TEST REPORT

FACTORY ACCEPTION TEST

PROTECTION RELAY

Location : WORKSHOP C-SAT

Date : 30/1/2024

Panel : PROTECTION PANEL TRANSFORMER 150/20kV 140MVA

Relay : GE MULTILIN

Type : F35 FEEDER PROTECTION SYSTEM

Order Code : F35-WC3-HKH-F8L-H6N-M8N-P6C-U8N-W6N

Serial Number : AAIC2000947

Hasil Akhir : Baik / Tidak Baik

Note :

Tested Witness

PT GAE ADVAN ENERGI PT SULFINDO ADIUSAHA


Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

Customer : PT SULFINDO ADIUSAHA


Equip No : PROTECTION PANEL TRANSFORMER 150/20kV 140MVA
Manufacture : F35 FEEDER PROTECTION SYSTEM
Type of Relay : GE MULTILIN
Serial number : AAIC2000947
Odercode : F35-WC3-HKH-F8L-H6N-M8N-P6C-U8N-W6N
Test Equipment : SMRT 46

I. CURRENT METERING AND VOLTAGE METERING (PRE FAT)

Setting
OUT1 CT Primary : 1000 A OUT3 CT Primary : 1000 A
OUT1 CT Secondary :1 A OUT3 CT Secondary :1 A
OUT2 CT Primar : 1000 A OUT4 CT Primary : 1000 A
OUT2 CT Secondary : 1 A OUT4 CT Secondary :1 A

OUT1 CURRENT METERING


Secondary Measured
Expected % Error
Metering test Injected Current (Amp) Remarks
Current(A) Current(A) Phase A Phase B Phase C Pass < 5% error

0,25 250 248,4 248,68 247,64 0,70% Pass


0,50 500 497,85 497,9 498,05 0,41% Pass
Phase Current
0,75 750 747,41 748,001 747,78 0,30% Pass
1,00 1000 997,55 997,7 997,97 0,23% Pass

OUT2 CURRENT METERING


Secondary Measured
Expected % Error
Metering test Injected Current (Amp) Remarks
Current(A) Current(A) Phase A Phase B Phase C Pass < 5% error
0,25 250 244,34 256,9 256,65 1,05% Pass
0,50 500 497,223 499,01 498,84 0,33% Pass
Phase Current
0,75 750 747,24 749,48 748,28 0,22% Pass
1,00 1000 997,11 999,02 997,32 0,22% Pass

OUT3 CURRENT METERING


Secondary Measured
Expected % Error
Metering test Injected Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C Pass < 5% error
0,25 250 247,97 248,12 247,84 0,81%
0,50 500 497,34 497,72 497,63 0,49%
Phase Current
0,75 750 746,84 747,82 748,42 0,31%
1,00 1000 996,6 996,89 998,1 0,28%

OUT4 CURRENT METERING


Secondary Measured
Expected % Error
Metering test Injected Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C Pass < 5% error
0,25 250 248,99 259,11 256,95 2,01%
0,50 500 496,83 498,97 499,34 0,32%
Phase Current
0,75 750 746,76 748,82 747,96 0,29%
1,00 1000 996,47 999,07 996,99 0,25%
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

Customer : PT SULFINDO ADIUSAHA

Equip No : PROTECTION PANEL TRANSFORMER 150/20kV 140MVA


Manufacture : F35 FEEDER PROTECTION SYSTEM
Type of Relay : GE MULTILIN
Serial number : AAIC2000947
Odercode : F35-WC3-HKH-F8L-H6N-M8N-P6C-U8N-W6N
Test Equipment : SMRT 46

I. CURRENT METERING AND VOLTAGE METERING (FAT)

Setting
OUT1 CT Primary : 2500 A OUT3 CT Primary : 2500 A
OUT1 CT Secondary :1 A OUT3 CT Secondary :1 A
OUT2 CT Primar : 2500 A OUT4 CT Primary : 2500 A
OUT2 CT Secondary : 1 A OUT4 CT Secondary :1 A

OUT1 CURRENT METERING


Secondary Measured
Expected Error
Metering test Injected Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C (%)
0,50 1250 1242 1248 1248 0,32%
Phase Current 0,75 1875 1868 1874 1873 0,18%
1,00 2500 2493 2498 2494 0,20%

OUT2 CURRENT METERING


Secondary Measured
Expected Error
Metering test Injected Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C (%)
0,50 1250 1244 1245 1245 0,43%
Phase Current 0,75 1875 1868 1869 1869 0,34%
1,00 2500 2493 2493 2495 0,25%

