TEST REPORT

RELAY F35 GEN_1A

PROJECT : RETROFIT GENERATOR & PROTEKSI MAIN TRAFO UNIT 1 & 2

Contarct No. : 070/BDSN-GAE/VII/2020

Date : 17 SEPT 2020

Relay : GE MULTILIN UR F35

Type : FEDEER MANAGEMENT RELAY

Order Code : F35-W00-HEH-F8N-H6X-M6X-P6X-U7H-WRH

Serial Number : AAIC20000364

PT GUNA ELEKTRO PT. PJBS ASAHAN 1


Customer : PT. BDSN

PANEL : 17 SEPT 2020


MANUFACTURER : GE MULTILIN UR F35
TYPE OF RELAY : FEDEER MANAGEMENT RELAY
SERIAL NUMBER : AAIC20000364

TEST EQUIPMENT : Megger SMRT46

I. CURRENT METERING
Ratio CT Phase = 5000 : 1 A Source : 50BF
Secondary Measured
Expected
Metering test Injected Accuracy (%) Remarks
Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C
0.25 1250 1251 1231 1235 0.88% Ok
0.5 2500 2510 2490 2468 0.43% Ok
Phase Current
0.75 3750 3750 3678 3749 0.65% Ok
1 5000 5098 4988 4987 0.49% Ok

Ratio CT Phase = 100 : 1 A Source : SIDE EXCITATION


Secondary Measured
Expected
Metering test Injected Accuracy (%) Remarks
Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C
0.25 25 25 24 25 1.33% Ok
0.5 50 49 50 49 1.33% Ok
Phase Current
0.75 75 75 74 75 0.44% Ok
1 100 99 100 100 0.33% Ok

711556077.xlsx/Current Metering Page 2 of 8


Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

#REF!

PANEL : 17 SEPT 2020


MANUFACTURER : GE MULTILIN UR F35
TYPE OF RELAY : FEDEER MANAGEMENT RELAY
SERIAL NUMBER : AAIC20000364

TEST EQUIPMENT : FREJA 306

I. Phase TOC Unit (51 P)

51 P Pickup setting : 0.75 pu CT Pri : 4000 A


51 P Curva type : IEEE EXT INV CT Sec ; 5A
Time Dial setting : 2.65

Minimum pickup : 3.775 A

Inject Current Fault Expected Phase


(A) (%) Trip Time (ms) Trip Time (ms)
4.5 120% 0.6359
5.625 150% 0.3895
7.5 200% 25.2330 25.174
12 500% 3.4360 3.453
11.25 300% 0.1833
13.125 350% 0.1693
30 800% 0.1352

#REF!

Tested By #REF! Approved By


Guna Elektro #REF! #REF!

#REF! #REF! #REF!

711556077.xlsx/PTOC Page 3 of 8
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

#REF!

PANEL : 17 SEPT 2020


MANUFACTURER : GE MULTILIN UR F35
TYPE OF RELAY : FEDEER MANAGEMENT RELAY
SERIAL NUMBER : AAIC20000364

TEST EQUIPMENT : FREJA 300

I. Phase TOC Voltage Restrained Unit (51 P)

51 P Pickup setting : 0.9 pu CT Pri : #REF! A


51 P Curva type : IAC Short Inverse CT Sec ; 5A
Time Dial setting : 16
V inj : 83%

Inject Current Fault Expected Phase


(A) (%) Trip Time (ms) Trip Time (ms)
5.4 120% 3.8397 2.478
6.75 150% 2.3516 1.681
9 200% 1.5451 1.293
11.25 250% 1.2514 1.106
13.5 300% 1.1068 1.007
15.75 350% 1.0223 0.947
18 400% 0.9673 0.905
22.5 500% 0.9001 0.859
27 600% 0.8607 0.821
31.5 700% 0.8348 0.814
36 800% 0.8164 0.778

#REF!

Tested By #REF! Approved By


Guna Elektro #REF! #REF!

#REF! #REF! #REF!

