coils for a.c. and d.c. − i.e. no risk of external leakage.

• Can be installed in vertical / horizontal • Solder connections up to 1 5/8 in.


position

Technical data Refrigerants Minimum opening differential pressure


For all CFC, HCFC and HFC ∆p = 0 bar

Max. working pressure Differential between pilot and suction pressure


PB = 21 bar ∆p = 3.5 → 21 bar

Max. test pressure Pilot valve


p' = 28 bar EVH top section

Max. temperature of medium Coils


+140°C a.c. and d.c. 18F standard coils

Min. temperature of medium Pilot connection


-40°C Hot gas, cool gas

Ambient temperature
−40 → +80°C (with a.c.-coil)
−40 → +50°C (with d.c.-coil)

Ordering Rated capacity 1) Solder kv


kW connection value 2) Code no.
Type
Valve body without coil
3
R 22 R 134a R 404A/R 507 R 407 in. mm m /h
PKVD 12 11.8 8.7 10.7 11.0 11/8 6.1 034N1070
PKVD 12 11.8 8.7 10.7 11.0 28 6.1 034N1073
PKVD 15 18.8 13.9 17.0 17.5 13/8 35 10.2 034N1075
PKVD 20 30.9 22.8 27.9 28.7 15/8 16.5 034N1072
PKVD 20 30.9 22.8 27.9 28.7 42 16.5 034N1077
1) Rated suction vapour capacity is based on
evaporating temperature te = −10°C
liquid temperature ahead ofvalve tl = +25°C
pressure drop across valve ∆p = 0.10 bar.
2) The k value is the water flow in m3/h at a pressure drop across valve of 1 bar, ρ = 1000 kg/m3.
v

Coils: See "Coils for solenoid valves", RD3JB

 Danfoss A/S (RC-CM/MWA), 10 - 2001 Technical leaflet - RD3MB302 5


Solenoid valves, type PKVD 12 - 20

Capacity Suction vapour capacity Qe kW at liquid temperature tl= +25°C


Type Press. drop across valve Evaporating temperature te °C
∆p bar –40 –30 –20 –10 0 +10

R 22
PKVD 12 0.02 2.7 3.5 4.3 5.3 6.4 7.6
0.06 4.7 6.0 7.5 9.2 11.1 13.1
0.1 5.9 7.6 9.6 11.8 14.2 17.0
0.2 8.0 10.5 13.3 16.5 19.9 23.9
PKVD 15 0.02 4.4 5.5 6.9 8.5 10.2 12.1
0.06 7.4 9.5 11.9 14.6 17.6 20.9
0.1 9.5 12.2 15.3 18.8 22.7 27.0
0.2 12.8 16.8 21.3 26.2 31.8 37.9
PKVD 20 0.02 7.2 9.1 11.3 13.9 16.7 19.8
0.06 12.2 15.6 19.6 24.0 28.9 34.3
0.1 15.5 19.9 25.0 30.9 37.2 44.3
0.2 21.0 27.5 34.8 42.9 52.0 62.1

R 134a
PKVD 12 0.02 1.8 2.4 3.1 4.0 4.9 6.1
0.06 3.1 4.1 5.3 6.8 8.5 10.5
0.1 3.9 5.2 6.8 8.7 10.9 13.5
0.2 4.9 6.9 9.3 12.1 15.2 18.8
PKVD 15 0.02 2.9 3.8 5.0 6.3 7.9 9.6
0.06 4.9 6.5 8.5 10.9 13.6 16.6
0.1 6.2 8.3 10.9 13.9 17.4 21.4
0.2 8.0 11.1 14.9 19.3 24.3 30.0
PKVD 20 0.02 4.2 6.3 8.2 10.4 12.9 15.8
0.06 8.1 10.7 13.9 17.8 22.3 27.3
0.1 10.1 13.5 17.8 22.8 28.5 35.2
0.2 13.0 18.1 24.4 31.6 39.8 49.1

R 404A/R 507
PKVD 12 0.02 2.2 3.1 3.8 4.8 5.8 7.0
0.06 3.9 5.3 6.7 8.3 10.1 12.1
0.1 4.9 6.6 8.5 10.7 13.0 15.7
0.2 6.6 9.1 11.8 14.9 18.2 22.0
PKVD 15 0.02 3.7 4.8 6.2 7.7 9.4 11.1
0.06 6.1 6.8 10.6 13.2 16.1 19.2
0.1 7.9 10.6 13.5 17.0 20.7 24.9
0.2 10.6 14.6 18.9 23.7 29.0 35.0
PKVD 20 0.02 6.0 8.0 10.0 10.9 15.3 18.2
0.06 10.1 13.6 17.4 21.7 26.4 31.6
0.1 12.8 17.3 22.1 27.9 34.0 40.8
0.2 17.4 24.0 30.8 38.8 47.5 57.2

R 407C
PKVD 12 0.02 2.3 3.1 3.8 4.9 6.1 7.4
0.06 4.0 5.3 6.6 8.6 10.5 12.7
0.1 5.0 6.7 8.4 11.0 13.5 16.5
0.2 6.8 9.2 11.7 15.3 18.9 23.2
PKVD 15 0.02 3.7 4.8 6.1 7.9 9.7 11.7
0.06 6.3 8.4 10.5 13.6 16.7 20.3
0.1 8.1 10.7 13.5 17.5 21.6 26.2
0.2 10.9 14.8 18.7 24.4 30.2 36.8
PKVD 20 0.02 6.1 8.0 9.9 12.9 15.9 19.2
0.06 10.4 13.7 17.2 22.3 27.5 33.3
0.1 13.2 17.5 22.0 28.7 35.3 43.0
0.2 17.9 24.2 30.6 39.9 49.4 60.2
The capacities are based on liquid temperature ahead of expansion valve, tl = +25°C
A change in super heat ts of 10 K changes the capacity approx. 4% accordingly.
Correction factors for liquid temperature tl
tl °C 10 15 20 25 30 35 40 45 50
R 134a 0.88 0.92 0.96 1.0 1.05 1.10 1.16 1.23 1.31
R 22 0.90 0.93 0.96 1.0 1.05 1.10 1.13 1.18 1.24
R 404A/ 0.84 0.89 0.94 1.0 1.07 1.16 1.26 1.40 1.57
R 507
R 407C 0.88 0.91 0.95 1.0 1.05 1.11 1.18 1.26 1.35

6 Technical leaflet - RD3MB302  Danfoss A/S (RC-CM/MWA), 10 - 2001


Solenoid valves, type PKVD 12 - 20

Sizing For optimum performance, it is important to l Refrigerant - CFC, HCFC or HFC


select a PKVD valve according to system l Evaporator capacity Qe in kW
conditions and application. l Evaporating temperature te in °C
The following data must be used when sizing l Liquid temperature ahead of expansion
a PKV/PKVS valve: valve tl in °C
l Connection type flare or solder
l Connection size in inches or mm

Valve selection When selecting the appropiate valve it may Refrigerant: R 404A
Example be necessary to convert the actual evaporator Evaporator capacity: Qe = 9 kW
capacity using a correction factor. This is Evaporating temperature: te = – 20°C
required when your system conditions are Pressure drop across regulator:
different than the table conditions. max. 0.06 bar
The following example illustrates how this is Liquid temperature ahead of expansion valve
done. tl = 30°C
Connection size: 1 5/8 in.

Step 1 Determine the correction factor for liquid From the correction factors table (see below)
temperature tl ahead of the expansion valve. a liquid temperature of 30°C, R 404A
corresponds to a factor of 1.07.
Correction factors for liquid temperature tl
tl °C 10 15 20 25 30 35 40 45 50
R 134a 0.88 0.92 0.96 1.0 1.05 1.10 1.16 1.23 1.31
R 22 0.90 0.93 0.96 1.0 1.05 1.10 1.13 1.18 1.24
R 404A/ 0.84 0.89 0.94 1.0 1.07 1.16 1.26 1.40 1.57
R 507
R 407C 0.88 0.91 0.95 1.0 1.05 1.11 1.18 1.26 1.35

Step 2 Corrected evaporator capacity is


Qe = 9 x 1.07 = 9.63 kW

Step 3 Select the capacity table for R 404A and In this example PKVD 15 will be suitable
choose the column for evaporating since the capacity (10.6 kW at a pressure
temperature te = – 20°C. drop across the regulator of
Using the corrected evaporator capacity, select a 0.06 bar) and the connection size fullfill the
valve that provides an equivalent or greater conditions.
capacity at maximum 0.06 bar pressure drop
across the valve.

Step 4 PKVD 15, 1 3/8 in. solder connection


Code no. 034N1075 see ordering

 Danfoss A/S (RC-CM/MWA), 10 - 2001 Technical leaflet - RD3MB302 7


Solenoid valves, type PKVD 12 - 20

Design/Function

1. Main valve
2. Cylinder with piston
3. Pilot valve
4. Orifice

When the coil is de-energized, pilot valve (3) is When the coil on pilot valve is energized, the
closed thereby shutting off hot gas supply from valve opens and hot gas from the pilot line is
the pilot line. Therefore, through orifice (4), able to flow freely into the space above the
pressure p1 above the piston will be equalized piston in cylinder (2).
with suction gas pressure p4 in the main valve This causes pilot pressure p1 to rise, forcing the
oulet.Thus, spring force p3 will keep the main piston down and closing main valve (1) when
valve open. the differential between pilot pressure p1 and
suction gas pressure p4 becomes greater than
3.5 bar.

Dimensions and weights

Coil with cable

Coil with DIN plugs

Weight of coil
10 W: approx. 0.3 kg
12 and 20 W: approx. 0.5 kg

L5 max. Weight
Connection H1 H2 H3 L L2 L3 L4 B ∅D
Type 10 W 12 / 20 W with coil
in. mm mm mm mm mm mm mm mm mm mm mm mm kg
PKVD 12 11/8 28 21 174 91 215 22 45 54 75 85 72 28.6 2.4
PKVD 15 13/8 35 182 99 285 25 45 54 75 85 82 35.0 3.6
PKVD 20 15/8 28 195 112 285 29 45 54 75 85 82 41.3 4.0
PKVD 20 42 28 195 112 267 29 45 54 75 85 82 42.0 4.0

8 Technical leaflet - RD3MB302  Danfoss A/S (RC-CM/MWA), 10 - 2001


Solenoid valves
Type EVR 2 ® 40 - NC / NO

Introduction EVR is a direct or servo operated solenoid valve


for liquid, suction, and hot gas lines with
fluorinated refrigerants.

EVR valves are supplied complete or as separate


components, i.e. valve body, coil and flanges, if
required, can be ordered separately.

Features • Complete range of solenoid valves for • MOPD up to 25 bar with 12 W coil
refrigeration, freezing and air conditioning
plant • Flare connections up to 5/8 in.

• Supplied both normally closed (NC) and • Solder connections up to 2 1/8 in.
normally open (NO) with de-energized coil
• Extended ends for soldering
• Wide choice of coils for a.c. and d.c. make installation easy
It is not necessary to dismantle the valve
• Suitable for all fluorinated refrigerants when soldering in.

• Designed for media temperatures up to • EVR are also available with flange
105°C connections

Approvals DnV, Det norske Veritas, Norge P Polski Rejestr Statków, Polen

Pressure Equipment Directive (PED) 97/23/EC MRS, Maritime Register of Shipping, Russia

The Low Voltage Directive (LVD) 73/23/EC with Versions with UL and CSA approval can be
amendments EN 60730-2-8 supplied to order.

Technical data Refrigerants Ambient temperature and


CFC, HCFC, HFC enclosure for coil
See "Coils for solenoid valves", RD3JE.
Temperature of medium
−40 → +105°C with 10 W or 12 W coil.
Max. 130°C during defrosting.

 Danfoss A/S, 05 - 2002 Technical leaflet - RD3AD302 9


Solenoid valves, type EVR 2 ® 40 - NC / NO

Technical data Opening differential pressure Temperature Max. working kv value 1)


Type
(continued) with standard coil of medium pressure
∆p bar PB
Max. (= MOPD) liquid 2)
Min. 10 W a.c. 12 W a.c. 20 W d.c. °C bar m3/h
EVR 2 0.0 25 18 −40 → 105 35 0.16
EVR 3 0.0 21 25 18 −40 → 105 35 0.27
EVR 6 0.05 21 25 18 −40 → 105 35 0.8
EVR 6 NO 0.05 21 21 21 −40 → 105 35 0.8
EVR 10 0.05 21 25 18 −40 → 105 35 1.9
EVR 10 NO 0.05 21 21 21 −40 → 105 35 1.9
EVR 15 0.05 21 25 18 −40 → 105 32 2.6
EVR 15 NO 0.05 21 21 21 −40 → 105 32 2.6
EVR 20 (a.c.) 0.05 21 25 13 −40 → 105 32 5.0
EVR 20 (d.c.) 0.05 16 −40 → 105 32 5.0
EVR 20 NO 0.05 19 19 19 −40 → 105 32 5.0
EVR 22 0.05 21 25 13 −40 → 105 32 6.0
EVR 22 NO 0.05 19 19 19 −40 → 105 32 6.0
EVR 25 0.20 21 25 18 −40 → 105 32 10.0
EVR 32 0.20 21 25 18 −40 → 105 32 16.0
EVR 40 0.20 21 25 18 −40 → 105 32 25.0
1) The kv value is the water flow in m3/h at a pressure drop across valve of 1 bar, ρ = 1000 kg/m3.
2) MOPD for media in gas form is approx. 1 bar greater.

Rated capacity
Type kW
Liquid Suction vapour Hot gas
R 22 R 134a R 404A/R 507 R 407C R 22 R 134a R 404A/R 507 R 407C R 22 R 134a R 404A/R 507 R 407C
EVR 2 3.20 2.90 2.20 3.01 1.50 1.20 1.20 1.46
EVR 3 5.40 5.00 3.80 5.08 2.50 2.00 2.00 2.43
EVR 6 16.10 14.80 11.20 15.13 1.80 1.30 1.60 1.66 7.40 5.90 6.00 7.18
EVR 10 38.20 35.30 26.70 35.91 4.30 3.10 3.90 3.96 17.50 13.90 14.30 16.98
EVR 15 52.30 48.30 36.50 49.16 5.90 4.20 5.30 5.43 24.00 19.00 19.60 23.28
EVR 20 101.00 92.80 70.30 94.94 11.40 8.10 10.20 10.49 46.20 36.60 37.70 44.81
EVR 22 121.00 111.00 84.30 113.74 13.70 9.70 12.20 12.60 55.40 43.90 45.20 53.74
EVR 25 201.00 186.00 141.00 188.94 22.80 16.30 20.40 20.98 92.30 73.20 75.30 89.53
EVR 32 322.00 297.00 225.00 302.68 36.50 26.10 32.60 33.58 148.00 117.00 120.00 143.56
EVR 40 503.00 464.00 351.00 472.82 57.00 40.80 51.00 52.44 231.00 183.00 188.00 224.07

Rated liquid and suction vapour capacity is based on


evaporating temperature te = -10°C,
liquid temperature ahead of valve tl = +25°C,
pressure drop in valve ∆p = 0.15 bar.
Rated hot gas capacity is based on
condensing temperature tc = +40°C,
pressure drop across valve ∆p = 0.8 bar,
hot gas temperature th = +65°C,
and subcooling of refrigerant ∆tsub = 4 K.

