TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

HASIL PENGUJIAN DIFFERENTIAL RELAY TRANSFORMER F87T


Lokasi : GI Tangerang Lama Ratio CT sisi Primer : 300 / 5A
Bay : Trafo-05 Ratio CT sisi Sekunder : 2000 / 5A
Ratio sisi Terseier : -
Project :
Merk / Type : Schneider P642 No. Seri : 39672180/09/18 Rating In : 5A

No.
1 Pengujian arus kerja minimum
Setting I op : 0.3 pu Hasil Uji IR : HV side 1.15 A & LV side 1.5 A
IS : HV side 1.15 A & LV side 1.5 A
IT : HV side 1.15 A & LV side 1.5 A

2 Pengujian Harmonic Blocking


Setting 2nd harmonic blockir : 15% Hasil Uji 2nd harmonic : Block
5th harmonic blockir : 30% 5th harmonic : Block

3 Pengujian slope differential


Setting Slope 1 : 30% Hasil Uji Slope 1 : 0.3012
Slope 2 : 80% Slope 2 : 0.8

Fasa Pengukuran Stn


I1 HV A 1.892
I2 LV A 1
Idiff Pu
Ibias Pu

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 23 November 2018


METER REFERENCE : CT Ratio 300 / 5 A
VT Ratio 150000 / 100 V
MEASURE AT : METER CONTROL PANEL SISI HV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MVar) (MVar)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=270ᵒ

0% MVAR (NEG) 0 0 0 OK
25% -19.485 -19.4 -0.44 OK
50% -38.97 -38.84 -0.33 OK
75% -58.455 -58.28 -0.30 OK
100% -77.94 -77.69 -0.32 OK

MEASURE AT : METER CONTROL PANEL SISI HV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MW) (MW)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=180ᵒ

0% MW (NEG) 0 0 0 OK
25% -19.485 -19.4 -0.44 OK
50% -38.97 -38.82 -0.38 OK
75% -58.455 -58.25 -0.35 OK
100% -77.94 -77.64 -0.38 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujain : 23 November 2018


METER REFERENCE : CT Ratio 300 / 5 A
VT Ratio 150000 / 100 V
MEASURE AT : METER CONTROL PANEL SISI HV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MVar) (MVar)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=90ᵒ

0% MVAR (POS) 0 0 0 OK
25% 19.485 19.41 -0.38 OK
50% 38.97 38.85 -0.31 OK
75% 58.455 58.3 -0.27 OK
100% 77.94 77.71 -0.30 OK

MEASURE AT : METER CONTROL PANEL SISI HV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MW) (MW)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=0ᵒ

0% MW (POS) 0 0 0 OK
25% 19.485 19.43 -0.28 OK
50% 38.97 38.89 -0.21 OK
75% 58.455 58.35 -0.18 OK
100% 77.94 77.78 -0.21 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 22 November 2018


METER REFERENCE : CT Ratio 2000 / 5 A
VT Ratio 20000 / 100 V
MEASURE AT : METER CONTROL PANEL SISI LV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MVar) (MVar)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=270ᵒ

0% MVAR (NEG) 0 0 0 OK
25% -17.32 -17.29 -0.17 OK
50% -34.64 -34.53 -0.32 OK
75% -51.96 -51.81 -0.29 OK
100% -69.28 -69.08 -0.29 OK

MEASURE AT : METER CONTROL PANEL SISI LV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MW) (MW)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=180ᵒ

0% MW (NEG) 0 0 0 OK
25% -17.32 -17.24 -0.46 OK
50% -34.64 -34.5 -0.40 OK
75% -51.96 -51.96 0.00 OK
100% -69.28 -69.28 0.00 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 22 November 2018


METER REFERENCE : CT Ratio 2000 / 5 A
VT Ratio 20000 / 100 V
MEASURE AT : METER CONTROL PANEL SISI LV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MVar) (MVar)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=90ᵒ

0% MVAR (POS) 0 0 0 OK
25% 17.32 17.26 -0.35 OK
50% 34.64 34.55 -0.26 OK
75% 51.96 51.84 -0.23 OK
100% 69.28 69.13 -0.22 OK

MEASURE AT : METER CONTROL PANEL SISI LV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(W) (W)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=0ᵒ

0% MW (POS) 0 0 0 OK
25% 17.32 17.29 -0.17 OK
50% 34.64 34.59 -0.14 OK
75% 51.96 51.9 -0.12 OK
100% 69.28 69.2 -0.12 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 21 November 2018


