I. CURRENT METERING
Ratio CT Phase = 750 : 1 A Source : SIDE 275kV
Secondary Measured
Expected
Metering test Injected Accuracy (%) Remarks
Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C
0.25 187.5 186,97 185,23 186.79 0.62% Ok
0.5 375 375 374 375 0.09% Ok
Phase Current
0.75 562.5 562 561 562 0.15% Ok
1 750 749 750 751 0.00% Ok
#REF!
#REF!
711556084.xlsx/PTOC Page 3 of 10
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id
#REF!
#REF!
10
Trip time (second)
0.1
100% 1000%
I fault
1. OVERALL DIFERENSIAL
SRC 1 SRC 2
Set Pickup : 0.34 pu 275kV 13,8 kV
Slope 1 : 30 % CT Pri : 750 5000 A
Break 1 : 1 pu CT Sec : 1 1A
Slope 2 : 90 % ramp side 275kV
Break 1 : 8 pu Source 1 side 275kV
Source 2 side 13,8 kV
1.40
1.27
1.20
1.00
0.80
0.60
0.56
0.40
0.29
0.20
0.11
0.00
0.11 0.45 0.75 1.49
Column E
CURRENT INJECTION Id Ir
Slope
I HV (275kV) I LV (13,8kV)
A pu A pu pu pu %
0.11 0.11 0.00 0.00 0.11 0.11 pkp
0.16 0.16 0.15 0.45 0.29 0.45 64.31%
0.19 0.19 0.25 0.75 0.56 0.75 74.57%
0.22 0.22 0.50 1.49 1.27 1.49 85.28%
TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIPINTERTRIP BI CB02_1 CB02_1 STOP GEN START CF
√ √ √ √ √ √
Customer : PT BDSN
Inject Current
Target (s) Actual (s) Error (%)
(A)
2 0.5 0.516 0.032
3 0.5 0.52 0.04
Inject Current
Target (s) Actual (s) Error (%)
(A)
2 9 9.01 0.0011
3 9 9.02 0.0022
711556084.xlsx/51P Page 7 of 10
Customer : PT BDSN
Inject Current
Target (s) Actual (s) Error (%)
(A)
2 1 1.009 0.0090
3 1 1.03 0.0300
Inject Current
Target (s) Actual (s) Error (%)
(A)
2 0.75 0.788 0.051
3 0.75 0.79 0.053
TEST FUNCTION :
TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN START CF
√ √ √ √ √ √
TEST EQUIPMENTMegger
: SMRT46
Inject Current
Target (s) Actual (s) Error (%)
(A)
2 2 2.044 0.022
3 2 2.036 0.018
Inject Voltage
Target (s) Actual (s) Error (%)
(Vp-p)
135 5 5.148 0.03
140 5 5.028 0.01
711556084.xlsx/51G Page 9 of 10
Customer : PT BDSN
Inject Voltage
Target (s) Actual (s) Error (%)
(Vp-p)
147 3 3.107 0.04
150 3 3.076 0.03
TEST FUNCTION :
TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN START CF
√ √ √ √ √ √
9. PHASE UV
Inject Voltage
Target (s) Actual (s) Error (%)
(Vp-N)
50 1 1.023 0.023
40 1 1.023 0.023
711556084.xlsx/24 Page 10 of 10