10 Technical leaflet - RD3AD302  Danfoss A/S, 05 - 2002


Solenoid valves, type EVR 2 ® 40 - NC / NO

Ordering Normally closed (NC) with a.c. coil 1)


Code no.
Complete valves Connection Valve body + 10 W a.c. coil with 1 m cable
Type Flare 2) Solder ODF
in. mm in./mm in. mm
EVR 3 1/4 6 032F2032 032F2042 032F2052
3
EVR 6 /8 10 032F2072 032F2082 032F2092
1
EVR 10 /2 12 032F2102 032F2122 032F2132
5
EVR 15 /8 16 032F2152 032F2192 032F2192

Code no.
Connection Valve body + 10 W a.c. coil with terminal box
Type Flare 2) Solder ODF
in. mm in./mm in. mm
1
EVR 3 /4 6 032F2033 032F2043 032F2053
3
EVR 6 /8 10 032F2073 032F2083 032F2093
1
EVR 10 /2 12 032F2103 032F2123 032F2133
5
EVR 15 /8 16 032F2153 032F2193 032F2193
7
EVR 20 /8 22 032F2243 032F2243

Code no.
Valve body + 10 W a.c. coil
Type Connection
with DIN plugs and protective cap
Flare 2) Solder ODF
in. mm in./mm in. mm
1
EVR 2 /4 6 032F2004 032F2014 032F2024
1
EVR 3 /4 6 032F2034 032F2044 032F2054
3
EVR 6 /8 10 032F2074 032F2084 032F2094
1
EVR 10 /2 12 032F2104 032F2124 032F2134

Type Connection Code no.


Valve body + 10 W a.c. coil
in. mm. with DIN plug 3)
EVR 2 1/4 6 032F2004 032F2014 032F2024
1)Please specify code no., voltage and frequency. Voltage and frequency can also be given in the form of an
appendix number, see table "Appendix numbers".
2)Supplied without flare nuts.
Separate flare nuts:
1
/4 in. or 6 mm, code no. 011L1101
3
/8 in. or 10 mm, code no. 011L1135
1/ in. or 12 mm, code no. 011L1103
2
5
/8 in. or 16 mm, code no. 011L1167
3) Can only be used with DIN plug

Appendix numbers
Voltage Frequency Energy consumpt.
Appendix no.
V Hz W
12 50 10 15
24 50 10 16
42 50 10 17
48 50 10 18
115 50 10 22
220-230 50 10 31
240 50 10 33
380-400 50 10 37
420 50 10 38
24 60 10 14
115 60 10 20
220 60 10 29
240 60 10 30
110 50/60 10 21
220-230 50/60 10 32

 Danfoss A/S, 05 - 2002 Technical leaflet - RD3AD302 11


Solenoid valves, type EVR 2 ® 40 - NC / NO

Ordering (fortsat) Separate valve bodies, normally closed (NC)


Code no.
Components Connection Valve body without coil
Type Required Flare 1) Solder ODF
Flare and solder connections coil type
With manual Without manual
in. mm in./mm in. mm operation operation
1
EVR 2 a.c. /4 6 032F1200 032F1201 032F1202
1
/4 6 032F1205 032F1206 032F1207
EVR 3
3
/8 10 032F1203 032F1204 032F1208
3
/8 10 032F1211 032F1212 032F1213
EVR 6
1
/2 12 032F1235 032F1209 032F1236
1
a.c./d.c. /2 12 032F1215 032F1217 032F1218
EVR 10 5
/8 16 032F1238 032F1214 032F1214
5
/8 16 032F1221 032F1228 032F1228
EVR 15 5
/8 16 032F1231 2) 032F1227
7
/8 22 032F1225 032F1225
7
/8 22 032F1240 032F1240
7
a.c. /8 22 032F1254
EVR 20 11/8 28 032F1244 032F1245
7
/8 22 032F1264 032F1264
d.c.
7
/8 22 032F1274
EVR 22 a.c. 13/8 35 032F3267 032F3267
11/8 032F2200 032F2201
EVR 25 28 032F2205 032F2206
13/8 35 032F2207 032F2208
13/8 35 042H1105 042H1106
EVR 32 a.c./d.c. 15/8 042H1103 042H1104
42 042H1107 042H1108
15/8 042H1109 042H1110
EVR 40 42 042H1113 042H1114
21/8 54 042H1111 042H1112

Separate valve bodies, normally open (NO) 3)


Code no.
Connection Valve body without coil 3)
Type Required
coil type Flare 1) Solder ODF
in. mm in. mm in. mm
3
EVR 6 /8 10 032F1289 032F1289 032F1290 032F1295
1
EVR 10 /2 12 032F1293 032F1293 032F1291 032F1296
5
/8 16 032F1297 032F1297 032F1299 032F1299
EVR 15 a.c./d.c.
7
/8 22 032F3270 032F3270
7
/8 22 032F1260 032F1260
EVR 20
11/8 28 032F1269 032F1279
EVR 22 a.c. 13/8 35 032F3268 032F3268
1) Valve bodies are supplied without flare nuts.
Separate flare nuts:
1
/4 in. or 6 mm, code no. 011L1101
3
/8 in. or 10 mm, code no. 011L1135
1/ in. or 12 mm, code no. 011L1103
2
5
/8 in. or 16 mm, code no. 011L1167
2) With manual operation.
3) The normal range of coils can be used for the NO valves, with the exception of the double
frequency versions of 110 V, 50/60 Hz and 220 V, 50/60 Hz.

Coils
See "Coils for solenoid valves", RD3JE.

12 Technical leaflet - RD3AD302  Danfoss A/S, 05 - 2002


Solenoid valves, type EVR 2 ® 40 - NC / NO

Ordering (continued) Separate valve bodies, normally closed (NC)


Code no.
Components Valve body + gaskets + bolts;
Flare and solder connections without coil and flanges
Type Required coil type Connection
With manual Without manual
operation operation
EVR 15 a.c./d.c. 032F1234 032F1224
a.c. Flanges 032F1253 032F1243
EVR 20
d.c. 032F1273 032F1263

Coils
See "Coils for solenoid valves", RD3JE.
Flange sets
Code no. Example
Connection EVR 15 without manual operation,
Valve type Solder Weld
code no. 032F1224
in. mm in. mm in.
1/ 027N1115
2 + 1/2 in. weld flange set,
5/
8 16 027L1117 027L1116 code no. 027N1115
EVR 15
3/ 027N1120
4
7/
+ coil with termfnal box, 220 V, 50 Hz,
22 027L1123 027L1122
8
code no. 018F6701
3/ 027N1220
4 (See "Coils for solenoid valves", RD3JE).
7/ 22 027L1223 027L1222
8
EVR 20
1 027N1225
11/8 28 027L1229 027L1228

Accessories
Description Code no.
Mounting bracket for EVR 2, 3, 6 and 10 032F0197
Strainer FA for direct mounting See "FA"

 Danfoss A/S, 05 - 2002 Technical leaflet - RD3AD302 13


Solenoid valves, type EVR 2 ® 40 - NC / NO

Capacity
Liquid capacity Qe kW R 22
Liquid capacity Qe kW at pressure drop across valve ∆p bar
Type
0.1 0.2 0.3 0.4 0.5
EVR 2 2.6 3.7 4.6 5.3 5.9
EVR 3 4.5 6.3 7.7 8.9 9.9
EVR 6 13.1 18.6 22.8 26.3 29.4
EVR 10 31.4 44.1 54.2 62.5 69.9
EVR 15 42.7 60.3 74.1 85.5 95.7
EVR 20 82.2 116.0 143.0 165.0 184.0
EVR 22 99.0 139.0 171.0 197.0 220.0
EVR 25 165.0 232.0 285.0 329.0 368.0
EVR 32 263.0 372.0 455.0 526.0 588.0
EVR 40 411.0 581.0 712.0 822.0 919.0

Liquid capacity Qe kW R 134a


Liquid capacity Qe kW at pressure drop across valve ∆p bar
Type
0.1 0.2 0.3 0.4 0.5
EVR 2 2.4 3.4 4.2 4.9 5.4
EVR 3 4.1 5.8 7.1 8.2 9.1
EVR 6 12.1 17.2 21.0 24.3 27.1
EVR 10 28.8 40.7 49.9 57.6 64.4
EVR 15 39.4 55.7 68.3 78.8 88.1
EVR 20 75.8 107.0 131.0 152.0 170.0
EVR 22 90.9 129.0 158.0 182.0 203.0
EVR 25 152.0 214.0 263.0 303.0 339.0
EVR 32 243.0 343.0 420.0 485.0 542.0
EVR 40 379.0 536.0 656.0 758.0 847.0

Liquid capacity Qe kW R 404A/R 507


Liquid capacity Qe kW at pressure drop across valve ∆p bar
Type
0.1 0.2 0.3 0.4 0.5
EVR 2 1.8 2.6 3.2 3.7 4.1
EVR 3 3.1 4.4 5.4 6.2 6.9
EVR 6 9.2 13.0 15.9 18.4 20.5
EVR 10 21.8 30.8 37.8 43.6 48.8
EVR 15 29.8 42.2 51.7 59.6 66.8
EVR 20 57.4 81.1 99.4 115.0 128.0
EVR 22 68.9 97.4 119.0 138.0 169.0
EVR 25 115.0 162.0 199.0 230.0 257.0
EVR 32 184.0 260.0 318.0 367.0 411.0
EVR 40 287.0 406.0 497.0 574.0 642.0

Capacities are based on


liquid temperature tl = +25°C ahead of valve,
evaporating temperature te = −10°C,
superheat 0 K.

Correction factors
When sizing valves, the plant capacity must be
multiplied by a correction
factor depending on liquid temperature
tl ahead of valve/evaporator.
When the corrected capacity is known, the
selection can be made from the table.
Correction factors for liquid temperature tl
tl°C −10 0 10 15 20 25 30 35 40 45 50
R 22 0.76 0.82 0.88 0.92 0.96 1.0 1.05 1.10 1.16 1.22 1.30
R 134a 0.73 0.79 0.86 0.90 0.95 1.0 1.06 1.12 1.19 1.27 1.37
R 404A/R 507 0.65 0.72 0.81 0.86 0.93 1.0 1.09 1.20 1.33 1.51 1.74

14 Technical leaflet - RD3AD302  Danfoss A/S, 05 - 2002


Solenoid valves, type EVR 2 ® 40 - NC / NO

Capacity
(continued) Liquid capacity Qe kW
R 407C
Liquid capacity Qe kW at pressure drop across valve ∆p bar
Type
0.1 0.2 0.3 0.4 0.5
EVR 2 2.4 3.4 4.3 5.0 5.3
EVR 3 4.2 5.9 7.2 8.4 9.3
EVR 6 12.3 17.5 21.4 24.7 27.6
EVR 10 29.5 41.5 50.9 58.7 65.7
EVR 15 40.1 56.7 69.7 80.4 90.0
EVR 20 77.0 109.0 134.0 155.0 172.0
EVR 22 93.1 130.0 161.0 185.2 207.0
EVR 25 155.0 218.0 268.0 309.0 346.0
EVR 32 247.0 350.0 428.0 494.0 553.0
EVR 40 386.0 546.0 669.0 773.0 864.0

Capacities are based on liquid temperature Correction factors


tl = +25°C ahead of valve, evaporating tempera- When sizing valves, the plant capacity must be
ture te = −10°C, and superheat 0 K. multiplied by a correction
factor depending on liquid temperature
tl ahead of valve/evaporator.
When the corrected capacity is known, the
selection can be made from the table.
Correction factors based on liquid temperature tl
tl°C −10 0 10 15 20 25 30 35 40 45 50
R 407C 0.71 0.78 0.85 0.89 0.94 1.0 1.06 1.14 1.23 1.33 1.46

Suction vapour capacity Qe


R 22
Pressure drop Suction vapour capacity Qe kW at evaporating temperature te °C
Type ∆p bar
–40 –30 –20 –10 0 +10
0.1 0.73 0.94 1.2 1.5 1.8 2.1
EVR 6 0.15 0.87 1.1 1.4 1.8 2.2 2.6
0.2 0.98 1.3 1.6 2.0 2.5 3.0
0.1 1.7 2.2 2.9 3.5 4.3 5.1
EVR 10 0.15 2.1 2.7 3.4 4.3 5.2 6.2
0.2 2.3 3.1 3.9 4.8 6.0 7.1
Capacities are based on liquid 0.1 2.3 3.1 4.0 4.8 5.8 6.9
temperature tl = +25°C ahead EVR 15 0.15 2.8 3.7 4.7 5.9 7.1 8.5
of evaporator. 0.2 3.2 4.2 5.3 6.6 8.2 9.8
The table values refer to the 0.1 4.6 5.9 7.6 9.3 11.2 13.3
evaporator capacity and are EVR 20 0.15 5.4 7.1 9.1 11.4 13.9 16.7
0.2 6.1 8.1 10.3 12.7 15.9 18.8
given as a function of
evaporating temperature te 0.1 5.5 7.1 9.1 11.2 13.4 16.0
EVR 22 0.15 6.5 8.5 10.7 13.7 16.4 20.0
and pressure drop ∆p across 0.2 7.3 9.7 12.3 15.2 19.0 22.6
valve.
0.1 9.1 11.8 15.2 18.6 22.4 26.6
Capacities are based on dry, EVR 25 0.15 10.9 14.2 17.9 22.8 27.4 32.6
saturated vapour ahead of 0.2 12.2 16.1 20.4 25.3 31.7 37.6
valve. 0.1 14.6 18.9 24.3 29.8 35.8 42.6
During operation with EVR 32 0.15 17.4 22.7 28.8 36.5 43.8 52.2
superheated vapour ahead of 0.2 19.6 25.7 32.6 40.5 50.7 60.2
valve, the capacities are 0.1 22.8 29.5 38.1 46.5 56.0 66.5
reduced by 4% for each 10 K EVR 40 0.15 27.2 35.4 45.0 57.0 68.6 81.5
superheat. 0.2 30.5 40.2 51.0 63.3 79.2 94.0

Correction factors
When sizing valves, the evaporator capacity
must be divided by a correction factor
depending on liquid temperature tl ahead of
expansion valve.
When the corrected capacity is known, the
selection can be made from the table.