METER REFERENCE : VT Ratio 20000 / 100 V
MEASURE AT : VOLT METER CONTROL PANEL

VALUE RESULT
INJECTION PHASE
CALCULATE DISPLAY
ERROR (%) OK/NOK
(kV) (kV)
I = 0 - 57.74 V
0% 0 0 0 0 OK
25% 14,43 V 2.75 2.89 5.09 OK
V R-N
50% 28,87 V 5.5 5.78 5.09 OK
75% 43,31 V 8.25 8.64 4.73 OK
100% 57,74 V 11 11.52 4.73 OK
I = 0 - 57.74 V
0% 0 0 0 0 OK
25% 14,43 V 2.75 2.88 4.73 OK
V S-N
50% 28,87 V 5.5 5.76 4.73 OK
75% 43,31 V 8.25 8.63 4.61 OK
100% 57,74 V 11 11.52 4.73 OK
I = 0 - 57.74 V
0% 0 0 0 0 OK
25% 14,43 V 2.75 2.89 5.09 OK
V T-N
50% 28,87 V 5.5 5.78 5.09 OK
75% 43,31 V 8.25 8.65 4.85 OK
100% 57,74 V 11 11.53 4.82 OK
I = 0 - 100 V
0% 0 0 0 0 OK
25% 25 V 5 5 0.00 OK
V R-S
50% 50 V 10 9.99 -0.10 OK
75% 75 V 15 14.99 -0.07 OK
100% 100 V 20 20 0.00 OK
I = 0 - 100 V
0% 0 0 0 0 OK
25% 25 V 5 5.02 0.40 OK
V R-T
50% 50 V 10 10.01 0.10 OK
75% 75 V 15 14.94 -0.40 OK
100% 100 V 20 19.9 -0.50 OK
I = 0 - 100 V
0% 0 0 0 0 OK
25% 25 V 5 5.2 4.00 OK
V S-T
50% 50 V 10 9.93 -0.70 OK
75% 75 V 15 14.97 -0.20 OK
100% 100 V 20 20 0.00 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 21 November 2018


METER REFERENCE : VT Ration 150000 / 100 V
MEASURE AT : VOLT METER CONTROL PANEL

VALUE RESULT
INJECTION PHASE
CALCULATE DISPLAY
ERROR (%) OK/NOK
(kV) (kV)
I = 0 - 57.74 V
0% 0 0 0 0 OK
25% 14,43 V 21.67 21.63 -0.18 OK
V R-N
50% 28,87 V 43.35 43.3 -0.12 OK
75% 43,31 V 65.03 64.93 -0.15 OK
100% 57,74 V 86.7 86.47 -0.27 OK
I = 0 - 57.74 V
0% 0 0 0 0 OK
25% 14,43 V 21.67 21.671 0.00 OK
V S-N
50% 28,87 V 43.35 43.351 0.00 OK
75% 43,31 V 65.03 64.93 -0.15 OK
100% 57,74 V 86.7 86.478 -0.26 OK
I = 0 - 57.74 V
0% 0 0 0 0 OK
25% 14,43 V 21.67 132.1 0.01 OK
V T-N
50% 28,87 V 43.35 264.1 0 OK
75% 43,31 V 65.03 400 0.1 OK
100% 57,74 V 86.7 480.2 -0.05 OK
I = 0 - 100 V
0% 0 0 0 0 OK
25% 25 V 37.5 37.471 -0.08 OK
V R-S
50% 50 V 75 75.012 0.02 OK
75% 75 V 112.5 112.48 -0.02 OK
100% 100 V 150 150 0.00 OK
I = 0 - 100 V
0% 0 0 0 0 OK
25% 25 V 37.5 37.51 0.03 OK
V R-T
50% 50 V 75 74.944 -0.07 OK
75% 75 V 112.5 112.512 0.01 OK
100% 100 V 150 150.1 0.07 OK
I = 0 - 100 V
0% 0 0 0 0 OK
25% 25 V 37.5 37.511 0.03 OK
V S-T
50% 50 V 75 75.058 0.08 OK
75% 75 V 112.5 112.519 0.02 OK
100% 100 V 150 150 0.00 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 19 November 2018


METER REFERENCE : CT Ratio 300 / 5A
MEASURE AT : AMPERE METER CONTROL PANEL

VALUE RESULT
INJECTION PHASE
CALCULATE DISPLAY
ERROR (%) OK/NOK
(A) (A)
I = 0 - 1.2 A
0% 0 0 0 0 OK
25% 0.33 19.8 19.78 -0.10 OK
I-R
50% 0.66 39.6 39.59 -0.03 OK
75% 1 60 59.99 -0.02 OK
100% 1.2 72 72.08 0.11 OK
I = 0 - 1.2 A
0% 0 0 0 0 OK
25% 0.33 19.8 131.6 -0.0505051 OK
I-S
50% 0.66 39.6 264.1 -0.05 OK
75% 1 60 400.1 0.08 OK
100% 1.2 72 480.4 -0.08 OK
I = 0 - 1.2 A
0% 0 0 0 0 OK
25% 0.33 19.8 132.1 -0.05 OK
I-T
50% 0.66 39.6 264.1 -0.03 OK
75% 1 60 400 0.05 OK
100% 1.2 72 480.2 0 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 19 November 2018


METER REFERENCE : CT Ratio 2000 / 5A
MEASURE AT : AMPERE METER CONTROL PANEL

VALUE RESULT
INJECTION PHASE
CALCULATE DISPLAY
ERROR (%) OK/NOK
(A) (A)
I = 0 - 1.2 A
0% 0 0 0 0 OK
25% 0.33 132 131.7 -0.23 OK
I-R
50% 0.66 264 264.2 0.08 OK
75% 1 400 400.6 0.15 OK
100% 1.2 480 480.1 0.02 OK
I = 0 - 1.2 A
0% 0 0 0 0 OK
25% 0.33 132 131.6 -0.30 OK
I-S
50% 0.66 264 264.1 0.04 OK
75% 1 400 400.1 0.03 OK
100% 1.2 480 480.4 0.08 OK
I = 0 - 1.2 A
0% 0 0 0 0 OK
25% 0.33 132 132.1 0.08 OK
I-T
50% 0.66 264 264.1 0.04 OK
75% 1 400 400 0.00 OK
100% 1.2 480 480.2 0.04 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :