TEST REPORT

RELAY T60 UNIT 1B

PROJECT : RETROFIT GENERATOR & PROTEKSI MAIN TRAFO UNIT 1 & 2

Contarct No. : 070/BDSN-GAE/VII/2020

Date : 13 SEPT 2020

Relay : GE MULTILIN UR T60

Type : TRANSFORMER MANAGEMENT RELAY

Order Code : T60-W00-HEH-F8L-H6W-M8N-P6X-U7H-WRH

Serial Number : ABHC20000833

PT GUNA ELEKTRO PT. PJBS ASAHAN 1


Customer : PT BDSN

PANEL : 13 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000833

TEST EQUIPMENT : Megger SMRT46

I. CURRENT METERING
Ratio CT Phase = 750 : 1 A Source : SIDE 275kV
Secondary Measured
Expected
Metering test Injected Accuracy (%) Remarks
Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C
0.25 187.5 186,81 185,23 186.79 0.65% Ok
0.5 375 376 377 375 0.27% Ok
Phase Current
0.75 562.5 561 562 561 0.21% Ok
1 750 749 748 751 0.09% Ok

Ratio CT Phase = 5000 : 1 A (SUM M1+M5) Source : SIDE 13.8kV


Secondary Measured
Expected
Metering test Injected Accuracy (%) Remarks
Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C
0.25 1250 1250 1249 1248 0.08% Ok
0.5 2500 2501 2492 2498 0.12% Ok
Phase Current
0.75 3750 3749 3745 3754 0.02% Ok
1 5000 5000 4988 4998 0.09% Ok

Ratio CT Phase = 5000 : 1 A Source : SIDE GEN


Secondary Measured
Expected
Metering test Injected Accuracy (%) Remarks
Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C
0.25 1250 1249 1250 1248 0.08% Ok
0.5 2500 2498 2499 2501 0.03% Ok
Phase Current
0.75 3750 3749 3745 3749 0.06% Ok
1 5000 5000 4999 4999 0.01% Ok

Ratio CT Phase = 5000 : 1 A Source : AUX TRAFO


Secondary Measured
Expected
Injected
Metering test Current (Amp) Accuracy (%) Remarks

Current(A) Current(A) Phase A Phase B Phase C


0.25 1250 1249 1251 1250 0.00% Ok
0.5 2500 2489 2498 2499 0.19% Ok
Phase Current
0.75 3750 3750 3751 3749 0.00% Ok
1 5000 5001 4999 4999 0.01% Ok

711556050.xlsx/Current Metering Page 2 of 10


Customer : PT BDSN

PANEL : 14 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000832

TEST EQUIPMENT : Megger SMRT46

1. OVERALL DIFERENSIAL
SRC 1 SRC 2
Set Pickup : 0.34 pu 275kV 13,8 kV
Slope 1 : 30 % CT Pri : 750 5000 A
Break 1 : 1 pu CT Sec : 1 1A
Slope 2 : 90 % ramp side 275kV
Break 1 : 8 pu Source 1 side 275kV
Source 2 side 13,8 kV

1.40

1.27
1.20

1.00

0.80

0.60
0.57

0.40
0.29
0.20
0.11
0.00
0.11 0.45 0.75 1.49

Column E

CURRENT INJECTION Id Ir
Slope
I HV (275kV) I LV (13,8kV)
A pu A pu pu pu %
0.11 0.11 0.00 0.00 0.11 0.11 pkp
0.16 0.16 0.15 0.45 0.29 0.45 64.31%
0.18 0.18 0.25 0.75 0.57 0.75 75.91%
0.22 0.22 0.50 1.49 1.27 1.49 85.28%

Pickup Value 275kV 0.11 A


Pickup Value 13,8 kV 0.32 A
Trip Time
Injected Current (A) Target (ms) Error (%)
(ms)
0,2 (LV) 50 35 0.3
0,4 (LV) 50 36 0.28

TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIPINTERTRIP BI CB02_1 CB02_1 STOP GEN STOP GEN
√ √ √ √ √ √ √

START CBF

Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

#REF!

PANEL : 13 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000833

TEST EQUIPMENT : FREJA 306

I. Phase TOC Unit (51 P)

51 P Pickup setting : 0.75 pu CT Pri : 4000 A


51 P Curva type : IEEE EXT INV CT Sec ; 5A
Time Dial setting : 2.65

Minimum pickup : 3.775 A

Inject Current Fault Expected Phase


(A) (%) Trip Time (ms) Trip Time (ms)
4.5 120% 0.6359
5.625 150% 0.3895
7.5 200% 25.2330 25.174
12 500% 3.4360 3.453
11.25 300% 0.1833
13.125 350% 0.1693
30 800% 0.1352

#REF!

Tested By #REF! Approved By


Guna Elektro #REF! #REF!

#REF! #REF! #REF!

711556050.xlsx/PTOC Page 4 of 10
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

#REF!