Correction factors for liquid temperature tl


tl°C −10 0 10 15 20 25 30 35 40 45 50
R 22 0.76 0.82 0.88 0.92 0.96 1.0 1.05 1.10 1.16 1.22 1.30

 Danfoss A/S, 05 - 2002 Technical leaflet - RD3AD302 15


Solenoid valves, type EVR 2 ® 40 - NC / NO

Capacity
(continued) Suction vapour capacity Qe kW R 134a
Pressure drop Suction vapour capacity Qe kW at evaporating temperature te °C
Type across valve ∆p bar
–40 –30 –20 –10 0 +10
0.1 0.46 0.63 0.84 1.1 1.4 1.7
EVR 6 0.15 0.53 0.74 1.0 1.3 1.7 2.0
0.2 0.58 1.83 1.1 1.5 1.9 2.4
0.1 1.1 1.5 2.0 2.6 3.3 4.0
EVR 10 0.15 1.3 1.8 2.4 3.1 4.0 4.9
0.2 1.4 2.0 2.7 3.5 4.5 5.7
0.1 1.5 2.1 2.7 3.6 4.5 5.5
EVR 15 0.15 1.7 2.4 3.3 4.2 5.5 6.7
0.2 1.9 2.7 3.7 4.8 6.1 7.8
0.1 2.9 4.0 5.3 7.0 8.6 10.6
EVR 20 0.15 3.3 4.7 6.3 8.1 10.6 13.0
0.2 3.7 5.2 7.1 9.3 11.7 15.0
0.1 3.4 4.7 6.3 8.3 10.3 12.7
EVR 22 0.15 4.0 5.6 7.5 9.7 12.7 15.5
0.2 4.4 6.2 8.5 11.1 14.0 17.9
0.1 5.8 7.9 10.5 13.9 17.2 21.1
EVR 25 0.15 6.6 9.3 12.5 16.3 21.1 25.9
0.2 7.3 10.4 14.1 18.5 23.4 29.9
0.1 9.3 12.6 16.8 22.2 27.7 33.8
EVR 32 0.15 10.6 14.9 20.0 26.1 33.8 41.4
0.2 11.7 16.6 22.6 29.6 37.4 47.8
0.1 14.5 19.8 26.3 34.8 43.3 52.8
EVR 40 0.15 16.5 23.3 31.3 40.8 52.8 64.8
0.2 18.3 26.0 35.3 46.3 58.5 74.8

Suction vapour capacity Qe kW R 404A/R 507


Pressure drop Suction vapour capacity Qe kW at evaporating temperature te °C
Type across valve ∆p bar
–40 –30 –20 –10 0 +10
0.1 0.62 0.8 1.1 1.3 1.6 2.0
EVR 6 0.15 0.73 0.97 1.3 1.6 2.0 2.4
0.2 0.82 1.1 1.4 1.8 2.3 2.8
0.1 1.5 1.9 2.5 3.2 3.9 4.7
EVR 10 0.15 1.7 2.3 3.0 3.9 4.8 5.8
0.2 2.0 2.6 3.4 4.3 5.5 6.7
Capacities are based on liquid 0.1 2.0 2.6 3.5 4.3 5.3 6.4
temperature tl = +25°C ahead EVR 15 0.15 2.4 3.2 4.1 5.3 6.5 7.9
of evaporator. 0.2 2.7 3.6 4.7 5.9 7.5 9.1
The table values refer to the 0.1 3.9 5.0 6.7 8.3 10.2 12.3
evaporator capacity and are EVR 20 0.15 4.6 6.1 7.9 10.2 12.5 15.2
given as a function of 0.2 5.2 6.9 9.0 11.4 14.4 17.5
evaporating temperature te 0.1 4.6 6.0 8.0 10.0 12.2 14.8
and pressure drop ∆p across EVR 22 0.15 5.5 7.3 9.5 12.2 15.0 18.2
0.2 6.2 8.3 10.8 13.6 17.3 21.0
valve.
Capacities are based on dry, 0.1 7.7 10.1 13.3 16.6 20.4 24.6
EVR 25 0.15 9.1 12.1 15.8 20.4 25.0 30.3
saturated vapour ahead of 0.2 10.3 13.8 18.0 22.7 28.8 35.0
valve.
During operation with 0.1 12.3 16.2 21.3 26.6 32.6 39.4
EVR 32 0.15 14.6 19.4 25.3 32.6 40.0 48.5
superheated vapour ahead of 0.2 16.5 22.0 28.8 36.3 46.1 56.0
valve, the capacities are 0.1 19.3 25.3 33.3 41.5 51.0 61.5
reduced by 4% for each 10 K EVR 40 0.15 22.8 30.3 39.5 51.0 62.5 75.6
superheat. 0.2 25.8 34.5 45.0 56.8 72.1 87.5

Correction factors
When sizing valves, the plant capacity must be
multiplied by a correction
factor depending on liquid temperature
tl ahead of valve/evaporator.
When the corrected capacity is known, the
selection can be made from the table.

Correction factors based on liquid temperature tl


tl°C −10 0 10 15 20 25 30 35 40 45 50
R 134a 0.73 0.79 0.86 0.90 0.95 1.0 1.06 1.12 1.19 1.27 1.37
R 404A/R 507 0.65 0.72 0.81 0.86 0.93 1.0 1.09 1.20 1.33 1.51 1.74

16 Technical leaflet - RD3AD302  Danfoss A/S, 05 - 2002


Solenoid valves, type EVR 2 ® 40 - NC / NO

Capacity
(continued)
R 407C
Pressure drop Suction vapour capacity Qe kW at evaporating temperature te °C
Type across valve ∆p bar
–40 –30 –20 –10 0 +10
0.1 0.61 0.81 1.1 1.4 1.7 2.0
EVR 6 0.15 0.72 0.95 1.3 1.7 2.1 2.5
0.2 0.81 1.1 1.4 1.8 2.4 2.9
0.1 1.4 1.9 2.6 3.2 4.0 4.9
EVR 10 0.15 1.7 2.3 3.0 4.0 4.9 6.0
0.2 1.9 2.7 3.5 4.4 5.6 6.9
0.1 1.9 2.7 3.6 4.4 5.5 6.7
EVR 15 0.15 2.3 3.2 4.2 5.4 6.7 8.2
0.2 2.7 3.6 4.7 6.1 7.7 9.5
0.1 3.8 5.1 6.8 8.6 10.5 12.9
EVR 20 0.15 4.5 6.1 8.1 10.5 13.1 16.2
Capacities are based on liquid 0.2 5.1 7.0 9.2 11.7 14.9 18.2
temperature tl = +25°C ahead of 0.1 4.6 6.1 8.1 10.3 12.6 15.5
evaporator. EVR 22 0.15 5.4 7.3 9.5 12.6 15.4 19.4
The table values refer to the 0.2 6.1 8.3 11.0 14.0 17.9 21.9
evaporator capacity and are given
0.1 7.6 10.2 13.5 17.1 21.1 25.8
as a function of evaporating EVR 25 0.15 9.1 12.2 15.9 21.0 25.8 31.6
temperature te and pressure drop ∆p 0.2 10.1 13.9 18.2 23.3 29.8 36.5
across valve.
Capacities are based on dry, 0.1 12.1 16.3 21.6 27.4 33.7 41.3
EVR 32 0.15 14.4 19.5 25.6 33.6 41.2 50.6
saturated vapour ahead of valve. 0.2 16.3 22.1 29.0 37.3 47.7 58.4
During operation with superheated
vapour ahead of valve, the capacities 0.1 18.9 25.4 33.9 42.8 52.6 64.5
are reduced by 4% for each 10 K EVR 40 0.15 22.6 30.4 40.1 52.4 64.5 79.1
0.2 25.3 34.6 45.4 58.2 74.4 91.2
superheat.

Correction factors
When sizing valves, the evaporator capacity
must be multiplied by a correction factor
depending on liquid temperature tl ahead of
expansion valve. When the corrected capacity is
known, the selection can be made from the
table.
Correction factors based on liquid temperature tl
tl°C −10 0 10 15 20 25 30 35 40 45 50
R 407C 0.71 0.78 0.85 0.89 0.94 1.0 1.06 1.14 1.23 1.33 1.46

Hot gas defrosting Heat recovery


With hot gas defrosting it is not normally possible The following is given:
to select a valve from condensing temperature tc Refrigerant = R 22
and evaporating temperature te. Evaporating temperature te = – 30°C
This is because the pressure in the evaporator Condensing temperature tc = + 40°C
as a rule quickly rises to a value near that of the Hot gas temperature ahead of valve th = + 85°C
condensing pressure. It remains at this value Heat recovery condenser yield Qh = 8 kW
until the defrosting is finished. The capacity table for R 22 with tc = + 40°C gives
In most cases therefore, the valve will be the the capacity for an EVR 10 as 8.9 kW, when
selected from condensing temperature tc and pressure drop ∆p is 0.2 bar.
pressure drop ∆p across the valve, as shown in The correction factor for te = – 30°C is given in
the example for heat recovery. the table as 0.94.
The correction for hot gas temperature
th = + 85°C has been calculated as 4% which
corresponds to a factor of 1.04.
Qh must be corrected with factors found:
With ∆p = 0.2 bar is
Qh = 8.9 x 0.94 x 1.04 = 8.7 kW.
With ∆p = 0.1 bar, Qh becomes only
6.3 x 0.94 x 1.04 = 6.2 kW.
An EVR 6 would also be able to give the required
capacity, but with ∆p at approx. 1 bar.
The EVR 6 is therefore too small.
The EVR is so large that it is doubtful whether
the necessary ∆p of apprx. 0.1 bar could be
obtained.
An EVR 15 would therefore be too large.
Result: An EVR 10 is the correct valve for the
given conditions.

 Danfoss A/S, 05 - 2002 Technical leaflet - RD3AD302 17


Solenoid valves, type EVR 2 ® 40 - NC / NO

Capacity
(continued) Hot gas capacity Qh kW R 22
Hot gas capacity Qh kW
Pressure drop Evaporating temp. te=-10°C. Hot gas temp. th=tc +25°C. Subcooling ∆tsub =4 K
Type
across valve Condensing temperature tc °C
∆p bar
+20 +30 +40 +50 +60
0.1 0.47 0.50 0.53 0.54 0.55
0.2 0.67 0.71 0.75 0.77 0.78
EVR 2 0.4 0.96 1.02 1.07 1.10 1.11
0.8 1.32 1.37 1.48 1.57 1.59
1.6 1.87 1.99 2.08 2.16 2.19
0.1 0.80 0.85 0.89 0.92 0.93
0.2 1.14 1.20 1.26 1.30 1.32
EVR 3 0.4 1.63 1.72 1.80 1.85 1.87
0.8 2.23 2.31 2.49 2.65 2.68
1.6 3.15 3.35 3.52 3.64 3.69
0.1 2.4 2.5 2.6 2.7 2.8
0.2 3.4 3.6 3.7 3.4 3.9
EVR 6 0.4 4.8 5.1 5.3 5.5 5.6
0.8 6.6 6.8 7.4 7.9 7.9
1.6 9.3 9.9 10.4 10.8 10.9
0.1 5.6 6.0 6.3 6.5 6.5
0.2 8.0 8.5 8.9 9.2 9.3
EVR 10 0.4 11.4 12.1 12.7 13.0 13.2
0.8 15.7 16.2 17.5 18.7 18.9
1.6 22.2 23.6 24.8 25.6 26.0
0.1 7.7 8.2 8.6 8.8 8.9
0.2 11.0 11.6 12.1 12.5 12.7
EVR 15 0.4 15.7 16.6 17.3 17.8 18.0
0.8 21.5 22.2 24.0 25.5 25.9
1.6 30.3 32.3 33.9 35.0 35.5
0.1 14.8 15.7 16.5 17.0 17.2
0.2 21.1 22.3 23.4 24.1 24.4
EVR 20 0.4 30.0 31.9 33.3 34.3 34.7
0.8 41.3 42.7 46.2 49.1 49.6
1.6 58.3 62.1 65.2 67.4 68.4
0.1 17.8 18.8 19.7 20.4 20.6
0.2 25.3 26.8 28.0 28.9 29.3
EVR 22 0.4 36.1 38.3 40.0 41.2 41.6
0.8 49.5 51.2 55.4 58.9 59.5
1.6 70.0 74.5 78.2 80.8 82.0
0.1 29.6 31.4 32.9 34.0 34.4
0.2 42.1 44.6 46.7 48.2 48.8
EVR 25 0.4 60.2 63.8 66.6 68.6 69.4
0.8 82.5 87.9 92.3 98.2 99.2
1.6 117.0 124.0 130.0 135.0 137.0
0.1 47.4 50.2 52.6 54.4 55.0
0.2 67.4 71.4 74.7 77.1 78.1
An increase in hot gas temperature EVR 32 0.4 96.3 102.0 107.0 110.0 111.0
th of 10 K, based on t h = tc +25°C, 0.8 132.0 140.0 148.0 157.0 159.0
reduces valve capacity approx. 2% 1.6 187.0 199.0 209.0 216.0 219.0
and vice versa.
0.1 74.0 78.5 82.3 85.0 86.0
A change in evaporating temperature 0.2 105.0 112.0 117.0 121.0 122.0
te changes valve capacity; see EVR 40 0.4 151.0 159.0 167.0 172.0 174.0
correction factor table below. 0.8 206.0 222.0 231.0 246.0 248.0
1.6 291.0 310.0 326.0 337.0 342.0

Correction factors
When sizing valves, the table value must be
multiplied by a correction factor depending on
evaporating temperature te.

Correction factors for evaporating temperatur te


te °C −40 −30 −20 −10 0 +10
R 22 0.90 0.94 0.97 1.0 1.03 1.05

18 Technical leaflet - RD3AD302  Danfoss A/S, 05 - 2002


Solenoid valves, type EVR 2 ® 40 - NC / NO

Capacity
(continued) Hot gas capacity Qh kW R 134a
Hot gas capacity Qh kW

Pressure drop Evaporating temp. te=-10°C. Hot gas temp. th=tc +25°C. Subcooling ∆tsub =4 Kv
Type
across valve Condensing temperature tc °C
∆p bar +20 +30 +40 +50 +60
0.1 0.38 0.40 0.41 0.42 0.42
0.2 0.54 0.57 0.59 0.60 0.59
EVR 2 0.4 0.74 0.82 0.84 0.86 0.85
0.8 1.06 1.13 1.17 1.23 1.22
1.6 1.50 1.61 1.67 1.70 1.69
0.1 0.64 0.67 0.70 0.71 0.71
0.2 0.91 0.96 0.99 1.01 1.00
EVR 3 0.4 1.26 1.38 1.42 1.44 1.43
0.8 1.79 1.90 1.98 2.08 2.05
1.6 2.57 2.72 2.82 2.88 2.86
0.1 1.88 1.99 2.07 2.11 2.09
0.2 2.69 2.84 2.95 3.00 2.97
EVR 6 0.4 3.73 4.08 4.22 4.28 4.23
0.8 5.29 5.62 5.86 6.16 6.08
1.6 7.61 8.05 8.37 8.52 8.46
0.1 4.5 4.7 4.9 5.0 5.0
0.2 6.4 6.8 7.0 7.1 7.1
EVR 10 0.4 8.9 9.7 10.0 10.2 10.1
0.8 12.6 13.3 13.9 14.6 14.4
1.6 18.1 19.1 19.9 20.2 20.1
0.1 6.1 6.5 6.7 6.7 6.8
0.2 8.7 9.2 9.6 9.7 9.7
EVR 15 0.4 12.1 13.3 13.7 13.9 13.8
0.8 17.2 18.3 19.0 20.0 19.8
1.6 24.8 26.2 27.2 27.7 27.5
0.1 11.8 12.5 13.0 13.2 13.1
0.2 16.8 17.8 18.4 18.7 18.6
EVR 20 0.4 23.4 25.5 26.4 26.7 26.5
0.8 33.1 35.1 36.6 38.5 38.0
1.6 47.6 50.3 52.3 53.3 52.9
0.1 14.1 15.0 15.5 15.8 15.7
0.2 20.2 21.3 22.1 22.6 22.3
EVR 22 0.4 28.0 30.6 31.6 32.1 31.7
0.8 39.7 42.2 43.9 46.2 45.6
1.6 57.1 60.4 62.8 63.9 63.5
0.1 23.6 24.9 25.9 26.4 26.2
0.2 33.6 35.5 36.8 37.4 37.1
EVR 25 0.4 46.6 51.0 52.7 53.4 52.9
0.8 66.2 70.2 73.2 77.0 76.0
1.6 95.2 101.0 105.0 107.0 106.0
0.1 37.6 39.8 41.4 42.1 41.8
0.2 53.8 56.8 58.9 59.8 59.4
An increase in hot gas temperature EVR 32 0.4 74.7 81.6 84.3 85.4 84.6
th of 10 K, based on th = tc +25°C, 0.8 106.0 112.0 117.0 123.0 122.0
reduces valve capacity approx. 2% 1.6 152.0 161.0 167.0 170.0 169.0
and vice versa.
0.1 58.8 62.3 64.7 65.8 65.3
A change in evaporating temperature 0.2 84.1 88.8 92.1 93.5 92.8
te changes valve capacity; see EVR 40 0.4 117.0 127.0 132.0 134.0 132.0
correction factor table below. 0.8 166.0 176.0 183.0 192.0 190.0
1.6 238.0 252.0 262.0 266.0 265.0

