001 01 AA-036011 R 990 NOTES:

REV. NO. SHT. NO. INDEX PLANT NO. 1. WESTERN TYPE WATER CLOSET FIXTURES IS OPTIONAL.
100
DRAWING NUMBER
8 GA WIRE
TIE CLIP 2. SECURE FLY CHASER FAN TO WALL WITH 1/2 " x 250mm MACHINE
TOP COURSE BOLTS BOLTED TO 3 x 50mm STEEL STRAP ON OUTSIDE OF
ONLY WALL.
1615 1220 1420 815 1220 1420

100
(TYPICAL) (TYPICAL) 3. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE.
WINDOW (TYPICAL) C
B OPENING
(TYPICAL)

1220
A A D 50 50
ELECT.
SUPPLY

1830

1830
WESTERN TYPE EASTERN TYPE WESTERN TYPE EASTERN TYPE

D DETAIL-1
TIE CLIP

1220
SCALE : 1:10

4880

1220

1220
4880

1200

820
F
200

12
815 1170 1420 1885 1170 1420 1220 1420 1220 1420 1885
815
10mm DIA. BAR
300 815 100 ON EVERY 3RD.
COURSE

600
560 1420 560 560 1420 560

CONC. BLK. WALL


3455

1515
CONC. FLOOR

1830

1830

0
1005

=5
1200

915

915
820

20
F

LEGEND:

100
ELECT. REINFORCING BARS OR FABRIC
194

10mm DIA. BAR CONSTRUCTION


SUPPLY ON EVERY 3RD. 12mm DIA. VERT. BARS 1270 1270 12mm DIA. VERT. BARS
B JOINT @ ALL PARTTION 1/2 " x 6"
COURSE @ ALL PARTTION C (TYPICAL) (TYPICAL) CONDUIT 3/4 " - 2 OF 12 TYPE TW WIRE
300 1830 CORNERS & @ DOORS & EXPANSION JOINT
CORNERS & @ DOORS &
WINDOW OPENINGS WINDOW OPENINGS 1 LAYER 0.70 Kg./m
4660 (4 STALL) 11785 (12 STALL) FILL CELLS W/GROUT TWIST LOCK CONVENIENCE OUTLET FOR
FILL CELLS W/GROUT FELT HOT MOPPED F
FLY CHASER FAN
7300 (8 STALL) 14430 (16 STALL) SEE NOTE-2

DETAIL-2 LIGHTING FIXTURE, 100 WATTS INCANDESCENT


CONC. MOULDING MOUNTED ON 4" OCTAGON BOX
ABOVE GRADE PLAN ABOVE GRADE PLAN SCALE : 1:10
4 AND 8 STALL 12 AND 16 STALL
SCALE : 1:40 SCALE : 1:40

15650
8520

610 7300 610 610 14430 610


ALTERNATIVE
610 x 1220mm TO 120V OVERHEAD 2 PLY BUILT-UP ROOF
2 PLY BUILT-UP ROOF 25mm ROUNDED SCREENED WINDOW
MORTAR CAP SUPPLY 3/4 " VENT TO ROOF OVER 1/2 " PLYWOOD
OVER 1/2 " PLYWOOD OPENING
3 OF 6 S.E.C.
CABLE SUPPORT
194mm BOND BEAM
W/16mm BAR SEE DETAIL-1 CONNECTOR
GROUTED
2 OF 8 THWN
610 x 1830mm
WINDOW FRAME WEATHERHEAD
3048=15 COURSES

W/ 3/8 " x 4" BOLTS 25mm


COUNTER SUNK 610 x 1220mm 8 GA WIRE
SCREENED WINDOW ROUNDED
& 3/4 " QT. RD. TIE CLIP
20 AMPERES OPENING MORTAR FOR EASTERN
MOULDING 600 TOP COURSE

2235
CIRCUIT BREAKER CAP TYPE WALL ONLY
2235

NO. 18 MESH SCREEN 400


2030

2030
2 COURSES

1830
1830

HIGHER WITH
1/2 " x 6"
10mm DIA.
EXPANSION JOINT
BARS
REFERENCE DRAWINGS
225

SEE
850

GROUND WIRE DETAIL-2


CONNECTOR STANDARD SEWER MANHOLE AB-036054

GRADE GRADE
400

2-12mm BARS MINIMUM REINF. FOR


CONTINUOUS ALL SIDES 1" 2 OF 8THWN 6" THICK WALL:
1 1/2 " FROM 1 #4 @ 1220mm (4’)
ALTERNATIVE
200

75 250 75 10mm DIA. TIE BARS 100mm CONCRETE SLAB WATER SUPPLY 100mm CONCRETE SLAB O.C. FOR 8"
W/ 6" x 6" WIRE MESH TO 120V W/ 6" x 6" WIRE MESH
400 @ +1200mm CTR. TO CTR. THICK WALLS
UNDERGROUND
SUPPLY
SECTION C-C REINFORCEMENT 1 #5 @ 1220mm (4’)
SCALE : 1:40 ALSO
PLACE VERT. BARS
SECTION A-A 610 AT ENDS OF
(TYP.) WALL AND
SCALE : 1:40 VERTICAL REINF. AT OPENING
(FILL CELLS
WIRE JOINT REINFORCING WITH GROUT)
REQUIRED IN ALTERNATE COURSES
FOR STACK BOND; USE 2-#9

