Gas-insulated switching and
isolating apparatus
Index
2 1. Description
7 2. Operating mechanisms
9 3. Accessories
14 4. Type available
20 5. Overall dimensions
22 6. Fuses
2 4 7. Electrical diagrams
34 8. Switchgear applications
1
1. Description
2 4 2 2 2
1 3 5 6
1 Moving contact
operating shaft
2 Top insulator
3 Upper fixed contact
4 Gas exhaust valve
5 Stainless steel
housing
6 Operating mechanism
7 Bottom insulator
8 Moving contact
9 Earth contact
7 9 8 7 7 7
2
Closed Open Earthed
3
1. Description
• IEC 60694 Test parameters for making capacity, breaking capacity and
Switch-disconnector making capacity under short circuit - rms (IEC 60265-1)
combined with fuses • CEI EN 60694
Electrical life
Common requirements for high voltage switching
and control apparatus. Transfer current secondo IEC 62271-105 A
• IEC 60282.1 Maximum overtemperature test under normal load °C
• CEI EN 60282.1 Mechanical life
Fuses with voltage higher than 1000 V. Atmospheric impulse withstand voltage
Part 1: current-limiting fuses.
Phase-Phase towards earth kVp
4
Switch-disconnector Isolator Earthing switch
24 - - 24 - - -
400-630 - - 400-630 - - -
50/60 - - 50/60 - - -
12.5-16- 20-25 12.5-16- 20-25 1 12.5-16- 20-25 (2) 12.5-16- 20-25 ( 2) 1 12.5-16-20-25
400-630 - - - - - -
4...16 - - - - - -
25 - - - - - -
50 - - - - - -
400 - - - - - -
T1-T1M-T2-T2M T1-T1M-T2-T2M T2-T2M T3-V1 T3-V1 - T4
Test Duties
- - - - - -
1-2-3-4-5-6-7
E3 E1 E1 - E1 E1 E1
N.O. N.O. Ask ABB N.O. N.O. N.O. N.O.
IEC 60694 - - IEC 60694 - - -
M1 M1 M1
(BIL 1.2/50 µs) (BIL 1.2/50 µs) (BIL 1,2/50 µs)
125 125 125
50 50 50
60 60 60
5
1. Description
6
2. Operating mechanism
7
2. Operating mechanism
During the closing operation, a separate spring is charged T3-V1 Operating mechanisms with dependent operation
automatically which stores the energy for opening. These allow manual closing of the isolator and earthing switch
Switch-disconnector opening can be carried out by means of: with operation speed dependent on the operator.
– the operating lever Closing and opening are obtained by working on the
– a shunt opening release (applied onto the operating operating lever. The lever can only be removed after
mechanism itself) on request completion of the operation.
– the release system, activated by the striker fuse in the case The T3 type operating mechanism is used in the SHS2/I,
of even a single fuse blowing (only for SHS2/T2F SHS2/I/N, SHS2/IF and SHS2/IB type isolators.
- SHS2/T2F/N - SHS2/T2MF - SHS2/T2MF/N). The type V1 operating mechanism is used in the SHS2/A type
It also carries out rapid manual closing of the earthing switch isolator.
with operating speed independent of the operator.
It is used in the SHS2/T2, SHS2/T2/N, SHS2/T2F, SHS2/
T2F/N type switch-disconnectors and in the corresponding T4 Operating mechanisms with independent operation
SHS2/T2M - SHS2 T2M/N SHS2/T2MF - SHS2/T2MF/N
These allow manual closing of the earthing switch with
motorized versions.
operating speed independent of the operator.
With the T2M operating mechanism, the closing operation can
The opening and closing operations are carried out locally
be carried out from remote or by means of the operating lever.
manually by means of an operating lever provided. The lever
can only be removed after completion of the operation.
The type T4 operating mechanism is used in the SHS2/ES
type earthing switch.