Correction factors
When sizing valves, the table value must be
multiplied by a correction factor depending on
evaporating temperature te.
Correction factors for evaporating temperatur te
te °C −40 −30 −20 −10 0 +10
R 134a 0.88 0.92 0.98 1.0 1.04 1.08

 Danfoss A/S, 05 - 2002 Technical leaflet - RD3AD302 19


Solenoid valves, type EVR 2 ® 40 - NC / NO

Capacity
(continued) Hot gas capacity Qh kW R 404A/R 507
Hot gas capacity Qh kW
Evaporating temp. te=-10°C. Hot gas temp. th=tc +25°C. Subcooling ∆tsub =4 K
Type Pressure drop
across valve Condensing temperature tc °C
∆p bar +20 +30 +40 +50 +60
0.1 0.43 0.44 0.43 0.40 0.37
0.2 0.61 0.62 0.61 0.58 0.53
EVR 2 0.4 0.87 0.87 0.87 0.82 0.75
0.8 1.19 1.21 1.21 1.19 1.07
1.6 1.68 1.70 1.69 1.62 1.48
0.1 0.73 0.74 0.73 0.69 0.63
0.2 1.03 1.04 1.03 0.98 0.89
EVR 3 0.4 1.46 1.48 1.47 1.39 1.27
0.8 2.01 2.04 2.03 2.00 1.81
1.6 2.83 2.87 2.84 2.74 2.50
0.1 2.16 2.18 2.15 2.05 1.86
0.2 3.03 3.08 3.05 2.90 2.64
EVR 6 0.4 4.34 4.38 4.35 4.13 3.76
0.8 5.94 6.05 6.02 5.92 5.37
1.6 8.37 8.52 8.43 8.10 7.40
0.1 5.1 5.2 5.1 4.9 4.4
0.2 7.2 7.3 7.3 6.9 6.3
EVR 10 0.4 10.3 10.4 10.3 9.8 8.9
0.8 14.1 14.4 14.3 14.1 12.8
1.6 19.9 20.3 20.0 19.2 17.6
0.1 7.0 7.1 7.0 6.7 6.1
0.2 9.9 10.0 9.9 9.4 8.6
EVR 15 0.4 14.1 14.3 14.2 13.4 12.2
0.8 19.3 19.7 19.6 19.2 17.5
1.6 27.2 27.7 27.6 26.3 24.1
0.1 13.4 13.7 13.5 12.8 11.6
0.2 18.9 19.2 19.1 18.2 16.5
EVR 20 0.4 27.1 27.4 27.2 25.8 23.5
0.8 37.1 37.8 37.7 37.0 33.6
1.6 52.4 53.3 52.6 50.6 46.2
0.1 16.1 16.4 16.1 15.4 14.0
0.2 22.7 23.1 22.9 21.8 19.8
EVR 22 0.4 32.5 32.9 32.7 31.0 28.2
0.8 44.5 45.4 45.2 44.4 40.3
1.6 62.8 64.0 63.2 60.8 55.5
0.1 26.8 27.4 26.9 25.6 23.3
0.2 37.9 38.4 38.2 36.3 33.0
EVR 25 0.4 54.2 54.9 54.5 51.7 47.0
0.8 74.2 75.6 75.3 74.0 67.2
1.6 105.0 107.0 105.0 101.0 92.5
0.1 43.0 43.8 43.0 40.9 37.3
0.2 60.6 61.4 61.1 58.1 52.8
An increase in hot gas temperature EVR 32 0.4 86.7 87.8 87.2 82.7 75.2
th of 10 K, based on t h = tc +25°C, 0.8 119.0 121.0 120.0 118.0 107.0
reduces valve capacity approx. 2% 1.6 167.0 171.0 168.0 162.0 148.0
and vice versa.
0.1 67.0 68.5 67.3 64.0 58.3
A change in evaporating temperature 0.2 94.8 96.0 95.5 90.8 82.5
te changes valve capacity; see EVR 40 0.4 136.0 137.0 136.0 129.0 117.0
correction factor table below. 0.8 186.0 189.0 188.0 185.0 168.0
1.6 262.0 266.0 263.0 253.0 231.0

Correction factors
When sizing valves, the table value must be
multiplied by a correction factor depending on
evaporating temperature te.
Correction factors for evaporating temperatur te
te °C −40 −30 −20 −10 0 +10
R 404A/R 507 0.86 0.88 0.93 1.0 1.03 1.07

20 Technical leaflet - RD3AD302  Danfoss A/S, 05 - 2002


Solenoid valves, type EVR 2 ® 40 - NC / NO

Capacity
(continued) Hot gas capacity Qh kW R 407C
Hot gas capacity Qh kW
Evaporating temp. te=-10°C. Hot gas temp. th=tc +25°C. Subcooling ∆tsub =4 K
Type Pressure drop
across valve Condensing temperature tc °C
∆p bar +20 +30 +40 +50 +60
0.1 0.53 0.55 0.57 0.56 0.54
0.2 0.75 0.78 0.80 0.80 0.76
EVR 2 0.4 1.08 1.12 1.14 1.14 1.09
0.8 1.48 1.51 1.58 1.63 1.56
1.6 2.09 2.19 2.23 2.25 2.15
0.1 0.9 0.94 0.95 0.96 0.91
0.2 1.28 1.32 1.35 1.35 1.29
EVR 3 0.4 1.83 1.89 1.93 1.92 1.83
0.8 2.50 2.54 2.66 2.76 2.63
1.6 3.53 3.69 3.77 3.79 3.62

0.1 2.7 2.8 2.8 2.8 2.7


0.2 3.8 4.0 4.0 3.5 3.8
EVR 6 0.4 5.4 5.6 5.7 5.7 5.5
0.8 7.4 7.5 7.9 8.2 7.7
1.6 10.4 10.9 11.1 11.2 10.7

0.1 6.3 6.6 6.7 6.8 6.4


0.2 9.0 9.4 9.5 9.6 9.1
EVR 10 0.4 12.8 13.3 13.6 13.5 12.9
0.8 17.6 17.8 18.7 19.4 18.5
1.6 24.9 26.0 26.5 26.6 25.5

0.1 8.6 9.0 9.2 9.2 8.7


0.2 12.3 12.8 12.9 13 12.4
EVR 15 0.4 17.6 18.3 18.5 18.5 17.6
0.8 24.1 24.4 25.7 26.5 25.4
1.6 33.9 35.5 36.3 36.4 34.8

0.1 16.6 17.3 17.7 17.7 16.9


0.2 23.6 24.5 25.0 25.1 23.9
EVR 20 0.4 33.6 35.1 35.6 35.7 34.0
0.8 46.3 47 49.4 51.1 48.6
1.6 65.3 68.3 69.8 70.1 67.0

0.1 19.9 20.7 21.1 21.2 20.2


0.2 28.3 29.5 30.0 30.1 28.7
EVR 22 0.4 40.4 42.1 42.8 42.8 40.8
0.8 55.4 56.3 59.3 61.3 58.3
1.6 78.4 82.0 83.7 84 80.4

0.1 33.2 34.5 35.2 35.4 33.7


0.2 47.2 49.1 50.0 50.1 47.8
EVR 25 0.4 67.4 70.2 71.3 71.3 68.0
0.8 92.4 96.7 98.8 102.1 97.2
1.6 131.0 136.4 139.1 140.4 134.3

0.1 53.1 55.2 56.3 56.6 53.9


0.2 75.5 78.5 79.9 80.2 76.5
An increase in hot gas temperature EVR 32 0.4 107.9 112.2 114.5 114.4 108.8
th of 10 K, based on th = tc +25°C, 0.8 147.8 154.0 158.4 163.3 155.8
reduces valve capacity approx. 2% 1.6 209.4 218.9 223.6 224.6 214.6
and vice versa.
0.1 82.9 86.4 88.1 88.4 84.3
A change in evaporating temperature 0.2 117.6 123.2 125.2 125.8 119.6
te changes valve capacity; see EVR 40 0.4 169.1 174.9 178.7 178.9 170.5
correction factor table below. 0.8 230.7 244.2 247.2 255.8 243.0
1.6 325.9 341.0 348.8 350.5 335.2

Correction factors
When sizing valves, the table value must be
multiplied by a correction factor depending on
evaporating temperature te.

Correction factors for evaporating temperatur te


te °C −40 −30 −20 −10 0 +10
R 407C 0.90 0.94 0.97 1.0 1.03 1.05

 Danfoss A/S, 05 - 2002 Technical leaflet - RD3AD302 21


Solenoid valves, type EVR 2 ® 40 - NC / NO

Capacity
(continued) Hot gas capacity Gh kg/s R 22
Hot gas Condensing Hot gas capacity Gh kg/s at pressure drop across valve ∆p bar
Type temperature temperature
t h °C t c °C 0.5 1 2 3 4 5 6 7 8
+25 0.005 0.007 0.01 0.011 0.012 0.012 0.012 0.012 0.012
EVR 2 +35 0.006 0.009 0.011 0.013 0.014 0.015 0.015 0.015 0.015
+45 0.007 0.01 0.013 0.016 0.017 0.018 0.019 0.019 0.02
+25 0.009 0.012 0.016 0.019 0.02 0.02 0.02 0.02 0.02
EVR 3 +35 0.01 0.014 0.019 0.022 0.024 0.025 0.026 0.026 0.026
+45 0.012 0.016 0.022 0.026 0.029 0.031 0.032 0.033 0.033
+25 0.027 0.037 0.049 0.055 0.058 0.059 0.059 0.059 0.059
EVR 6 +35 0.031 0.043 0.057 0.067 0.072 0.075 0.077 0.077 0.077
+45 0.035 0.049 0.066 0.078 0.086 0.092 0.095 0.097 0.098
+25 0.064 0.088 0.116 0.131 0.139 0.14 0.14 0.14 0.14
EVR 10 +35 0.074 0.102 0.137 0.158 0.172 0.179 0.182 0.182 0.182
+45 0.084 0.116 0.158 0.185 0.205 0.218 0.227 0.231 0.232
+25 0.084 0.116 0.153 0.173 0.182 0.184 0.184 0.184 0.184
EVR 15 +35 0.097 0.134 0.18 0.208 0.226 0.236 0.239 0.239 0.239
+45 0.11 0.153 0.208 0.244 0.269 0.287 0.298 0.304 0.305
+90
+25 0.169 0.231 0.305 0.346 0.365 0.368 0.368 0.368 0.368
EVR 20 +35 0.194 0.267 0.359 0.416 0.452 0.472 0.478 0.478 0.478
+45 0.22 0.305 0.415 0.488 0.539 0.574 0.597 0.608 0.611
+25 0.203 0.277 0.366 0.415 0.438 0.442 0.442 0.442 0.442
EVR 22 +35 0.279 0.32 0.431 0.499 0.542 0.566 0.574 0.574 0.574
+45 0.264 0.366 0.498 0.586 0.647 0.689 0.716 0.722 0.733
+25 0.331 0.453 0.599 0.677 0.715 0.722 0.722 0.722 0.722
EVR 25 +35 0.38 0.524 0.704 0.816 0.886 0.925 0.938 0.938 0.938
+45 0.431 0.598 0.814 0.956 1.056 1.125 1.169 1.192 1.197
+25 0.539 0.739 0.976 1.106 1.168 1.179
EVR 32 +35 0.619 0.856 1.15 1.331 1.446 1.509 1.531
+45 0.704 0.978 1.329 1.562 1.723 1.837 1.909 1.947 1.955
+25 0.843 1.155 1.525 1.728 1.825 1.843
EVR 40 +35 0.968 1.338 1.798 2.08 2.26 2.358 2.393
+45 1.1 1.528 2.078 2.44 2.693 2.87 2.983 3.043 3.055

R 134a
Hot gas Condensing Hot gas capacity Gh kg/s at pressure drop across valve ∆p bar
Type temperature temperature
t h °C t c °C 0.5 1 2 3 4 5 6 7 8
+25 0.005 0.007 0.008 0.008 0.008
EVR 2 +35 0.006 0.008 0.01 0.011 0.012 0.012 0.012
+45 0.007 0.009 0.012 0.014 0.015 0.015 0.015 0.015 0.015
+25 0.008 0.011 0.011 0.014 0.014
EVR 3 +35 0.009 0.013 0.016 0.018 0.018 0.018 0.018
+45 0.01 0.016 0.02 0.023 0.025 0.025 0.025 0.025 0.025
+25 0.024 0.032 0.04 0.041 0.041
EVR 6 +35 0.028 0.038 0.049 0.055 0.056 0.056 0.056
+45 0.032 0.045 0.059 0.068 0.072 0.073 0.073 0.073 0.073
+25 0.057 0.075 0.094 0.098 0.098
EVR 10 +35 0.066 0.09 0.117 0.13 0.132 0.132 0.132
+45 0.076 0.107 0.141 0.161 0.17 0.172 0.172 0.172 0.172
+25 0.074 0.1 0.124 0.129 0.129
EVR 15 +35 0.087 0.119 0.154 0.171 0.167 0.167 0.167
+45 0.1 0.14 0.185 0.212 0.223 0.225 0.225 0.225 0.225
+60
+25 0.149 0.199 0.247 0.258 0.258
EVR 20 +35 0.174 0.238 0.307 0.341 0.347 0.347 0.347
+45 0.2 0.28 0.37 0.423 0.447 0.452 0.452 0.452 0.452
+25 0.179 0.239 0.296 0.31 0.31
EVR 22 +35 0.209 0.286 0.368 0.409 0.416 0.416 0.416
+45 0.24 0.336 0.444 0.508 0.536 0.542 0.542 0.542 0.542
+25 0.292 0.391 0.486 0.506 0.506
EVR 25 +35 0.341 0.467 0.602 0.668 0.679 0.679 0.679
+45 0.393 0.549 0.725 0.83 0.876 0.885 0.885 0.885 0.885
+25 0.478 0.638 0.793 0.826 0.826
EVR 32 +35 0.556 0.763 0.994 1.091 1.108 1.108 1.108
+45 0.641 0.897 1.197 1.354 1.432 1.446 1.446 1.446 1.446
+25 0.747 0.998 1.24 1.291 1.291
An increase in hot gas temperature EVR 40 +35 0.87 1.192 1.553 1.704 1.731 1.731 1.731
th of 10 K reduces valve capacity +45 1.002 1.402 1.87 2.117 2.237 2.259 2.259 2.259
approx. 2% and vice versa.