(TYP.)
WIRE CRIMPED AND KNURLED,

610
SPACERS WELDED AT 457mm O.C.,
WIRE TO COMPLY WITH
ASTM A82; PLACE
SPACER WIRES DOWN

6100 6100
CONC. HOR. REINF.
610 4880 610 LINTEL
610 4880 610

2 PLY BUILT-UP ROOF 2 PLY BUILT-UP ROOF


ALTERNATIVE 3/4 " VENT TO ROOF
OVER 1/2 " PLYWOOD OVER 1/2 " PLYWOOD
TO 120V OVERHEAD 2" x 6" BLOCKING
SUPPLY 2" x 6" BLOCKING GRAVEL STOP
@ SIDES AND MIDDLE GRAVEL STOP @ SIDES AND MIDDLE
2 OF 8 THWN
1" x 3" MOULD FOOTING DOWEL:
3 OF 6 S.E.C. 1" x 3" MOULD #5 BAR AT 1220mm
(4’) O.C. MAXIMUM
CABLE SUPPORT 100W LAMP 2" x 6" FASCIA

300
100W LAMP 2" x 6" FASCIA 194mm BOND BEAM 20 AMP. AND AT THE ENDS
300

CONNECTOR W/16mm BAR FLY CHASER FAN CIRCUIT OF WALL


2" x 6" JOIST GROUTED SEE NOTE-2 BREAKER 2" x 6" JOIST
WEATHERHEAD @ +400mm CTR. TO CTR. @ +400mm CTR. TO CTR.
610 x 1830mm 200mm LINTEL
FLY CHASER FAN 2" x 8" PLATE WINDOW FRAME 2" x 8" PLATE
W/ 1/2 " x 8"
2030 (DOOR OPENING)
3048=15 COURSES

SEE NOTE-2 W/ 1/2 " x 8" W/ 3/8 " x 4" BOLTS


MACH. BOLTS FLOOR LN.
200mm LINTEL MACH. BOLTS COUNTER SUNK
ON 1200mm CTR. TO CTR. & 3/4 " QT. RD. ON 1200mm CTR. TO CTR.
20 AMPERES MOULDING 600
CIRCUIT BREAKER 1" x 3" TRIM NO. 18 MESH SCREEN 400
1" x 3" TRIM
BOTH SIDES
TYPICAL INSTALLATION DRAWING
2030

BOTH SIDES
1830

DETAIL-4
1830

1/2 " x 6" 15 5/8 " x 7 5/8 " x 7 5/8 " 15 5/8 " x 7 5/8 " x 7 5/8 "
EXPANSION JOINT CONC. STD. WALL BLOCK DOWELS
CONC. STD. WALL BLOCK NOT TO SCALE
225
850

15 5/8 " x 7 5/8 " x 3 5/8 "


GROUND WIRE 15 5/8 " x 7 5/8 "
CONC. PARTITION BLOCK
x 3 5/8 "
CONC. PARTITION BLOCK DETAIL-3
CONNECTOR

1 LAYER 0.7 Kg./m 1 LAYER 0.7 Kg./m2 NOT TO SCALE


01 11-01-88 RLO NEW DRAWING DIGITIZED IN CADD.
GRADE GRADE
FELT HOT MOPPED FELT HOT MOPPED VERTICAL AND HORIZONTAL REINFORCING BARS
BOTH SIDES @ TWO COURSES REV.
400

BOTH SIDES @ TWO AND ADDED AT THE EDGES OF THE OPENING DATE BY DESCRIPTION CHKD CERT. APPD.
2-12mm BARS NO.
COURSES AND EXTEND 610mm PAST THE EDGES OF THE OPENING
1" 2 OF 8THWN CONTINUOUS ALL SIDES
FOR ARABIAN AMERICAN OIL COMPANY
200

ALTERNATIVE 75 250 75 10mm DIA. TIE BARS ALTERNATIVE


TO 120V NO. 4 AWG BC HOR. REINF. TYP. MASONRY WALL BOND BEAM REINF. BARS
GROUND 400 @ +1200mm CTR. TO CTR. 1" 2 OF 8 TW RLO NAK SCALE: AS NOTED
UNDERGROUND BAR DRAWN BY CHECKED BY
DOWELS OUTSIDE BARS
SUPPLY 12mm DIA.
DATE STARTED 08-26-87
VERT. BARS DATE COMPLETED
ALL CORNERS
SECTION B-B FILL CELL OPR’G. DEPT. ENG. DEPT.ORIGINAL SIGNED
SCALE : 1:40 W/GROUT
APP’D. FOR CONST.

VERT. REINF. VERT. REINF. BARS THIS DRAWING IS NOT TO BE USED FOR CERTIFIED ORIGINAL SIGNED
SECTION D-D BAR CONSTRUCTION OR FOR ORDERING
DATE
MATERIAL UNTIL CERTIFIED AND DATED

SCALE : 1:40
PLAN, SECTIONS AND DETAILS
INSIDE BARS HAMMAM 4, 8, 12 AND 16 STALL

DETAIL-5 DETAIL-6 DETAIL-7 STD. DWG. METRIC


NOT TO SCALE NOT TO SCALE NOT TO SCALE PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.
THE BARS ARE LAPPED 30 BAR DIAMETERS THE REINFORCING SHALL LAP 30 BAR TRUSS TYPE
OR A MINIMUM OF 610mm DIAMETERS OR A MINIMUM OF 610mm JOINT REINFORCING 990 R AA-036011 001 01
ARAMCO A-2615 (11-84)

CADD