NOTES:
BILL OF MATERIALS
1. ALL DIMENSIONS ARE IN MILLIMETER UNLESS
ITEM ISSUE REQ'D. OTHERWISE SPECIFIED.
AMS # DESCRIPTION
NO. UNIT QTY.
2. POLES SHALL BE PRE-DRILLED WITH 20MM DIA HOLES
1 1000379019 EA 1 ROD; GROUNDING (UNTHREADED) TYPE 19.05MM (3/4 IN)
AT LOCATIONS SPECIFIED IN THIS DRAWING.
2 1000233149 EA 6 WASHER; ROUND, FLAT; STEEL; GALV.ƒ" DIA. HOLE
3. ALL PRE-DRILLED HOLES SHALL BE PROVIDED WITH
3 CS MT 1 PIPE: FIBERGLASS 250MM DIA
CAPS OR PLUGS (DURABLE PLASTIC OR COMPOSITE

OF
4 1000233194 EA 8 WASHER; ROUND STL. GALV. ƒ" DIA. BOLT SIZE
MATERIALS).
5 45026 74313-0001 EA 4 CROSSARM STEEL 4"X6"X8FT LONG

CONSENT
CS THERMIT WELD 4. EARTHING NUT SHALL BE PROVIDED WITH BOLT AND
6 EA 2
191 1028 1028 191 WASHER.
7 CS EA 10 STRAP: HOLDING FOR CONDUIT AND GOUND WIRE
|

SHEILD WIRE OR OPGW 8 6 5. POLE SHALL BE PERMANENTLY MARKED WITH MANU-


1000256857 EA MACHINE SCREW; ‚" DIA. 1•" LONG
2 11 13 17 18 19 23 FACTURERS NAME YEAR OF MANUFACTURE LEGNTH
102
9 CS FT 3 PIPE; PVC 1•" DIA.
AND ULTIMATE LOAD RATING.
10 1000390097 EA 14 BOLT; MACHINE ƒ" x 14" LONG W/NUT
(TYP. FOR-3)

TTEN
1000
11 1000387225 EA 6 INSULATOR: DISTRIBUTION SUSPENSION 6. CONTRACTOR SHALL INSTALL THE STEEL STRAP
1000

898

FOR HOLDING CONDUIT AND GROUND WIRE AT THE


12 1000829281 EA 1 POLE: STEEL, OCTAGONAL, 55FEET OR LENGTH AS REQUIRED

WRI
DISTANCE OF 610mm.
13 1000391984 EA 3 EYE; NUT, 3/4" SSZ. GALV.
3 7. FOR 34.5KV SYSTEM, MATERIAL SPECIFICATIONS OF
5 14 1000385547 EA ARRESTER; LIGHTNING, POLE MOUNTED
INSULATORS, FUSES, LIGHTNING ARRESTORS, CABLES,

THE
15 1000419988 MT 30 WIRE; GROUND, 25MM GREEN INSULATED
EA OR TERMINATING KIT SHALL BE RATED TO
16 1000386362 3 BRACKET: MOUNTING; X-ARM FOR SURGE ARRESTOR
ITS VOLTAGE RATING.
17 1000390607 EA 3 CLAMP, DEAD-END, ALUM. 4/0 AWG TO 2/0 AWG STRANDED

THOUT
20 18 1000391426 EA 3 CLEVIS: INSULATOR CLEVIS, BALL, CURVED BRACKET MTG, FORGED 8. CROSS ARM LENGTH FOR 34.5KV SHALL BE

1540
20 19 1000389587 EA 3 BOLT; DOUBLE ARMING, 3/4" DIA. 22" LONG. 10FEET LONG.

WI
20 1000412342 FT 25 WIRE: COPPER SOFT DRAWN 2/0 AWG 9. REFER TO SAES-P-107 TABLE-1 FOR CONDUCTOR
10
21 14-407-615 FT 1 ANGLE BAR, 3"x3"x3/8" & JUMPER CLEARANCES.