22 Technical leaflet - RD3AD302  Danfoss A/S, 05 - 2002


Solenoid valves, type EVR 2 ® 40 - NC / NO

Capacity
(continued) Hot gas capacity Gh kg/s R 404A/R 507
Hot gas Condensing Hot gas capacity Gh kg/s at pressure drop across valve ∆p bar
Type temperature temperature
th °C tc °C 0.5 1 2 3 4 5 6 7 8
+25 0.007 0.009 0.012 0.014 0.016 0.016 0.016 0.016 0.016
EVR 2 +35 0.008 0.011 0.014 0.017 0.019 0.02 0.02 0.02 0.02
+45 0.009 0.012 0.016 0.019 0.021 0.024 0.025 0.025 0.025
+25 0.011 0.016 0.021 0.024 0.026 0.026 0.027 0.027 0.027
EVR 3 +35 0.013 0.018 0.024 0.029 0.031 0.033 0.035 0.035 0.035
+45 0.015 0.02 0.028 0.032 0.037 0.039 0.041 0.043 0.043
+25 0.034 0.047 0.062 0.072 0.077 0.079 0.08 0.08 0.08
EVR 6 +35 0.038 0.054 0.072 0.085 0.093 0.098 0.101 0.101 0.102
+45 0.043 0.061 0.082 0.097 0.108 0.116 0.122 0.126 0.128
+25 0.08 0.11 0.148 0.17 0.183 0.188 0.19 0.19 0.19
EVR 10 +35 0.091 0.127 0.171 0.2 0.22 0.233 0.241 0.241 0.243
+45 0.102 0.143 0.194 0.23 0.257 0.277 0.288 0.3 0.303
+25 0.105 0.146 0.195 0.224 0.24 0.247 0.249 0.249 0.249
EVR 15 +35 0.12 0.167 0.224 0.253 0.289 0.307 0.316 0.317 0.32
+45 0.135 0.189 0.225 0.303 0.339 0.365 0.38 0.393 0.399
+60
+25 0.21 0.29 0.39 0.448 0.48 0.495 0.5 0.5 0.5
EVR 20 +35 0.239 0.333 0.45 0.526 0.58 0.614 0.632 0.633 0.639
+45 0.27 0.375 0.51 0.606 0.677 0.729 0.76 0.785 0.799
+25 0.252 0.348 0.468 0.538 0.576 0.594 0.6 0.6 0.6
EVR 22 +35 0.287 0.4 0.54 0.631 0.696 0.737 0.758 0.76 0.767
+45 0.324 0.45 0.612 0.727 0.812 0.875 0.912 0.942 0.959
+25 0.411 0.57 0.763 0.878 0.942 0.969 0.978 0.978 0.978
EVR 25 +35 0.468 0.653 0.881 1.032 1.136 1.203 1.239 1.241 1.253
+45 0.529 0.734 1.0 1.188 1.326 1.43 1.49 1.539 1.566
+25 0.672 0.931 1.245 1.432 1.539 1.581 1.581 1.581 1.581
EVR 32 +35 0.765 1.069 1.436 1.686 1.854 1.964 2.022 2.025 2.025
+45 0.862 1.198 1.632 1.939 1.836 2.34 2.433 2.513 2.557
+25 1.05 1.454 1.946 2.238 2.406 2.471 2.471 2.471 2.471
EVR 40 +35 1.195 1.657 2.245 2.635 2.897 3.068 3.161 3.166 3.166
+45 1.348 1.873 2.55 3.03 3.384 3.65 3.801 3.926 3.995

Hot gas capacity Gh kg/s R 407C


Hot gas Condensing Hot gas capacity Gh kg/s at pressure drop across valve ∆p bar
Type temperature temperature
th °C tk °C 0.5 1 2 3 4 5 6 7 8
+25 0.0054 0.0076 0.0108 0.0118 0.0130 0.0132 0.0132 0.0132 0.0132
EVR 2 +35 0.0065 0.0097 0.0118 0.0140 0.0151 0.0165 0.0165 0.0165 0.0165
+45 0.0076 0.0108 0.0140 0.0173 0.0184 0.0198 0.0209 0.0209 0.022
+25 0.010 0.013 0.017 0.021 0.022 0.022 0.022 0.022 0.022
EVR 3 +35 0.011 0.015 0.021 0.024 0.026 0.028 0.029 0.029 0.029
+45 0.013 0.017 0.024 0.028 0.032 0.034 0.036 0.037 0.037
+25 0.029 0.040 0.053 0.06 0.063 0.065 0.065 0.065 0.065
EVR 6 +35 0.033 0.046 0.062 0.073 0.078 0.083 0.085 0.085 0.085
+45 0.038 0.053 0.071 0.085 0.094 0.101 0.105 0.108 0.109
+25 0.069 0.095 0.125 0.143 0.152 0.154 0.155 0.155 0.155
EVR 10 +35 0.08 0.11 0.148 0.172 0.187 0.197 0.202 0.202 0.202
+45 0.091 0.125 0.171 0.202 0.223 0.24 0.252 0.256 0.258
+25 0.091 0.125 0.165 0.189 0.198 0.202 0.204 0.204 0.204
EVR 15 +35 0.105 0.145 0.194 0.227 0.246 0.26 0.265 0.265 0.265
+45 0.119 0.165 0.225 0.266 0.293 0.316 0.331 0.337 0.339
+90
+25 0.183 0.249 0.329 0.377 0.398 0.405 0.408 0.408 0.408
EVR 20 +35 0.21 0.288 0.388 0.453 0.493 0.519 0.531 0.531 0.531
+45 0.238 0.329 0.448 0.532 0.588 0.631 0.663 0.675 0.678
+25 0.219 0.299 0.395 0.452 0.477 0.486 0.491 0.491 0.491
EVR 22 +35 0.301 0.346 0.465 0.544 0.591 0.623 0.637 0.637 0.637
+45 0.285 0.395 0.538 0.639 0.705 0.758 0.795 0.801 0.814
+25 0.357 0.489 0.647 0.738 0.779 0.794 0.801 0.801 0.801
EVR 25 +35 0.41 0.566 0.76 0.889 0.966 1.018 1.041 1.041 1.041
+45 0.465 0.646 0.879 1.042 1.151 1.238 1.298 1.323 1.329
+25 0.582 0.798 1.054 1.206 1.273 1.297
EVR 32 +35 0.669 0.924 1.242 1.451 1.576 1.66 1.699
+45 0.76 1.056 1.435 1.703 1.878 2.021 2.119 2.161 2.17
An increase in hot gas temperature +25 0.91 1.247 1.647 1.884 1.989 2.027
th of 10 K reduces valve capacity EVR 40 +35 1.045 1.445 1.942 2.267 2.463 2.594 2.656
approx. 2% and vice versa. +45 1.188 1.65 2.244 2.66 2.935 3.157 3.311 3.378 3.391

 Danfoss A/S, 05 - 2002 Technical leaflet - RD3AD302 23


Solenoid valves, type EVR 2 ® 40 - NC / NO

Design / Function

EVR 2 (NC)

EVR 10 (NC)

EVR 10 (NO)

EVR 25 (NC) EVR 32 and 40 (NC)

4. Coil EVR solenoid valves are designed on two different becomes connected to the outlet side of the valve.
16. Armature principles: The differential pressure between inlet and outlet
18. Valve plate / Pilot valve plate 1. Direct operation sides then presses the diaphragm away from the
20. Earth terminal
24. Connection for flexible steel
2. Servo operation main orifice and opens it for full flow. Therefore a
hose certain minimum differential pressure is
28. Gasket 1. Direct operation necessary to open the valve and keep it open.
29. Pilot orifice EVR 2 and 3 are direct operated. The valves open For EVR 6 → 22 valves this differential pressure
30. O-ring direct for full flow when the armature (16) moves is 0.05 bar.
31. Piston ring up into the magnetic field of the coil.
36. DIN plug This means that the valves operate with a min. When current is switched off, the pilot orifice
37. DIN socket differential pressure of 0 bar. closes. Via the equalization holes (73) in the
(to DIN 43650)
40. Protective cap/Terminal box
The teflon valve plate (18) is fitted direct on the diaphragm, the pressure above the diaphragm
43. Valve cover armature (16). then rises to the same value as the inlet
44. O-ring Inlet pressure acts from above on the armature pressure and the diaphragm closes the main
45. Valve cover gasket and the valve plate. Thus, inlet pressure, spring orifice.
49. Valve body force and the weight of the armature act to close
50. Gasket the valve when the coil is currentless. EVR 25, 32 and 40 are servo operated piston
51. Threaded plug valves. The valves are closed with currentless
53. Manual operation spindle 2. Servo operation coil. The servo piston (80) with main valve plate
73. Equalization hole
74. Main channel
EVR 6 → 22 are servo operated with a "floating" (84) closes against the valve seat (83) by
75. Pilot channel diaphragm (80). The pilot orifice (29) of stainless means of the differential pressure between inlet
76. Compression spring steel is placed in the centre of the diaphragm. The and outlet side of the valve, the force of the
80. Diaphragm/Servo piston teflon pilot valve plate (18) is fitted direct to the compression spring (76) and possibly the piston
83. Valve seat armature (16). When the coil is currentless, the weight. When current to the coil is switched on,
84. Main valve plate main orifice and pilot orifice are closed. The pilot the pilot orifice (29) opens. This relieves the
90. Mounting hole orifice and main orifice are held closed by the pressure on the piston spring side of the valve.
weight of the armature, the armature spring force The differential pressure will then open the
and the differential pressure between inlet and valve. The minimum differential pressure
outlet sides. needed for full opening of the valves is 0.07 bar.
EVR (NO) has the opposite function to EVR
When current is applied to the coil the armature (NC), i.e. it is open with de-energised coil.
is drawn up into the magnetic field and opens the EVR (NO) is available with servo operation only.
pilot orifice. This relieves the pressure above the
diaphragm, i.e. the space above the diaphragm

24 Technical leaflet - RD3AD302  Danfoss A/S, 05 - 2002


Solenoid valves, type EVR 2 ® 40 - NC / NO

Material specifications
EVR 2 to 22

Solenoid valves Standard


No. Description Type Material Analysis Mat.no. W.no. DIN EN
1 Valve body EVR 2 til 25 Brass CuZn40Pb2 CW617N 2.0402 17672-1 12165
EVR 2 til 3 Stainless steel X5 CrNi18-10 1.4301 10088
2 Cover EVR 6 til 22 Brass CuZn40Pb2 CW617N 2.0402 17672-1 12165
EVR 25 Cast iron GGG 40.3 0.7043 1693
3 Armature tube EVR 2 til 25 Stainless steel X2 CrNi19-11 1.4306 10088
4 Armature tube nut EVR 25 Stainless steel X8 CrNiS 18-9 1.4305 10088
5 Gasket EVR 2 til 25 Rubber Cr
6 Gasket EVR 25 Al. gasket Al 99.5 3.0255 10210
7 Solder tube EVR 25 Copper SF-Cu CW024A 2.0090 1787 12449
8 Screws EVR 2 til 25 Stainless steel A2-70 3506
9 Spindle for man. operat. EVR 25 Stainless steel X8 CrNiS 18-9 1.4305 10088
10 Gasket EVR 25 Rubber Cr

EVR 32 to 40

Solenoid valves Standard


No. Description Type Material Analysis Mat.no. W.no. DIN EN
1 Valve body EVR 32/40 Cast Iron EN-GJS-400-18-LT EN-JS1025 1563
2 Cover EVR 32/40 Brass CuZn40Pb2 CW617N 2.0402 12165
3 Armature tube EVR 32/40 Stainless steel X2 CrNi19-11 1.4306 10088
4 Armature tube nut EVR 32/40 Stainless steel X8 CrNiS 18-9 1.4305 10088
5 Gasket EVR 32/40 Rubber Cr
6 Gasket EVR 32/40 Al. gasket Al 99.5 3.0255 10210
7 Solder tube EVR 32/40 Copper SF.Cu CW024A 2.0090 1787 12449
8 Screws EVR 32/40 Stainless steel A2-70 3506
9 Spindle for. man. operation EVR 32/40 Stainless steel X8 CrNiS 18-9 1.4305 10088

 Danfoss A/S, 05 - 2002 Technical leaflet - RD3AD302 25


Solenoid valves, type EVR 2 ® 40 - NC / NO

Dimensions and weights EVR (NC) 2 → 15, flare connection


Weight of coil
10 W: approx. 0.3 kg
12 and 20 W: approx. 0.5 kg

With DIN plugs coil


With cable connection coil

With terminal box coil

Connection L5 max. Weight


H1 H2 H3 H4 L L2 L3 L4 B B1 max.
Type Flare 10 W 12/20 W with coil
in. mm mm mm mm mm mm mm mm mm mm mm mm mm kg
EVR 2 1/ 6 14 71 9 59 45 54 75 85 33 68 0.5
4

EVR 3 1/ 6 14 71 9 59 45 54 75 85 33 68 0.5
4
3/ 10 14 73 9 62 45 54 75 85 33 68 0.5
8

EVR 6 3/ 10 14 78 10 69 45 54 75 85 36 68 0.6
8
1/ 12 14 78 10 75 45 54 75 85 36 68 0.6
2

EVR 10 1/ 12 16 79 11 84 45 54 75 85 46 68 0.8
2
5/ 16 16 79 11 92 45 54 75 85 46 68 0.8
8

EVR 15 5/ 16 19 86 49 104 45 54 75 85 56 68 1.0


8

26 Technical leaflet - RD3AD302  Danfoss A/S, 05 - 2002


Solenoid valves, type EVR 2 ® 40 - NC / NO

Dimensions and weights EVR (NC) 2 → 22, solder connection


(continued)
Weight of coil
10 W: approx. 0.3 kg
12 and 20 W: approx. 0.5 kg

With cable connection coil With DIN plugs coil

With terminal box coil

Connection L5 max. Weight


H1 H2 H3 H4 L L2 L3 L4 B B1 max.
Type Solder 10 W 12/20 W with coil
in. mm mm mm mm mm mm mm mm mm mm mm mm mm kg
EVR 2 1/
4 6 14 71 9 102 7 45 54 75 85 33 68 0.5
EVR 3 1/ 6 14 71 9 102 7 45 54 75 85 33 68 0.6
4
3/ 10 14 73 9 117 9 45 54 75 85 33 68 0.6
8

EVR 6 3/
8 10 14 78 10 111 9 45 54 75 85 36 68 0.6
1/ 12 14 78 10 127 10 45 54 75 85 36 68 0.6
2

EVR 10 1/
2 12 16 79 11 127 10 45 54 75 85 46 68 0.7
5/ 16 16 79 11 160 12 45 54 75 85 46 68 0.7
8

EVR 15 5/ 16 19 86 49 176 12 45 54 75 85 56 68 1.0


8
7/ 22 19 86 176 17 45 54 75 85 56 68 1.0
8

EVR 20 7/ 22 20 90 53 191 17 45 54 75 85 72 68 1.5


8

11/8 28 20 90 214 22 45 54 75 85 72 68 1.5


EVR 22 13/ 8 35 20 90 281 25 45 54 75 85 72 68 1.5

 Danfoss A/S, 05 - 2002 Technical leaflet - RD3AD302 27


Solenoid valves, type EVR 2 ® 40 - NC / NO

Dimensions and weights (continued)