OUT3 CURRENT METERING


Secondary Measured
Expected Error
Metering test Injected Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C (%)
0,50 1250 1244 1249 1252 0,13%
Phase Current 0,75 1875 1868 1873 1871 0,23%
1,00 2500 2492 2497 2495 0,21%

OUT4 CURRENT METERING


Secondary Measured
Expected Error
Metering test Injected Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C (%)
0,50 1250 1244 1245 1246 0,40%
Phase Current 0,75 1875 1869 1868 1870 0,32%
1,00 2500 2494 2493 2495 0,24%

Setting
Phase VT Primary : 20 kV
Phase VT Secondary : 100 V

PHASE VOLTAGE METERING


Secondary Measured
Expected Error
Metering test Injected Voltage (KV)
Voltage(V) Voltage(KV) Phase AB Phase BC Phase CA (%)
43,30 15 14,991 14,998 14,997 0,03%
Phase Voltage
57,74 20 19,999 20,004 20,001 0,01%
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

Customer : PT SULFINDO ADIUSAHA


Equip No : : PROTECTION PANEL TRANSFORMER 150/20kV 140MVA
Manufacture : F35 FEEDER PROTECTION SYSTEM
Type of Relay : GE MULTILIN
Serial number : AAIC2000947
Odercode : F35-WC3-HKH-F8L-H6N-M8N-P6C-U8N-W6N
Test Equipment : SMRT 46

II. CONTACT CT & VT

Testing Output Name Contact Marker Contact TB TO TB TO HV


Remark
Relays Relay Relay RELAY APPARATUS

F5a XF35.1-2
VT PHASE A - P
F5c F6c
F6a XF35.1-4
VT PHASA VT PHASE B - P
F6c F7c
F7a XF35.1-6
VT PHASE C - P
F7c XF35.1-8
M1c XF35.2-2
CT PHASE A - P
M1b M2b
M2c XF35.2-4
CT PHASE B - P
M2b M3b
CT PHASA OUT1
M3c XF35.2-6
CT PHASE C - P
M3b M4c
M4c M3b
CT PHASE GROUND - P
M4b XF35.2-8
M5c XF35.2-22
CT PHASE A - P
M5b M6b
M6c XF35.2-24
CT PHASE B - P
M6b M7b
CT PHASA OUT2
M7c XF35.2-26
CT PHASE C - P
M7b M8c
M8c M7b
CT PHASE GROUND - P
M8b XF35.2-28
U1c XF35.3-2
CT PHASE A - P
U1b U2b
U2c XF35.3-4
CT PHASE B - P
U2b U3b
CT PHASA OUT3
U3c XF35.3-6
CT PHASE C - P
U3b U4c
U4c U3b
CT PHASE GROUND - P
U4b XF35.3-8
U5c XF35.3-22
CT PHASE A - P
U5b U6b
U6c XF35.3-24
CT PHASE B - P
U6b U7b
CT PHASA OUT4
U7c XF35.3-26
CT PHASE C - P
U7b U8c
U8c U7b
CT PHASE GROUND - P
U8b XF35.3-28
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

Customer : PT SULFINDO ADIUSAHA


Equip No : PROTECTION PANEL TRANSFORMER 150/20kV 140MVA
Manufacture : F35 FEEDER PROTECTION SYSTEM
Type of Relay : GE MULTILIN
Serial number : AAIC2000947
Odercode : F35-WC3-HKH-F8L-H6N-M8N-P6C-U8N-W6N
Test Equipment : SMRT 46

III. CONTACT OUTPUT

Testing Output Name Contact Marker Contact TB TO TB TO HV


Remark
Relays Relay Relay RELAY APPARATUS

H1c X4.2-2 -
R-1 TRIP OUTGOING-1 P
H1b X4.2-1 -
H2c X4.2-4 -
R-2 CLOSE CB OUTGOING-1 P
H2b X4.2-3 -
H3c X4.2-6 -
R-3 TRIP OUTGOING-2 P
H3b X4.2-5 -
H4c X4.2-8 -
R-4 CLOSE CB OUTGOING-2 P
H4b X4.2-7 -
H5c X4.2-10 -
R-5 TRIP OUTGOING-3 P
H5b X4.2-9 -
H6c X4.2-12 -
R-6 CLOSE CB OUTGOING-3 P
H6b X4.2-11 -
H7c X4.2-14 -
R-7 TRIP OUTGOING-4 P
H7b X4.2-13 -
H8c X4.2-16 -
R-8 CLOSE CB OUTGOING-4 P
H8b X4.2-15 -
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