1
2 Key locks on isolator and earthing switch
operation (on request)
2
3 Key locks on earthing switch operation
(on request)
8
3. Accessories
Optional accessories
Switch-disconnector-isolator
Auxiliary contacts
mechanism of isolator
Fuse adapters
fuse blown
Retrofit Kit
Door lock
key locks
lamps
lamps
SHS2/T1 C C C C C C C
– – – – C
T1 SHS2/T1/N C C – – C C C C C – – C
SHS2/T1M C C – – C C C C C – – C
SHS2/T1M/N C C – – C C C C C – – C
SHS2/T2F C C C ABB C C C C C C
SHS2/T2F/N C C C ABB C C C C C C
T2
SHS2/T2 C C C – C C C C C – – C
SHS2/T2/N C C C – C C C C C – – C
SHS2/IF C C – – C C C C C C
SHS2/I C C – – C C C C C – – C
T1-T3-V1 SHS2/I/N C C – – C C C C C – – C
SHS2/IB C C – – C C C C C C – C
SHS2/A C C – – C C C C C C – C
SHS2/ES C C – – C C C C C – –
SHS2/T2M C C C – C C C C C – – C
T4 SHS2/T2M/N C C C – C C C C C – – C
SHS2/T2MF C C C ABB C C C C C C
SHS2/T2MF/N C C C ABB C C C C C C
C Assembly by the customer.
ABB Assembly by ABB.
Accessory always supplied.
– Not available.
9
3. Accessories
These allow the apparatus to be locked in the closed or open These signal the position of the apparatus state.
position. These signal the position of the apparatus state.
It is possible to combine a maximum of four key locks for T1, It is possible to combine a maximum of two closing or
T2 and T3 operating mechanisms, and a maximum of two key opening contacts for each position (closed/open/earthed).
locks for T4 operating mechanisms.
If key locks are not requested, a pre-assembled extension
is supplied which allows the use of padlocks to lock the
operations.
SHS2 - T1, T2, T3 and V1 operating mechanism (*): 3 Shunt opening release (only T2-T2M operating mechanism)
Line-side isolator operation
1 free key IMS open
1 free key IMS closed
1 free key IMS open + 1 free key IMS closed
2 free keys IMS open
2 free keys IMS closed
Earthing switch operation
1 free key ST open
1 free key ST closed
1 free key ST open + free key ST closed
2 free keys ST open
2 free keys ST closed
SHS2/ES - (T4 operating mechanism)
1 free key earthing switch open
1 free key earthing switch open + 1 free key earthing switch closed
1 free key earthing switch closed
This is an electromechanical device which, following
2 free keys earthing switches closed
energisation of an electromagnet, activates the release lever
2 free keys earthing switches open
of the operating mechanism making the switch-disconnector
IMS Switch-disconnector. open.
ST Earthing switch.
(*) A key interlock, with the key free with the line-side isolator closed, is always sup- Power supply voltages:
plied as a compulsory application. – 24-48-110-220 V DC
– 24-48-110-220 V AC. 50-60 Hz.
10
4 Voltage indicator lamps 6 Door lock
These can be supplied with one or two sets of three lamps This is a mechanical device which does not allow the unit door to
integrated in the operating mechanism casing. be opened with the earthing switch open.
The device is prepared for verification of concordance of the
phase with fibre optics.
It can be combined with the crosspiece with capacitive
insulators.
This can be supplied to complete the switchgear in the This is fitted with:
versions with pole insulators or, alternatively, with pole – transmission;
capacitive insulators. – interlock;
Should voltage indicator lamps be requested on the cable – auxiliary contacts: two closing or opening contacts.
side, it is necessary to install a crosspiece with capacitive The spaced earthing switch is standard for: SHS2/T2F, SHS2/
insulators. T2MF, SHS2/T2MF/N, SHS2/IF, SHS2/ES.
The crosspiece is always present in the versions fitted with In the SHS2/IB isolator, the earthing switch with making
fuses. capacity (62.5 kAp) is available.
11
3. Accessories
When a fuse blows, special kinematics activate a signalling The kit includes three field diffusers to be applied to the end of the
contact. busbars in correspondence with the switchgear closure sheet.
The kit is optional and assembly is by the customer.
The kit must be used, for insulation reasons, in 375 mm units
(should the switchgear manufacturer not provide alternative
solutions).
This solution is already used in ABB UniMix switchgear and
application of the kit requires a busbar cross-section similar to that
of the UniMix switchgear.