EVR (NC) 25, 32 og 40, solder connection

EVR 25
EVR 32 and 40

EVR 32 and 40 terminal box

EVR 25 with terminal box coil

Weight of coil
10 W: approx. 0.3 kg Coil with cable Coil with DIN plugs
12 and 20 W: approx. 0.5 kg

Coil with Coil with Coil with


Weight
Connection cable DIN terminal box
H1 H2 H3 H4 L L2 L5 max. B B1 max. with
Type Solder connection connection
coil
L3 L4 10 W 12/20 W
in. mm mm mm mm mm mm mm mm mm mm mm mm mm kg
EVR 25 11/8 28 38 138 72 256 22 45 54 75 85 95 68 3.0
13/8 35 38 138 72 281 25 45 54 75 85 95 68 3.3
EVR 32 13/8 35 47 111 53 281 25 45 54 75 85 80 68 4.5
15/8 42 47 111 53 281 29 45 54 75 85 80 68 4.6
EVR 40 15/8 42 47 111 53 281 29 45 54 75 85 80 68 4.6
21/8 54 47 111 53 281 34 45 54 75 85 80 68 4.6

EVR (NC) 15 and 20, flange connection

Coil with cable Coil with DIN plugs

Weight of coil
10 W: approx. 0.3 kg
12 and 20 W: approx. 0.5 kg

Weight of flange set


With terminal box coil For EVR 15: 0.6 kg
For EVR 20: 0.9 kg

Coil with Coil with Coil with


Weight
cable DIN terminal box
H1 H2 H3 H4 L L1 L2 L5 max. B B1 max. with coil
Type connection connection
excl.
L3 L4 10 W 12/20 W flanges
mm mm mm mm mm mm mm mm mm mm mm mm mm kg
EVR 15 19 86 19 49 125 68 45 54 75 85 80 68 1.2
EVR 20 20 90 21 53 155 85 45 54 75 85 96 68 1.7

28 Technical leaflet - RD3AD302  Danfoss A/S, 05 - 2002


Solenoid valves, type EVR 2 ® 40 - NC / NO

Dimensions and weights EVR (NO) 6 → 22, flare or solder connection


(continued)

With cable connection coil


With DIN plugs coil

Weight of coil
10 W: approx. 0.3 kg
12 and 20 W: approx. 0.5 kg With terminal box coil

Coil with Coil with DIN Coil with


cable connection terminal box Weight
H1 H2 H3 H4 L L1 L2 connection L5 max. B B1 max. with coil
Type
L3 L4 10 W 12/20 W
mm mm mm mm mm mm mm mm mm mm mm mm mm kg

Flare
EVR 6 14 88 10 69 45 54 75 85 36 68 0.6
EVR 10 16 89 11 84 45 54 75 85 46 68 0.7
EVR 15 19 96 104 45 54 75 85 56 68 0.9

Solder
EVR 6 14 88 10 111 9 45 54 75 85 36 68 0.6
EVR 10 16 89 11 127 10 45 54 75 85 46 68 0.7
EVR 15 19 96 176 12 45 54 75 85 56 68 0.9
EVR 20 20 100 191 1) 17 1) 45 54 75 85 72 68 1.5
EVR 22 20 100 281 25 45 54 75 85 72 68 1.5
1
) Applies to 7/8 in. and 22 mm connections. For 11/8 in. and 28 mm connections is L = 214 mm and L2 = 22 mm.

 Danfoss A/S, 05 - 2002 Technical leaflet - RD3AD302 29


Solenoid valves
Type EVRC 10 ® 20 - NC

Introduction EVRC is a servo operated solenoid valve for use


in liquid lines in refrigeration plant.

EVRC allows flow in both directions and can


therefore be used in liquid lines in refrigeration
plant with hot gas or gas defrost.

During the refrigeration period EVRC works as a


normal solenoid valve, while during the defrost it
allows the condensed liquid to return to the liquid
manifold.

During the defrosting period coil for EVRC must


be energized.

Technical data Refrigerants Capacity


CFC, HCFC, HFC. The capacity of the valve depends on the flow
direction, see kv values from the table.
Temperature of medium
−40 → +105°C with 10 W or 12 W coil. See extended capacity tables as for EVR
(data sheet RD3AD).
Ambient temperature and
enclosure for coil
See "Coils for solenoid valves", RD3JE.

Approvals Low Voltage Directive (LVD) 73/23/EC with


amendments EN 60730-2-8

Rated capacity Opening differential pressure kv-value 2)


with normal flow direction 1) with standard coil m3/h
kW ∆p bar Max.
working pressure
Type Max. (= MOPD) liquid Flow in arrow Flow against
R 22 R 134a R 404A R 407C Min. PB direction arrow direction
R 507 10 W 12 W 20 W
a.c. a.c. d.c. bar
EVRC 10 38.2 35.3 26.7 35.9 0.05 21 25 18 35 1.9 1.1
EVRC 15 52.3 48.3 36.5 49.2 0.05 21 25 18 32 2.6 1.2
EVRC 20 94.6 87.2 66.1 88.9 0.05 21 25 13 32 5.0 4.7

1) Rated liquid capacity is based on evaporating temperature te = −10°C, liquid temperature ahead of valve tl = +25°C, and
pressure drop across valve ∆p = 0.15 bar.
2) The k value is the water flow in m3/h at a pressure drop across valve of 1 bar, ρ = 1000 kg/m3.
v

Ordering Separate valve housing


Connection Code nr.
Type Required coil Solder
in. mm Valve housing without coil
EVRC 10 1/ 032F1216
2
a.c. 5/
EVRC 15 8 16 032F1255
d.c.
EVRC 20 7/ 22 032F1258
8

Coils
See "Coils for solenoid valves".

For further information, please contact Danfoss.

 Danfoss A/S, 04 - 2002 Technical leaflet - RD3JC302 31


Solenoid valves, type EVRC 10 ® 20 - NC

Material specifications

Standard
No. Description Material Analysis Mat. no.
W.no. DIN EN
1 Valve body Brass CuZn40Pb2 CW617N 2.0402 17672 12165
2 Cover Brass CuZn40Pb2 2.0402 12165
3 Armature tube Stainless steel X2 CrNi19-11 1.4306 17672-1 10088
4 Gasket Gummi Cr
5 Solder tube Copper SF-Cu CW024A 2.0090 1787 12449
6 Screws Stainless steel A2-70 3506

Dimensions and weight

EVRC (NC) EVRC (NC)


Coil with cable Coil with terminal box

Weight of coil
10 W: ca. 0.3 kg
12 og 20 W: ca. 0.5 kg

L5 max.
B1 Weight
H1 H2 H3 L L2 L3 12 W B max. with coil
Type 10 W 20 W
mm mm mm mm mm mm mm mm mm mm kg
EVRC 10 (NC) 16 79 11 127 10 45 75 85 46 68 0.7
EVRC 15 (NC) 19 86 176 12 45 75 85 56 68 1.0
EVRC 20 (NC) 20 90 191 17 45 75 85 72 68 1.5

For further information, please contact Danfoss.

32 Technical leaflet - RD3JC302  Danfoss A/S, 04 - 2002


Stainless steel solenoid valves
Type EVRS 3 ® 20 and EVRST 10 ® 20

Introduction EVRS and EVRST are valves made of stainless


steel.

EVRS 3 is direct operated.

EVRS 10, 15 and 20 are servo operated.


EVRST 10,15 and 20 are forced servo operated
valves used in liquid, suction, hot gas and oil
return lines with ammonia or fluorinated
refrigerants.

EVRS 3 and EVRST are designed for keeping


open at a pressure drop of 0 bar.
EVRS and EVRST are supplied as components,
i.e. valve body and coil must be separately
ordered.

EVRS/EVRST 10, 15 and 20 are equipped with


spindel for manual opening.

Features • Stainless steel valve body and connections • Designed for temperatures of media
up to 105°C
• Suitable for applications where high hygiene
is required • Wide choice of a.c. and d.c. coils

• Used for ammonia and all fluorinated


refrigerants

Technical data Refrigerants Temperature of medium


R 717 (NH3), R 22, R 134a, R 404A etc. −40 → +105°C. Max. 130°C during defrosting.
Ambient temperature and enclosure for coil: See "Coils for solenoid valves", lit.no. RD3JE.

Opening differential pressure Max. operating


Temperature
Type ∆p bar pressure kv value 2)
of medium
PB
Max. (MOPD) liquid 1)
Min.
10 W a.c. 12 W a.c. 20 W d.c. °C bar m3/h
EVRS 3 0.0 21 25 14 −40 → 105 28 0.23
EVRS 10 0.05 21 25 18 −40 → 105 28 1.5
EVRST 10 0.0 14 21 16 −40 → 105 28 1.5
EVRS 15 0.05 21 25 18 −40 → 105 28 2.7
EVRST 15 0.0 14 21 18 −40 → 105 28 2.7
EVRST 20 0.05 21 25 18 −40 → 105 28 4.5
EVRST 20 0.0 14 21 18 −40 → 105 28 4.5
1) MOPD for media in gas form is approx. 1 bar greater.
2) The kv value is the water flow in m3/h at a pressure drop in the valve of 1 bar, ρ = 1000 kg/m3.

 Danfoss A/S, 04 - 2002 Technical leaflet - RD3XA302 33


Stainless steel solenoid valves type EVRS 3 ® 20 and EVRST 10 ® 20

Technical data (continued) Ratedcapacity1)


kW
Type Liquid Suction vapour Hot gas
R 717 R 22 R 134a R 404A R 717 R 22 R 134a R 404A R 717 R 22 R 134a R 404A
EVRS 3 21.8 4.6 4.3 3.2 6.5 2.1 1.7 1.7
EVRS/EVRST 10 142.0 30.2 27.8 21.1 9.0 3.4 2.5 3.1 42.6 13.9 11.0 11.3
EVRS/EVRST 15 256.0 54.4 50.1 38.0 16.1 6.2 4.4 5.5 76.7 24.9 19.8 20.3
EVRS/EVRST 20 426.0 90.6 83.5 63.3 26.9 10.3 7.3 9.2 128.0 41.5 32.9 33.9
1) Rated liquid and suction vapour capacity is based on evaporating temperature te = −10°C, liquid temperature ahead
of valve tl = +25°C, and pressure drop across valve ∆p = 0.15 bar.
Rated hot gas capacity is based on condensing temperature tc = +40°C, pressure drop across valve ∆p = 0.8 bar, hot
gas temperature th = +60°C, and subcooling of refrigerant ∆tsub = 4 K.

Ordering Separate valve bodies


Connection Code no.
Type Weld Pipe thread With manual Without manual
in. ISO 228/1 operation operation
EVRS 3 3/8 032F3080
EVRS 3 G 1/4 032F3081
EVRS 10 1/2 032F3082
EVRST 10 1/2 032F3083
EVRS 15 3/4 032F3084
EVRST 15 3/4 032F3085
EVRS 20 1 032F3086
EVRST 20 1 032F2237

Coils See "Coils for solenoid valves".

Capacity Liquid capacity Qe kW at pressure drop across valve ∆p bar


Type
Liquid capacity Qe kW 0.1 0.2 0.3 0.4 0.5

R 717 (NH3)
EVRS 3 17.8 25.1 30.8 35.6 39.8
EVRS/EVRST 10 116.0 164.0 201.0 232.0 259.0
EVRS/EVRST 15 209.0 295.0 362.0 418.0 467.0
EVRS/EVRST 20 348.0 492.0 603.0 696.0 778.0

R 22
EVRS 3 3.8 5.3 6.6 7.6 8.5
EVRS/EVRST 10 24.7 34.9 42.7 49.3 55.1
EVRS/EVRST 15 44.4 62.8 76.9 88.8 99.2
EVRS/EVRST 20 73.9 105.0 128.0 148.0 165.0

R 134a
EVRS 3 3.5 4.9 6.0 7.0 7.8
EVRS/EVRST 10 22.7 32.2 39.4 45.5 50.8
EVRS/EVRST 15 40.9 57.9 70.9 81.8 91.5
EVRS/EVRST 20 68.2 96.5 118.0 136.0 153.0

R 404A
EVRS 3 2.6 3.7 4.6 5.3 5.9
Capacities are based on liquid EVRS/EVRST 10 17.2 24.3 29.8 34.4 38.5
temperature tl = + 25°C ahead of EVRS/EVRST 15 31.0 43.8 53.7 62.0 69.3
valve, evaporating temperature
te = –10°C, and superheat 0 K. EVRS/EVRST 20 51.7 73.0 89.5 103.0 116.0

Correction factors When sizing valves, the plant capacity must be multiplied by a correction factor depending on liquid
temperature tl ahead of valve/evaporator.
When the corrected capacity is known, the selection can be made from the table.
tl°C −10 0 +10 +20 +25 +30 +40 +50
R 717 (NH3) 0.84 0.88 0.92 0.97 1.0 1.03 1.09 1.16
R 22, R 134a 0.76 0.81 0.88 0.96 1.0 1.05 1.16 1.31
R 404A 0.70 0.76 0.84 0.94 1.0 1.07 1.24 1.47

34 Technical leaflet - RD3XA302  Danfoss A/S, 04 - 2002


Stainless steel solenoid valves type EVRS 3 ® 20 and EVRST 10 ® 20

Capacity Suction vapour capacity Qe kW


(continued)
Pressure drop Suction vapour capacity Qe kW at evaporating temperature te °C
Type
across valve ∆p bar –40 –30 –20 –10 0 +10

R 717 (NH3)
0.1 3.4 4.5 5.9 7.3 8.9 10.6
EVRS/EVRST 10 0.15 4.0 5.4 7.0 9.0 10.9 13.0
0.2 4.5 6.1 7.9 10.0 12.6 15.0
0.1 6.1 8.1 10.7 13.2 16.0 19.1
EVRS/EVRST 15 0.15 7.2 9.7 12.5 16.1 19.6 23.4
0.2 8.0 11.0 14.2 18.0 22.6 27.0
0.1 10.2 13.5 17.8 21.9 26.6 31.9
EVRS/EVRST 20 0.15 12.1 16.1 20.9 26.9 32.6 39.0
0.2 13.4 18.3 23.7 29.9 37.7 45.1

R 22
0.1 1.4 1.8 2.3 2.8 3.4 4.0
EVRS/EVRST 10 0.15 1.6 2.1 2.7 3.4 4.1 4.9
0.2 1.8 2.4 3.1 3.8 4.8 5.6
0.1 2.5 3.2 4.1 5.0 6.1 7.2
EVRS/EVRST 15 0.15 2.9 3.8 4.8 6.2 7.4 8.8
0.2 3.3 4.3 5.5 6.8 8.6 10.2
0.1 4.1 5.3 6.8 8.4 10.1 12.0
EVRS/EVRST 20 0.15 4.9 6.4 8.1 10.3 12.3 14.7
0.2 5.5 7.2 9.2 11.4 14.3 16.9