PANEL : 13 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000833

TEST EQUIPMENT : FREJA 300

I. Phase TOC Voltage Restrained Unit (51 P)

51 P Pickup setting : 0.9 pu CT Pri : #REF! A


51 P Curva type : IAC Short Inverse CT Sec ; 5A
Time Dial setting : 16
V inj : 83%

Inject Current Fault Expected Phase


(A) (%) Trip Time (ms) Trip Time (ms)
5.4 120% 3.8397 2.478
6.75 150% 2.3516 1.681
9 200% 1.5451 1.293
11.25 250% 1.2514 1.106
13.5 300% 1.1068 1.007
15.75 350% 1.0223 0.947
18 400% 0.9673 0.905
22.5 500% 0.9001 0.859
27 600% 0.8607 0.821
31.5 700% 0.8348 0.814
36 800% 0.8164 0.778

#REF!

Tested By #REF! Approved By


Guna Elektro #REF! #REF!

#REF! #REF! #REF!

711556050.xlsx/PTOC VREST Page 5 of 10


Ground Time Overcurrent Functions (ANSI Devices 51G)

Phase Trip Time (ms)

10
Trip time (second)

0.1
100% 1000%
I fault

711556050.xlsx/PTOC VREST Page 6 of 10


Customer : PT BDSN

PANEL : 13 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000833

TEST EQUIPMENT : Megger SMRT46

2. PHASE OVERCURRENT (51P)_SIDE 275kV

51 Pickup setting 0.4 pu CT Pri 750 A


51 Time Delay 0.5 s CT Sec 1A

Pickup Value 0.400 A


Dropout 0.388 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 0.5 0.526 0.052
3 0.5 0.511 0.022

TEST FUNCTION : Injection Sekunder ABC signal Source Side 275kV


TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN STOP GEN
√ √ √ √ √ √ √

START CBF

3. PHASE OVERCURRENT (51P)_SIDE 275kV_MT OVERLOAD

51 Pickup setting 0.31 pu CT Pri 750 A


51 Time Delay 9s CT Sec 1A

Pickup Value 0.310 A


Dropout 0.300 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 9 9.017 0.0019
3 9 9.014 0.0016

TEST FUNCTION : Injection Sekunder ABC signal Source Side 275kV


TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN STOP GEN
√ √ √ √ √ √ √

START CBF

711556050.xlsx/51P Page 7 of 10
Customer : PT BDSN

PANEL : 13 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000833

TEST EQUIPMENT : Megger SMRT46

4. PHASE OVERCURRENT (51P)_SIDE GEN

51 Pickup setting : 1.1 pu CT Pri 5000 A


51 Time Delay : 1s CT Sec 1A

Pickup Value 1.103 A


Dropout 1.069 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 1 1.036 0.0360
3 1 1.019 0.0190

TEST FUNCTION : Injection Sekunder ABC signal Source Side Gen


TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN STOP GEN
√ √ √ √ √ √ √

START CBF

5.. GROUND OVERCURRENT (51G)_SIDE 275kV

51 Pickup setting : 1.5 pu CT Pri 150 A


51 Time Delay : 0.75 s CT Sec 1A

Pickup Value 1.506 A


Dropout 1.472 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 0.75 0.795 0.060
3 0.75 0.798 0.064

TEST FUNCTION :
TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN STOP GEN
√ √ √ √ √ √ √

START CBF

711556050.xlsx/51P (2) Page 8 of 10


Customer : PT BDSN

PANEL : 13 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000833

TEST EQUIPMENTMegger
: SMRT46

6. GROUND OVERCURRENT (51G)_SIDE 275kV

51 Pickup setting 1 pu CT Pri 150 A


51 Time Delay 2s CT Sec 1A

Pickup Value 1.006 A


Dropout 0.986 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 2 2.028 0.014
3 2 2.04 0.020

TEST FUNCTION: Injection Sekunder AN signal Source Side 275kV


TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN STOP GEN
√ √ √ √ √ √ √

START CBF

7. OVER FLUXING (24)_STAGE_1

24 Pickup setting 1.21 pu VT Pri 275 kV


24 Time Delay 5s VT Sec 110 V
Source Neutral
Pickup Value 133.18 Vp-p

Inject Voltage
Target (s) Actual (s) Error (%)
(Vp-p)
135 5 5.15 0.03
140 5 5.16 0.03

TEST FUNCTION: Injection Sekunder AN signal Source Side Neutral


TRIP TARGET : no Action to Matrik trip

711556050.xlsx/51G Page 9 of 10
Customer : PT BDSN

PANEL : 13 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000833

TEST EQUIPMENT :Megger SMRT46

8. OVER FLUXING (24)_STAGE_2

24 Pickup setting 1.32 pu VT Pri 275 kV


24 Time Delay 3s VT Sec 110 V

Pickup Value 145.25 Vpp

Inject Voltage
Target (s) Actual (s) Error (%)
(Vp-p)
147 3 3.194 0.06
150 3 3.182 0.06

TEST FUNCTION :
TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN STOP GEN
√ √ √ √ √ √ √

START CBF

9. PHASE UV

27X Pickup setting 0.8 pu VT Pri 13.8 kV


27X Time Delay 1s VT Sec 110 V
SOURCE : 13,8 kV
Pickup Value 50.89 Vp-N

Inject Voltage
Target (s) Actual (s) Error (%)
(Vp-N)
50 1 1.023 0.023
40 1 1.023 0.023

TEST FUNCTION : Injection volt ABC source 13,8kV


TRIP TARGET : Alarm, Block UV_OCR

711556050.xlsx/24 Page 10 of 10