DIN
e
The kit includes all the accessories needed to adapt and mount
three fuses according to DIN Standards with dimension “e” less
than 442 mm.
Different adapters are available for 292 mm and 192 mm fuses.
12
11 Retrofit Kit 13 Two-level pressure switch
The kit includes the lateral supports to be assembled on the The device allows the internal pressure of the SHS2 switch-
stainless steel structure to allow fixing in panels built for SHS2 disconnector to be monitored.
switch-disconnectors and isolators of the first series. There are two contacts in the device which allow the
With regard to the auxiliary electrical connections, it is operating pressure (contact 1) and the minimum pressure
necessary to carry out the panel retrofit according to the below which operation is not guaranteed (contact 2).
electric circuit diagrams, available on request.
13
4. Types Available
Switch-disconnectors
Fig. 1 - UniMix P3
14
Isolators
15
4. Types Available
SHS2/IF SHS2/IB
HD4/UniMix-F
VD4/UniMix-F
SHS2/A
Fig. 4 - UniMix M Fig. 5 - UniMix P1F Fig. 6 - UniMix P1A Fig. 7 - UniMix A
16
Icw [kA] Width Unit
Type Dimensions U [kV] In [A]
Unit UniMix UniMix
SHS2/T1 24.04.12 1vcd003305 24 400 12,5 500 P3
SHS2/T1 24.04.16 1vcd003305 24 400 16 500 P3
SHS2/T1 24.06.16 1vcd003305 24 630 16 500 P3
SHS2/T1 24.06.20 1vcd003305 24 630 20 500 P3
SHS2/T1 24.06.25 1vcd003305 24 630 25 500 P3
SHS2/T1/N 24.04.12 1vcd003307 24 400 12,5 375 P3
SHS2/T1/N 24.04.16 1vcd003307 24 400 16 375 P3
SHS2/T1/N 24.06.16 1vcd003307 24 630 16 375 P3
SHS2/T1/N 24.06.20 1vcd003307 24 630 20 375 P3
SHS2/T1/N 24.06.25 1vcd003307 24 630 25 375 P3
SHS2/T2 24.04.12 1vcd003309 24 400 12,5 500 P3
SHS2/T2 24.04.16 1vcd003309 24 400 16 500 P3
SHS2/T2 24.06.16 1vcd003309 24 630 16 500 P3
SHS2/T2 24.06.20 1vcd003309 24 630 20 500 P3
SHS2/T2 24.06.25 1vcd003309 24 630 25 500 P3
SHS2/T2/N 24.04.12 1vcd003311 24 400 12,5 375 P3
SHS2/T2/N 24.04.16 1vcd003311 24 400 16 375 P3
SHS2/T2/N 24.06.16 1vcd003311 24 630 16 375 P3
SHS2/T2/N 24.06.20 1vcd003311 24 630 20 375 P3
SHS2/T2/N 24.06.25 1vcd003311 24 630 25 375 P3
SHS2/T2F 24.04.12 1vcd003313 24 400 12,5 500 P2
SHS2/T2F 24.04.16 1vcd003313 24 400 16 500 P2
SHS2/T2F 24.06.16 1vcd003313 24 630 16 500 P2
SHS2/T2F 24.06.20 1vcd003313 24 630 20 500 P2
SHS2/T2F 24.06.25 1vcd003313 24 630 25 500 P2
SHS2/T2F/N 24.04.12 1vcd003315 24 400 12,5 375 P2
SHS2/T2F/N 24.04.16 1vcd003315 24 400 16 375 P2
SHS2/T2F/N 24.06.16 1vcd003315 24 630 16 375 P2
SHS2/T2F/N 24.06.20 1vcd003315 24 630 20 375 P2
SHS2/T2F/N 24.06.25 1vcd003315 24 630 25 375 P2
SHS2/T1M 24.04.12 1vcd003306 24 400 12,5 500 P3
SHS2/T1M 24.04.16 1vcd003306 24 400 16 500 P3
SHS2/T1M 24.06.16 1vcd003306 24 630 16 500 P3
SHS2/T1M 24.06.20 1vcd003306 24 630 20 500 P3
SHS2/T1M 24.06.25 1vcd003306 24 630 25 500 P3
SHS2/T1M/N 24.04.12 1vcd003308 24 400 12,5 375 P3
SHS2/T1M/N 24.04.16 1vcd003308 24 630 16 375 P3
SHS2/T1M/N 24.06.16 1vcd003308 24 630 16 375 P3
SHS2/T1M/N 24.06.20 1vcd003308 24 630 20 375 P3
SHS2/T1M/N 24.06.25 1vcd003308 24 630 25 375 P3
SHS2/I 24.04.12 1vcd003318 24 400 12,5 500 ASR
SHS2/I 24.04.16 1vcd003318 24 400 16 500 ASR
SHS2/I 24.06.16 1vcd003318 24 630 16 500 ASR
SHS2/I 24.06.20 1vcd003318 24 630 20 500 ASR
SHS2/I 24.06.25 1vcd003318 24 630 25 500 ASR
SHS2/I/N 24.04.12 1vcd003319 24 400 12,5 500 ASR
SHS2/I/N 24.04.16 1vcd003319 24 400 16 500 ASR
SHS2/I/N 24.06.16 1vcd003319 24 630 16 500 ASR
SHS2/I/N 24.06.20 1vcd003319 24 630 20 500 ASR
SHS2/I/N 24.06.25 1vcd003319 24 630 25 500 ASR
17
4. Types Available
18