R 134a
0.1 0.87 1.2 1.6 2.1 2.6 3.2
EVRS/EVRST 10 0.15 0.99 1.4 1.9 2.4 3.2 3.9
0.2 1.1 1.6 2.1 2.8 3.5 4.5
0.1 1.6 2.1 2.8 3.8 4.7 5.7
EVRS/EVRST 15 0.15 1.8 2.5 3.4 4.4 5.7 7.0
0.2 2.0 2.8 3.8 5.0 6.3 8.1
0.1 2.6 3.6 4.7 6.3 7.8 9.6
EVRS/EVRST 20 0.15 3.0 4.2 5.6 7.3 9.5 11.7
0.2 3.3 4.7 6.4 8.3 10.5 13.5
Capacities are based on liquid
temperature tl = +25°C ahead of
evaporator.
The table values refer to the
R 404A
evaporator capacity and are given 0.1 1.2 1.5 2.0 2.5 3.1 3.7
as a function of evaporating EVRS/EVRST 10 0.15 1.4 1.8 2.4 3.1 3.8 4.6
temperature te and pressure drop ∆p 0.2 1.6 2.1 2.7 3.4 4.3 5.3
in valve.
0.1 2.1 2.7 3.6 4.5 5.5 6.6
Capacities are based on dry,
EVRS/EVRST 15 0.15 2.5 3.3 4.3 5.5 6.8 8.2
saturated vapour ahead of valve.
0.2 2.8 3.7 4.9 6.1 7.8 9.5
During operation with superheated
vapour ahead of valve, the capacities 0.1 3.5 4.6 6.0 7.5 9.2 11.1
are reduced by 4% for each 10 K EVRS/EVRST 20 0.15 4.1 5.5 7.1 9.2 11.3 13.6
superheat. 0.2 4.6 6.2 8.1 10.2 13.0 15.8

Correction factors
When sizing valves, the evaporator capacity
must be multiplied by a correction factor
depending on liquid temperature tl ahead of
expansion valve. When the corrected capacity is
known, the selection can be made from the
table.
tl°C −10 0 +10 +20 +25 +30 +40 +50
R 717 (NH3) 0.84 0.88 0.92 0.97 1.0 1.03 1.09 1.16
R 22, R 134a 0.76 0.81 0.88 0.96 1.0 1.05 1.16 1.31
R 404A 0.70 0.76 0.84 0.94 1.0 1.07 1.24 1.47

 Danfoss A/S, 04 - 2002 Technical leaflet - RD3XA302 35


Stainless steel solenoid valves type EVRS 3 ® 20 and EVRST 10 ® 20

Capacity Hot gas capacity Qe kW


(continued) Hot gas capacity Qh kW
Pressure drop Evaporating temp. te = −10°C. Hot gas temp. t h = tc + 25°C. Subcooling ∆tsub = 4 K
Type across valve
Condensing temperature tc °C
∆p bar +20 +30 +40 +50 +60

R 717 (NH3)
0.1 1.8 2.1 2.3 2.5 2.6
0.2 2.6 2.9 3.2 3.5 3.7
EVRS 3 0.4 3.8 4.2 4.6 4.9 5.3
0.8 5.1 6.0 6.5 7.1 7.6
1.6 7.4 8.3 9.1 9.9 10.9
0.1 12.0 3.4 14.7 16.0 17.2
0.2 17.1 19.0 20.9 22.7 24.4
EVRS/EVRST 10 0.4 24.5 27.1 29.7 32.2 34.7
0.8 34.0 39.0 42.6 46.1 49.5
1.6 48.5 53.8 59.1 64.3 1.3
0.1 21.7 24.1 26.4 28.8 31.0
0.2 30.8 34.2 37.5 40.8 44.0
EVRS/EVRST 15 0.4 44.1 48.8 53.5 58.0 62.4
0.8 61.2 70.3 76.7 83.0 89.1
1.6 87.4 96.9 106.0 116.0 128.0
0.1 36.1 40.1 44.0 48.0 51.7
0.2 51.4 57.0 62.6 68.0 73.2
EVRS/EVRST 20 0.4 73.5 81.3 89.1 96.7 104.0
0.8 102.0 117.0 128.0 138.0 148.0
1.6 146.0 161.0 177.0 193.0 214.0

R 22
0.1 0.68 0.72 0.76 0.78 0.79
0.2 0.97 1.0 1.1 1.1 1.1
EVRS 3 0.4 1.4 1.5 1.5 1.6 1.6
0.8 1.9 2.0 2.1 2.3 2.3
1.6 2.7 2.9 3.0 3.1 3.2
0.1 4.4 4.7 4.9 5.1 5.2
0.2 6.3 6.7 7.0 7.2 7.3
EVRS/EVRST 10 0.4 9.0 9.6 10.0 10.3 10.4
0.8 12.4 13.2 13.9 14.7 14.9
1.6 17.5 18.6 19.6 20.2 20.5
0.1 8.0 8.5 8.9 9.2 9.3
0.2 11.4 12.1 12.6 13.0 13.2
EVRS/EVRST 15 0.4 16.3 17.2 18.0 18.5 18.7
0.8 22.3 23.1 24.9 26.5 26.8
An increase in hot gas temperature
1.6 31.5 33.5 35.2 36.4 36.9
th of 10 K reduces valve capacity
approx. 2% and vice versa. 0.1 13.3 14.1 14.8 15.3 15.5
0.2 19.0 20.1 21.0 21.7 22.0
A change in evaporating temperature EVRS/EVRST 20 0.4 27.1 28.7 30.0 30.9 31.2
te changes valve capacity; see 0.8 37.1 38.4 44.5 44.2 44.6
correction factor table below. 1.6 52.5 55.9 58.6 60.6 61.5

Correction factors
When sizing valves, the table value must be
multiplied by a correction factor depending on
evaporating temperature te.
te °C −40 −30 −20 −10 0 +10
R 717 (NH3) 0.89 0.91 0.96 1.0 1.06 1.10
R 22 0.90 0.94 0.97 1.0 1.03 1.05
R 134a 0.88 0.92 0.98 1.0 1.04 1.08

36 Technical leaflet - RD3XA302  Danfoss A/S, 04 - 2002


Stainless steel solenoid valves type EVRS 3 ® 20 and EVRST 10 ® 20

Capacity Hot gas capacity Qh kW


(continued) Hot gas capacity Qh kW
Pressure drop Evaporating temp. te = −10°C. Hot gas temp. th = tc + 25°C. Subcooling ∆tsub = 4 K
Type across valve
Condensing temperature tc °C
∆p bar +20 +30 +40 +50 +60

R 134a
0.1 0.54 0.57 0.6 0.61 0.6
0.2 0.77 0.82 0.85 0.86 0.85
EVRS 3 0.4 1.1 1.2 1.2 1.2 1.2
0.8 1.5 1.6 1.7 1.8 1.8
1.6 2.2 2.3 2.4 2.5 2.4
0.1 3.5 3.7 3.9 4.0 3.9
0.2 5.0 5.3 5.5 5.6 5.6
EVRS/EVRST 10 0.4 7.0 7.7 7.9 8.0 7.9
0.8 9.9 10.5 11.0 11.6 11.4
1.6 14.3 15.1 15.7 16.0 15.9
0.1 6.4 6.7 7.0 7.1 7.1
0.2 9.1 9.6 10.0 10.1 10.0
EVRS/EVRST 15 0.4 12.6 13.8 14.2 14.4 14.3
0.8 17.9 19.0 19.8 20.8 20.5
1.6 25.7 27.2 28.2 28.8 28.6
0.1 10.6 11.2 11.7 11.8 11.8
0.2 15.1 16.0 16.6 16.8 16.7
EVRS/EVRST 20 0.4 21.0 22.9 23.7 24.0 23.8
0.8 29.8 31.6 33.0 34.7 34.2
1.6 42.8 45.3 47.1 47.9 47.6

R 404A
0.1 0.62 0.63 0.62 0.59 0.54
0.2 0.87 0.89 0.88 0.83 0.76
EVRS 3 0.4 1.2 1.3 1.3 1.2 1.1
0.8 1.7 1.7 1.7 1.7 1.5
1.6 2.4 2.5 2.4 2.3 2.1
0.1 4.0 4.1 4.0 3.8 3.5
0.2 5.7 5.8 5.7 5.5 5.0
EVRS/EVRST 10 0.4 8.1 8.2 8.2 7.8 7.0
0.8 11.1 11.4 11.3 11.1 10.1
1.6 15.7 16.0 15.8 15.2 13.9
0.1 7.3 7.4 7.3 6.9 6.3
0.2 10.2 10.4 10.3 9.8 8.9
EVRS/EVRST 15 0.4 14.6 14.8 14.7 14.0 12.7
0.8 20.1 20.4 20.3 20.0 18.1
An increase in hot gas temperature 1.6 28.3 28.8 28.4 27.4 25.0
th of 10 K reduces valve capacity
approx. 2% and vice versa. 0.1 12.1 12.3 12.1 11.5 10.5
0.2 17.1 17.3 17.2 16.3 14.9
A change in evaporating tempera- EVRS/EVRST 20 0.4 24.4 24.7 24.5 23.3 21.1
ture te changes valve capacity; see 0.8 33.4 34.0 33.9 33.3 30.2
correction factor table below. 1.6 47.1 48.0 47.4 45.6 41.6

Correction factors
When sizing valves, the table value must be
multiplied by a correction factor depending on
evaporating temperature te.
te °C −40 −30 −20 −10 0 +10
R 404A 0.86 0.88 0.93 1.0 1.03 1.07

 Danfoss A/S, 04 - 2002 Technical leaflet - RD3XA302 37


Stainless steel solenoid valves type EVRS 3 ® 20 and EVRST 10 ® 20

Capacity Hot gas capacity Gh kg/s


(continued) Hot gas Condensing Hot gas capacity Gh kg/s at pressure drop across valve ∆p bar
Type temperature temperature
th °C tc °C 0.5 1 2 3 4 5 6 7 8

R 717 (NH3)
25 0.003 0.005 0.006 0.007 0.007 0.007 0.007 0.007 0.007
EVRS 3 35 0.004 0.005 0.007 0.009 0.009 0.01 0.01 0.01 0.01
45 0.005 0.006 0.009 0.01 0.011 0.012 0.013 0.013 0.013
25 0.022 0.03 0.04 0.045 0.048 0.048 0.048 0.048 0.048
EVRS/EVRST 10 35 0.026 0.036 0.048 0.056 0.061 0.064 0.065 0.065 0.065
45 0.030 0.041 0.056 0.066 0.074 0.079 0.083 0.085 0.086
90
25 0.040 0.054 0.072 0.081 0.086 0.087 0.087 0.087 0.087
EVRS/EVRST 15 35 0.046 0.064 0.086 0.100 0.109 0.115 0.117 0.117 0.117
45 0.053 0.074 0.101 0.120 0.133 0.142 0.149 0.153 0.155
25 0.066 0.090 0.120 0.120 0.144 0.145 0.145 0.145 0.145
EVRS/EVRST 20 35 0.077 0.107 0.144 0.167 0.182 0.191 0.195 0.195 0.195
45 0.089 0.124 0.169 0.199 0.211 0.237 0.248 0.255 0.258

R 22
25 0.008 0.011 0.014 0.016 0.017 0.017 0.017 0.017 0.017
EVRS 3 35 0.009 0.012 0.017 0.019 0.021 0.022 0.022 0.022 0.022
45 0.010 0.014 0.019 0.022 0.025 0.026 0.027 0.028 0.028
25 0.051 0.069 0.092 0.104 0.109 0.111 0.111 0.111 0.111
EVRS/EVRST 10 35 0.058 0.08 0.108 0.125 0.136 0.142 0.144 0.144 0.144
45 0.066 0.092 0.125 0.146 0.162 0.172 0.179 0.183 0.183
90
25 0.091 0.125 0.165 0.187 0.197 0.199 0.199 0.199 0.199
EVRS/EVRST 15 35 0.105 0.144 0.194 0.225 0.244 0.256 0.258 0.258 0.258
45 0.119 0.165 0.224 0.263 0.291 0.31 0.322 0.329 0.330
25 0.152 0.208 0.275 0.311 0.328 0.332 0.332 0.332 0.332
EVRS/EVRST 20 35 0.174 0.241 0.323 0.375 0.407 0.425 0.431 0.431 0.431
45 0.193 0.275 0.374 0.439 0.485 0.516 0.537 0.548 0.550

R 134a
25 0.007 0.009 0.011 0.012 0.012
EVRS 3 35 0.009 0.011 0.014 0.016 0.016 0.016 0.016
45 0.01 0.012 0.018 0.02 0.021 0.021 0.021 0.021 0.021
25 0.048 0.06 0.074 0.077 0.077
EVRS/EVRST 10 35 0.055 0.071 0.092 0.103 0.104 0.104
45 0.06 0.084 0.111 0.127 0.134 0.135 0.135 0.135 0.135
60
25 0.081 0.108 0.134 0.14 0.14
EVRS/EVRST 15 35 0.094 0.129 0.166 0.192 0.187 0.187 0.187
45 0.108 0.151 0.2 0.228 0.241 0.244 0.244 0.244 0.244
25 0.134 0.180 0.223 0.233 0.233
EVRS/EVRST 20 35 0.157 0.215 0.276 0.307 0.312 0.312 0.312
45 0.181 0.252 0.333 0.381 0.403 0.407 0.407 0.407 0.407

R 404A
25 0.01 0.013 0.018 0.021 0.022 0.023 0.023 0.023 0.023
EVRS 3 35 0.011 0.015 0.02 0.024 0.027 0.028 0.029 0.029 0.03
45 0.012 0.017 0.023 0.028 0.032 0.034 0.035 0.036 0.037
25 0.063 0.087 0.116 0.134 0.145 0.148 0.149 0.149 0.149
EVRS/EVRST 10 35 0.072 0.1 0.134 0.158 0.174 0.184 0.19 0.19 0.192
45 0.081 0.112 0.153 0.182 0.203 0.228 0.228 0.237 0.239
60
25 0.113 0.157 0.21 0.242 0.26 0.267 0.269 0.269 0.269
EVRS/EVRST 15 35 0.129 0.18 0.242 0.285 0.313 0.332 0.341 0.342 0.346
45 0.146 0.202 0.275 0.327 0.365 0.393 0.411 0.424 0.431
An increase in hot gas temperature 25 0.189 0.262 0.350 0.403 0.433 0.445 0.449 0.449 0.449
th of 10 K reduces valve capacity EVRS/EVRST 20 35 0.215 0.300 0.404 0.474 0.521 0.552 0.569 0.570 0.576
approx. 2% and vice versa. 45 0.243 0.337 0.459 0.545 0.609 0.656 0.684 0.707 0.719

38 Technical leaflet - RD3XA302  Danfoss A/S, 04 - 2002


Stainless steel solenoid valves type EVRS 3 ® 20 and EVRST 10 ® 20

Design/Function

EVRS 3, pipe thread EVRS 3, weld

4. Coil
16. Armature
18. Pilot valve plate
20. Earth terminal
24. Connection for flexible steel
hose
28. Gasket
29. Pilot orifice
36. DIN connector
40. Terminal box
43. Valve cover
44. O-ring
45. Valve cover gasket
49. Valve body
51. Cover
53. Manual operating spindle
73. Equalization hole
80. Diaphragm
82. Support washer
83. Valve seat
84. Main valve plate
EVRST EVRS
EVRS / EVRST 10 and 15 EVRS / EVRST 20

The solenoid valve design is based on three When current is applied to the coil the armature
different principles: is drawn up into the magnetic field and opens
1. Direct operation the pilot orifice. This relieves the pressure
2. Servo operation above the diaphragm because the space above
3. Forced servo operation the diaphragm becomes connected to the outlet
side of the valve.
1. Direct operation The differential pressure between inlet and out-
EVRS 3 is directly operated. The valve opens let sides then presses the diaphragm away from
direct for full flow when the armature (16) moves the main orifice which opens to full flow.
up into the magnetic field of the coil. This means Thus a certain minimum differential pressure is
that the valve operates with a min. differential necessary to open the valve and keep it open.
pressure of 0 bar. For EVRS 10, 15 and 20 valves this differential
The valve plate (18) made of teflon and is fitted pressure is 0.05 bar.
direct to the armature (16). When current is switched off, the pilot orifice
Inlet pressure acts from above on the armature closes. Then the pressure above the diaphragm
and with it the valve plate. Thus, inlet pressure, rises, via the equalization holes (73) in the
spring force and the weight of the armature act diaphragm, to the inlet pressure and causes the
to close the valve when the coil is currentless. diaphragm to close the main orifice.