711556077.xlsx/PTOC VREST Page 4 of 8


Ground Time Overcurrent Functions (ANSI Devices 51G)

Phase Trip Time (ms)

10
Trip time (second)

0.1
100% 1000%
I fault

711556077.xlsx/PTOC VREST Page 5 of 8


Customer : PT. BDSN

PANEL : 17 SEPT 2020


MANUFACTURER : GE MULTILIN UR F35
TYPE OF RELAY : FEDEER MANAGEMENT RELAY
SERIAL NUMBER : AAIC20000364

TEST EQUIPMENT : Megger SMRT46

1. PHASE OVERCURRENT (51P)_50BF

51 Pickup setting 0.88 pu CT Pri 5000 A


51 Time Delay 0.2 s CT Sec 1A

Pickup Value 0.881 A


Dropout 0.855 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 0.2 0.229 0.145
3 0.2 0.232 0.16

TEST FUNCTION : INJECTION ABC SOURCE (50BF)


TRIP TARGET :
FIELD CB TRIP FIELD CB TRIP START BF STOP TURBIN TRIP GCB TRIP GCB REDUCE EXCITATION

INTERTRIP 275kV initatiate CBF


Note : Breaker condition Closed

2. PHASE INSTANT OVERCURRENT (50P)_ET. OVERCURRENT

50 Pickup setting 0.47 pu CT Pri 100 A


50 Time Delay 0.5 s CT Sec 1A

Pickup Value 0.466 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 0.5 0.51 0.0200
3 0.5 0.510 0.0200

TEST FUNCTION : INJECTION ABC SOURCE (EXCITATION TRANS)


TRIP TARGET :
FIELD CB TRIP FIELD CB TRIP START BF STOP TURBIN TRIP GCB TRIP GCB REDUCE EXCITATION
√ √ √ √ √ √

INTERTRIP 275kV

711556077.xlsx/51P Page 6 of 8
Customer : PT. BDSN

PANEL : 17 SEPT 2020


MANUFACTURER : GE MULTILIN UR F35
TYPE OF RELAY : FEDEER MANAGEMENT RELAY
SERIAL NUMBER : AAIC20000364

TEST EQUIPMENT : Megger SMRT46

3. PHASE INSTANT OVERCURRENT (50P)_ET. INSTANT OVERCURRENT

50 Pickup setting : 7.5 pu CT Pri 100 A


50 Time Delay : 0.1 s CT Sec 1A

Pickup Value 7.462 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
7.8 0.1 0.126 0.2600
8.0 0.1 0.127 0.2700

TEST FUNCTION : INJECTION ABC SOURCE (EXCITATION TRANS)


TRIP TARGET :
FIELD CB TRIP FIELD CB TRIP START BF STOP TURBIN TRIP GCB TRIP GCB REDUCE EXCITATION
√ √ √ √ √ √

INTERTRIP 275kV

4. NETRAL OVERCURRENT (51N)_50BF

51 Pickup setting : 0.168 pu CT Pri 5000 A


51 Time Delay : 0.2 s CT Sec 1A

Pickup Value 0.168 A


Dropout 0.164 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 0.2 0.229 0.145
3 0.2 0.224 0.120

TEST FUNCTION : INJECTION AN SOURCE (50BF)


TRIP TARGET :
FIELD√√CB TRIP FIELD CB TRIP START BF STOP TURBIN TRIP GCB TRIP GCB REDUCE EXCITATION

INTERTRIP 275kV initatiate CBF


Note test : Breaker Condition Closed

711556077.xlsx/51P_2 Page 7 of 8
Customer : PT. BDSN

PANEL : 17 SEPT 2020


MANUFACTURER : GE MULTILIN UR F35
TYPE OF RELAY : FEDEER MANAGEMENT RELAY
SERIAL NUMBER : AAIC20000364

TEST EQUIPMENT : Megger SMRT46

5. NETRAL OVERCURRENT (51N)_50BF

51 Pickup setting : 0.1 pu CT Pri 5000 A


51 Time Delay : 0.2 s CT Sec 1A

Pickup Value 0.101 A


Dropout 0.099 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 2 2.028 0.014
3 2 2.04 0.020

TEST FUNCTION : INJECTION AN SOURCE (50BF)


TRIP TARGET : No action for matrik

711556077.xlsx/51N Page 8 of 8