Switch-disconnectors approved by Enel spaced earthing switch, both with operation independent of
Can only be ordered together with a complete UniMix unit the operator.
in the fixed configuration and with the accessories indicated It is normally used to make 1UT type units according to
below. DY803/3 and DY 803/316.
• Mix-L: three-position switch-disconnector with manual • Mix-LM: three-position switch-disconnector with motor
operating mechanism on exceeding dead centre, with operator (24 V DC auxiliary voltage) on exceeding dead
operation independent of the operator . centre.
It is normally used to make 1L type units according to It is normally used to make 1LE type units according to
DY803/1 and DY 803/116. DY803/4 and DY 803/416.
IMS-ST1 IMS-ST1
IMS-ST
ST2 ST2
19
5. Overall dimensions
The SHS2 switch-disconnectors and isolators have been The overall dimensions of the different apparatus are available on
designed with a 230 mm pole centre distance. request. For detailed information and other types of apparatus,
As an example, the figure shows the dimensions of the SHS2/T1 please contact us.
type of switch-disconnector.
20
SHS2 for units 500 mm wide
21
6. Fuses
Three fuses for transformer protection can be connected in Transformer protection and selection of fuses
series with the SHS2 switch-disconnector, with dimensional When the isolators are used to control and protect
characteristics complying with DIN 43625 Standards. transformers, they are fitted with a particular type of current-
The fuse striker must have the force and run shown in the limiting fuses which guarantee selectivity with other protection
diagram. devices and can take the high transformer connection
Selection of the fuse according to the voltage and power of currents without deteriorating.
the transformer must be made in conformity with the data In this case, protection against overcurrents on the medium
indicated in the table. voltage side of the transformer is not indispensable since
this task is carried out by the protection provided on the low
voltage side.
The protection on the medium voltage side can be entrusted
F (N) just to the fuse, which must be selected taking into account
the no-load connection current, which can take on values
60 equal to or higher than 10 times the rated current according
to the power of the transformer and to the type of laminations
50
used (hot laminated or with orientated crystals).
40 There is the maximum connection current when circuit-
breaker closing takes place corresponding to the voltage
30 passing through zero.
20 A further result to be guaranteed is protection against faults in
the low voltage winding and in the stretch of the connection
10 from this to the circuit-breaker positioned on the secondary,
avoiding the use of fuses with rated current which is too high,
in order to ensure tripping within a short time even under
10 20 30 40 S (mm)
F = Striker force.
these fault conditions.
S = Striker run.
22
A rapid check of the short-circuit current at the secondary The usage table given below takes both the required
terminals of the transformer and on the supply side of the conditions into account, i.e. sufficiently high rated current to
circuit-breaker on the secondary - if placed at a significant avoid untimely fuse blowing during the no-load connection
distance, allows the trip time to be verified on the fuse stage and, in any case, of a value which guarantees protection
blowing curve. of the machine against faults on the low voltage side.