2. Servo operation 3. Forced servo operation


EVRS 10, 15 and 20 are servo operated with a EVRST 10, 15 and 20 are forced servo operated
"floating" diaphragm (80). The pilot orifice (29), solenoid valves.
which is of stainless steel, is placed in the cen- Forced servo operation differs from servo
tre of the diaphragm. operation in that in a forced servo operated
The teflon pilot valve plate (18) is fitted direct to valve the armature and the diaphragm are
the armature (16). connected by a spring. Thus the armature helps
With the coil currentless, the main orifice and to lift the diaphragm (80) and keep it lifted so
pilot orifice are closed. that the
The pilot orifice and main orifice are held closed pressure drop in the open valve is the least
by the weight of the armature, the armature possible.
spring force and the differential pressure These types of valves therefore require no
between inlet and outlet sides. differential pressure to keep them open.

 Danfoss A/S, 04 - 2002 Technical leaflet - RD3XA302 39


Stainless steel solenoid valves type EVRS 3 ® 20 and EVRST 10 ® 20

Material specification

EVRS 3, Pipe thread EVRS 3, welded

EVRS/ EVRST 10 and 15 EVRS/ EVRST 20

Solenoid valves Standard


No. Description Type Material Analysis Mat.no. W.no. DIN EN
1 Valve housing EVRS 3 Stainless steel X8 CrNiS 18-9 1.4305 10088
EVRS (T) 10/15/20 Stainless steel X6 CrNi 18-9 1.4308 17455
2 Welding tube
EVRS 3 Stainless steel X2 CrNiMo 17-12-2 1.4404 17455
3 Cover EVRS (T) 10(15/20 Stainless steel X6 CrNi 18-9 1.4308 17455
4 Armature tube EVRS(T) 3/10/15/20 Stainless steel X2 CrNi 19-11 1.4306 10088
5 Armature tube nut EVRS(T) 3/10/15/20 Stainless steel X8 CrNi 19-11 1.4305 10088
6 Gasket EVRS(T) 3/10/15/20 Rubber Cr
7 Gasket armature tube EVRS(T) 10/15/20 Al gasket Al 99.5 3.0255 10210
8 Screws EVRS(T) 10/15/20 Stainless steel A2-70
9 Spindle for man. oper. EVRS(T) 10/15/20 Stainless steel X8 CrNiS 18-9 1.4305 10088
10 Gasket EVRS(T) 10/15/20 Rubber Cr

40 Technical leaflet - RD3XA302  Danfoss A/S, 04 - 2002


Stainless steel solenoid valves type EVRS 3 ® 20 and EVRST 10 ® 20

Dimensions and weights

Coil with cable

EVRS 3, pipe thread EVRS 3, weld

Coil with DIN plugs

EVRS / EVRST 10 and 20


EVRS / EVRST 20
Coil with terminal box
Coil with terminal box
Weight of coil
10 W: approx. 0.3 kg
12 and 20 W: approx. 0.5 kg

L5 max.
Weight
Type 10 W 12 W with coil
20 W
mm mm kg
EVRS 3, pipe thread 75 85 0.7
EVRS 3, weld 75 85 0.6
EVRS/EVRST 10 75 85 1.4
EVRS/EVRST 15 75 85 1.5
EVRS/EVRST 20 75 85 2.2

 Danfoss A/S, 04 - 2002 Technical leaflet - RD3XA302 41


Coils for solenoid valves

Introduction The coils are specially designed to operate in the


aggressive environment of high humidity and
temperature fluctuations that you find in most
refrigeration systems.

The new Clip-on fastening system ensures a


faultless installation and makes the coils easy to
mount and dismount. A Danfoss Clip-on coil can be
mounted without any tools at all, and it is simple to
dismount the coil by means of a screwdriver.

The Clip-on coils are available for the entire range


of Danfoss solenoid valves for refrigeration,
freezing and air conditioning purposes.

Features • Encapsulated coils with long operating life, • Standard coils from 12 V to 420 V, 50, 60
even under extreme conditions or 50/60 Hz

• Standard coils for a.c. or d.c. • Standard coils dimensioned for max. opening
differential pressure (MOPD) of up to 21 bar
• Standard coils available with 3-core cable,
terminal box or DIN plugs • Coils can be fitted without the use of tools

Technical data Ambient temperature Enclosure


10 or 12 W a.c. coil IP 67 with cable or terminal box
for NC (normally closed) valve: IP 20 with DIN plugs and protective cap
−40 → +80°C IP 65 with DIN socket
IP 00 with DIN plugs.
10 W a.c. coil
for NO (normally open) valve: Approvals
−40 → +55°C See under the required solenoid valve.

20 W d.c. coil
for NC and NO valve:
−40 → +50°C

Permissible voltage variation


10 and 12 W a.c. coils: +10 → −15% and as
double frequency coils: ±10%
a.c. coils for 220-230 / 380-400 V: +6 → −15%
and as double frequency coils: +6 → −10%
20 W d.c. coils: ±10%.

Connection 3-core cable DIN plugs


The external thread in the screwed cable entry The three pins on the coil can be fitted with
suits flexible steel hose or corresponding cable spade tabs, 6.3 mm wide (to DIN 46247).
protection. The two current carrying pins can also be fitted
with spade tabs, 4.8 mm wide.
Terminal box Max. lead cross section: 1.5 mm2.
Leads are connected to terminal screws in the Use of the protective cap supplied will prevent
terminal box. The box is fitted with a Pg 13.5 inadvertent contact with live parts.
screwed entry for 6 → 14 mm cable.
Max. lead cross section: 2.5 mm2. DIN socket
(to DIN 43650)
Leads are connected in the socket. The socket
is fitted with a Pg 11 screwed entry for
6 → 12 mm.

 Danfoss A/S, 04 - 2002 Technical leaflet - RD3JE202 43


Coils for solenoid valves

Ordering Code no.


Voltage Frequency Appen- Power
With 1 m With With With
Valve type dix con-
Clip-on coils 3-core cable terminal box DIN plugs and DIN plugs**)
protective cap no.*) sumption
V Hz IP 67 IP 67 IP 20

Alternating current a.c.


12 50 018F6256 018F6706 018F6181 15
EVR 2 → 40 (NC) 24 50 018F6257 018F6707 018F6182 018F7358 16
EVR 6 → 22 (NO)
EVRC 42 50 018F6258 018F6708 018F6183 17
EVRA 48 50 018F6259 018F6709 018F6184 18
EVRAT
115 50 018F6261 018F6711 018F6186 018F7361 22
EVRS / EVRST
PKVD 220-230 50 018F6251 018F6701 018F6176 018F7351 31
Holding:
EVM (NC) 240 50 018F6252 018F6702 018F6177 018F7352 33 10 W
380-400 50 018F6253 018F6703 018F6178 37 21 VA
420 50 018F6254 018F6704 018F6179 38
Inrush:
24 60 018F6265 018F6715 018F6190 14 44 VA
115 60 018F6260 018F6710 018F6185 20
220 60 018F6264 018F6714 018F6189 29
240 60 018F6263 018F6713 018F6188 30
110 50/60 018F6280 018F6730 018F6192 018F7360 21
220-230 50/60 018F6282 018F6732 018F6193 018F7363 32

Direct current d.c. Coil type I


EVR 2 → 15 (NC) 12 018F6856 01
EVR 25 → 40 (NC/NO)
EVR 6 → 15 (NO) 24 018F6857 02
EVRC 10 → 15 48 018F6859 04
EVRA 3 → 15 (NC)
EVRA 25 → 40 (NC) 110 018F6860 06
EVRAT 10 → 15 (NC) 115 018F6861 07 20 W
EVRS / EVRST 3 → 15
PKVD 220 018F6851 09
EVM (NC/NO)

Direct current d.c. Coil type II


EVR 20 → 22 (NC/NO) 12 018F6886 01
EVRC 20
EVRA 20 24 018F6887 02
EVRAT 20 48 018F6889 04
EVRST 20
110 018F6890 06 20 W
115 018F6891 07
220 018F6881 09

See "Opening differential pressure" under "Technical data" for the valve concerned.

*) Indicates voltage and frequency


**) Can only be used with DIN socket
***) When replacing a coil with terminal box, it is sufficient to change the coil unit itself. Therefore,
order coil with DIN plugs and protective cap.

44 Technical leaflet - RD3JE202  Danfoss A/S, 04- 2002


Coils for solenoid valves

Ordering (continued) Code no.


Voltage Frequency Appendix no. Power
Special coils Valve type With
terminal box Indicates voltage consumption
and frequency
V Hz IP 67

Alternating current a.c.


EVR 3 → 40 24 50 018F6807 16
EVRC 42 50 018F6808 17
EVRA
EVRAT 48 50 018F6809 18
EVRS / EVRST Holding:
110 50 018F6811 22 12 W
PKVD
EVM (NC / NO) 220-230 50 018F6801 31 26 VA
240 50 018F6802 33
Inrush:
380-400 50 018F6803 37 55 VA
24 60 018F6815 14
110 60 018F6813 20
220 60 018F6814 29

See "Opening differential pressure" under "Technical data" for the valve concerned.
When replacing a coil with terminal box, it is sufficient to change the coil unit itself. Therefore, order coil
with DIN plugs and protective cap.

Accessories
Description Code no.
DIN socket 042N0156
Terminal box with build-in light emmiting indicator diode for solenoid valves 018Z0089
Dimensions and weights
See under the required solenoid valve.

 Danfoss A/S, 04 - 2002 Technical leaflet - RD3JE202 45


Coils for use in EX zone 2 EEx nA II T3

Introduction Danfoss has developed a series of ATEX


approved coils for use in EX zone 2. The coils
are equipped with clip-on fastening system
for easy and faultless installation. Thus the
coil can be installed without use of tools and
easily dismounted by means of a screwdriver.

Features • ATEX approved for use in EX zone 2 • Mounting on valve without use of tools

• Embedded coils with long lifetime - even under • Standard coils for a.c. and d.c.
extreme conditons
• Standard coils from 24 to 240 V
• Available with 1 m 3-core cable or terminal
• Standard coils dimensioned to max. opening
• Quick and safe mounting with "clip-on"coil differential pressure (MOPD) up to 21 bar

Approval EExnAIIT3 DEMKO 01 ATEX 130591X

Technical data Ambient temperature


• 11 or 14 W, 50 Hz a.c. coil −40 → +50°C Enclosure for coil
• 13 W, 50/60 Hz a.c. coil −25 → +50°C • IP 67
• 20 W d.c. coil −25 → +50°C Permissible voltage variation
• 11 and 14 W a.c. coils: +10 → −15% and as
Temperature of medium double frequency coils: ±10%
max. 105°C • 20 W d.c. coils: ±10%

Connections 3-core cable Terminal box


The external thread of the cable entry is suitable The cables are connected with the terminal screws
for flexible steel hose or similar cable protection in the terminal box which is equipped with a Pg 13.5
cable gland for 6 → 14 mm cable.
Max. cable diam.: 2.5 mm2

46 Technical leaflet - RD3JE202  Danfoss A/S, 04 - 2002


Coils for use in EX zone 2 EEx nA II T3

Ordering Voltage Frequency Code no.


Coils V Hz With 1 m With Power
Type 3-core cable terminal box consumption
IP 67 IP 67

Alternating current a.c.


EVR 2 → 40 (NC) 24 50 018F5257 018F5707
EVR 6 → 22 (NO) 48 50 018F5259 018F5709 Holding:
EVRC 115 50 018F5261 018F5711 11 W
EVRA/ EVRAT 230 50 018F5251 018F5701 21 VA
EVRS/ EVRST 240 50 018F5252 018F5702
PKVD Inrush:
EVM (NC) 44 VA
230 50/60 018F5282 018F5732 Holding:
24 50/60 018F5277 018F5727 13 W

25 VA
Inrush:
48 VA

Alternating current a.c.


EVR 2 → 40 (NC) 24 50 018F5807 Holding:
EVR 6 → 22 (NO) 48 50 018F5809 14 W
EVRC 110 50 018F5811 26 VA
EVRA/ EVRAT 230 50 018F5801 Inrush
EVRS/ EVRST 240 50 018F5802 55 VA
PKVD
EVM (NC)

Direct current d.c.


EVR 2 →15 (NC) 24 018F5857
EVR 25 → 40 (NC/NO)
EVR 6 →15 (NO)
EVRC 10 → 15
EVRA 3 → 15 (NC)
EVRA 25 → 40 (NC) 20 W
EVRAT 10 → 15 (NC)
EVRS/ EVRST 3 → 15
PKVD
EVR (NC/NO)

Must always be installed with fuse ahead of coil

 Danfoss A/S, 04 - 2002 Technical leaflet - RD3JE202 47


UL - approved coil, type GP

Introduction With the Danfoss general purpose coils,


type GP, for solenoid valves the mounting
with a "click-on".
DanlokTM makes mounting faster and easier
and keeps the coil safely in place.

Features • Easy mounting and dismounting • Suitable to all standard solenoid valves
• No loose parts during operation • Available with junction box or conduit boss

Approvals S UL listed with EVR, MH 7648


A CSA certified, SA 52727

Technical data Enclosure


junction box: NEMA 2 ~ IP 12 - 32
Conduit boss: NEMA 4 ~ IP 54

Ordering Connection Cable length Voltage Frequency Code.no Power


in. V Hz consumption

Alternating current a.c.


Junction box 120/208-240 50/60 018Z7600 Holding
Junction box 24 50/60 018Z7613 17.5 W
Junction box Junction box 110/120 50/60 018Z7612 40 VA
Junction box 208/240 50/60 018Z7611
Conduit boss 18 24 50/60 018Z7623
Conduit boss 18 110/120 50/60 018Z7622 inrush
Conduit boss 18 208/240 50/60 018Z7621 76VA
Conduit coil

48 Technical leaflet - RD3JE202  Danfoss A/S, 04 - 2002