Customer : PT SULFINDO ADIUSAHA


Equip No : PROTECTION PANEL TRANSFORMER 150/20kV 140MVA
Manufacture : F35 FEEDER PROTECTION SYSTEM
Type of Relay : GE MULTILIN
Serial number : AAIC2000947
Odercode : F35-WC3-HKH-F8L-H6N-M8N-P6C-U8N-W6N
Test Equipment : SMRT 46

IV. CONTACT INPUT

Testing Inputs Name Contact Marker Contact TB TO HV


TB TO RELAY Remarks
Relays Relay Relay APPARATUS

1 52A OUTGOING-1 H5a X4.2-1 - P


2 52B OUTGOING-1 H5c X4.2-2 - P
3 52A OUTGOING-2 H6a X4.2-3 - P
4 52B OUTGOING-2 H6c X4.2-4 - P
Common Common(-) H5b -S - P
5 52A OUTGOING-3 H7a X4.2-5 - P
6 52B OUTGOING-3 H7c X4.2-6 - P
7 52A OUTGOING-4 H8a X4.2-7 - P
8 52B OUTGOING-4 H8c X4.2-8 - P
Common Common(-) H7b -S - P
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

Customer : PT SULFINDO ADIUSAHA


Equip No : PROTECTION PANEL TRANSFORMER 150/20kV 140MVA
Manufacture : F35 FEEDER PROTECTION SYSTEM
Type of Relay : GE MULTILIN
Serial number : AAIC2000947
Odercode : F35-WC3-HKH-F8L-H6N-M8N-P6C-U8N-W6N
Test Equipment : SMRT 46

FUNCTION TEST

Elemen Proteksi Function Indikasi Remarks

Led 14,Trip PTOC1,


Phase Time Overcurrent 1 ( 51P ) TRIP OK
Phase A, B, C
Led 15,Trip, PIOC1,
Phase Instantaneous Overcurrent 1 ( 50P ) TRIP OK
Phase A, B, C
Led 16,Trip, GTOC1,
Ground Time Overcurrent 1 ( 51G ) TRIP OK
Phase A, B, C
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

Customer : PT SULFINDO ADIUSAHA


Equip No : PROTECTION PANEL TRANSFORMER 150/20kV 140MVA
Manufacture : F35 FEEDER PROTECTION SYSTEM
Type of Relay : GE MULTILIN
Serial number : AAIC2000947
Odercode : F35-WC3-HKH-F8L-H6N-M8N-P6C-U8N-W6N
Test Equipment : SMRT 46

FUNCTION TEST

Elemen Proteksi Function Indikasi Remarks

Led 20,Trip PTOC2,


Phase Time Overcurrent 2 ( 51P ) TRIP OK
Phase A, B, C
Led 21,Trip, PIOC2,
Phase Instantaneous Overcurrent 2 ( 50P ) TRIP OK
Phase A, B, C
Led 22,Trip, GTOC2,
Ground Time Overcurrent 2 ( 51G ) TRIP OK
Phase A, B, C
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

Customer : PT SULFINDO ADIUSAHA


Equip No : PROTECTION PANEL TRANSFORMER 150/20kV 140MVA
Manufacture : F35 FEEDER PROTECTION SYSTEM
Type of Relay : GE MULTILIN
Serial number : AAIC2000947
Odercode : F35-WC3-HKH-F8L-H6N-M8N-P6C-U8N-W6N
Test Equipment : SMRT 46

FUNCTION TEST

Elemen Proteksi Function Indikasi Remarks

Led 26,Trip PTOC3,


Phase Time Overcurrent 3 ( 51P ) TRIP OK
Phase A, B, C
Led 27,Trip, PIOC3,
Phase Instantaneous Overcurrent 3 ( 50P ) TRIP OK
Phase A, B, C
Led 28,Trip, GTOC3,
Ground Time Overcurrent 3 ( 51G ) TRIP OK
Phase A, B, C
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

Customer : PT SULFINDO ADIUSAHA


Equip No : PROTECTION PANEL TRANSFORMER 150/20kV 140MVA
Manufacture : F35 FEEDER PROTECTION SYSTEM
Type of Relay : GE MULTILIN
Serial number : AAIC2000947
Odercode : F35-WC3-HKH-F8L-H6N-M8N-P6C-U8N-W6N
Test Equipment : SMRT 46

FUNCTION TEST

Elemen Proteksi Function Indikasi Remarks

Led 32,Trip PTOC4,


Phase Time Overcurrent 4 ( 51P ) TRIP OK
Phase A, B, C
Led 33,Trip, PIOC4,
Phase Instantaneous Overcurrent 4 ( 50P ) TRIP OK
Phase A, B, C
Led 34,Trip, GTOC4,
Ground Time Overcurrent 4 ( 51G ) TRIP OK
Phase A, B, C