NG
22 1000283632 MT 3 BAR; CONC.; REINF. 12mm DIA. 10. GALVANIZED STEEL POLE MUST BE COATED WITH

DRAWI
23 1000393239 EA 3 CLEVIS: SOCKET EYE , 21 MM, 15.9 MM (5/8 IN) INSIDE WD, 35 MM INSIDE LG ANTI-CORROSION COATING OF COAL TAR EPOXY
24 1000233190 EA 4 LOCKWASHER, SPRING TYPE FOR ƒ" DIA. BOLT SIZE AS PER 14-SAMSS-403.
25 1000389703 EA 6 BOLT: MACHINE, 1/2 " x 1-1/2" WITH NUT & WASHER 11. STAND-OFF INSULATORS SHALL BE INSTALLED
1000231866

S
26 EA 8 WASHER" FOR 3/4" DIA. BOLT CAD PLTD. FOR 34.5KV FUSE CUT-OUTS.

1540

THI
SEE DETAIL
EA
* * * FOR GUY AND ANCHOR
27

28
1000374679

1000389836 EA
15
4
LUG: TERMINAL 2-HOLE 4/0 ACSR

BOLT, MACHINE †" DIA. X 6" LONG


12. EITHER COMPOSITE OR PORCELAIN TYPE INSULATORS
SEE NOTE 9 MAY BE USED. REFER TO SAES-P-107 FOR DETAILS.

FROM
2
29 1000408655 KT 1 TERMINATING KIT FOR 15000V, 3-1/C-95-240mm CABLE
30 CS EA 3 STRAP: CABLE 2" SIZE 2 HOLE MOUNTING CLAMP FOR TERMINATOR
31 1000405805 PK 2 DUXSEAL SEALING COMPOUND

NED
32 CS EA 2 BUSHING; 4" DIA. SIZE
5

1540
33 CONDUIT; RSG PVC COATED; 4" DIA.

OBTAI
CS PC
34 CS EA 1 ELBOW; RIGID CONDUIT; PVC COATED; 4", 90 DEG. 36"R

35 CS CM 0.2 CONCRETE: READY MIX, 2500PSI


36 1000168148 EA 2 TAG; BRASS TAG

BE
37 1000522061 EA 3 LINK FUSE; 10A RATING FOR 15 KV FUSE CUT OUT

38 1000386369 EA 3 CUT OUT; FUSE TYPE, 15KV OPEN EYE 10000 A/C

PART,SHALL
39 1000522174 EA 3 LINK FUSE; 7A RATING FOR 15 KV FUSE CUT OUT

40 1000418550 FT CABLE POWER 15KV IC-120MM2 (4/0AWG) STANDARD

1540
16
41 CS EA 1 ROD; GROUNDING 16MM (5/8 ") DIA. x 3M (10') LONG THREADED AT ONE END (J9160)

38 27

39 37

N
I
FULL,OR
REFERENCE DRAWINGS

1200
14

N
I ON
14

REPRODUCTI
1540
1200
29 24 27 25
12
29 27 25

SAUDIARAMCO.NO
30 8

1600
(TYP. FOR-3)

OF
STEEL CROSSARM
MOUNTING BRACKET

PROPERTY
15
36

SOLE
33
33

13000

THE
7

3000
MINIMUM
POLE GROUNDING

ARE
500

N
HEREINED
SCALE: NONE
FOR CONTINUATION
3 9 21 22
L

CONTAI
DETAI

AND CABLE SIZES

2600
31 32 SEE POWERLINE
REVISION VALIDATION
ROUTING PLAN 35 6 1 41
THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
ON

GROUND ROD CONCRETE REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
GROUND ROD
POLE

FOUNDATI

ANCHOR

ON
FOR LIGHTNING 34 31 FOR LIGHTNING 765200-0915-001

NFORMATI
ARRESTER ARRESTER
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
SEE

32 ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

RM JAB RM JAB
09/01/15 09/01/15 09/01/15 09/01/15

REV.NO. DATE REVISION DESCRIPTION

34

I
00 09/01/15 NEW STANDARD FOR STEEL POLE

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
765200 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
DRAWING TYPE

ELEVATION SECTION DEAD-END RISER POLE WITH FUSE STD

NG
13.8KV -34.5KV OVERHEAD POWERLINE

DRAWI
STANDARD DRAWING

STD. DWG. SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
990 P AA-036142 008 00
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01