23
7. Electric circuit diagram
Continues on page 25
24
SHS2/T1 electric circuit diagram
Control circuit of the switch-disconnector (48-110 V DC – 110 V AC)
Continues on page 26
25
7. Electric circuit diagram
26
SHS2/T2 electric circuit diagram
Circuit of the closing motor
27
7. Electric circuit diagram
28
Circuit for indication of voltage present busbars and line
29
7. Electric circuit diagram
Auxiliary contacts of the isolator (see note C), for the SHS2/T1, SHS2/T2 and SHS2/T3 type isolators.
30
Circuit for signalling voltage present on the earth for the
SHS2/T1 and SHS2/T3 isolators
Circuit for signalling fuse blown for the SHS2/T1 and SHS2/
T2 isolators
31
7. Electric circuit diagram
Note: To take development of the product into account it is, in BI421...422 = L ine earth-open position contacts
any case, always useful to refer to the electric circuit diagram BI431...432 = E arthing switch-QE position contacts
provided with each circuit-breaker. -BK = C ontact activated by the key lock
-BU1...3 = C apacitive dividers located on phases L1, L2, L3 of
the line
State of operation shown
-BU1...6 = C apacitive dividers located on phases L1, L2, L3
The diagram is shown under the following conditions:
-BU4...6 = C apacitive dividers located on phases L1, L2, L3 of
– switch-disconnector open the busbars
-C1/L1...L3 = C apacitive dividers located on phases L1, L2, L3 of
the line
– earthing switch open
-C2/L1...L3 = C apacitive dividers located on phases L1, L2, L3 of
the busbars
– circuits de-energised.
-F1…-F3 = M edium voltage fuses
-FF1…3 = M edium voltage fuses
-KC = A uxiliary relay for closing the switch-disconnector
-KO = A uxiliary relay for opening the switch-disconnector
Caption
-KD = A uxiliary relay for with two contacts delayed at
= Number of diagram figure
attraction and two instantaneous contacts
* = See the note indicated by the letter
-MI4 = M otor for operating the switch-disconnector
A1 = Switch-disconnector operating mechanism
-MM = M otor for operating the switch-disconnector
applications
-MO = S hunt opening release (see note C)
A4 = Switchgear applications (indicative apparatus and
connections for operating mechanism and signals) -MS = M otor for operating the switch-disconnector
AK = Switch-disconnector auxiliary circuit diagram -PGN = L amp for signalling switch-disconnector open
-B80/1…2 = Earthing switch position contact -PRD = L amp for signalling switch-disconnector closed
-B80/L = Position contact open during manual operation of -PU1...2 = Voltage indicator located on phases L1, L2, L3 of the
earthing switch -Q80 line/busbars
-B80-90/1…2 = Position contact open during manual operation of -PUD1 = Voltage indicator located on the line
earthing switch -Q80 and during manual operation of -PUD2 = Voltage indicator located on the busbars
the switch-disconnector -Q80 = E arthing switch
-B90/1…3 = Switch-disconnector position contacts -Q90 = S witch-disconnector
-B90/C = Position contact open with switch-disconnector -QE = E arthing switch
closed
-QI4 = S witch-disconnector
-B90/E = Contact activated by the key lock
-RR1…2 = S uppressors of transients
-B90/L = Position contact open during manual operation of
-S75F = C ontact signalling medium voltage fuse blown
switch-disconnector Q90
-SC = P ushbutton for local switch-disconnector closing
-B90/O = Position contact open with the switch-disconnector
open -SO = P ushbutton for local switch-disconnector opening
-BE7 = Position contact open during manual operation of the -SS = L ocal/remote selector
earthing switch -TR = Converter
-BF = Contact signalling medium voltage fuse blown -TR1…2 = R ectifier
-BI1...4 = Position contact open with switch-disconnector -X = Interface connector with the feeder (outside the unit)
closed
-X1…-X3 = Terminal boxes of the operating mechanism
-BI2...5 = Position contact open with switch-disconnector open applications
-BI7 = Position contact open during manual operation of the -XB1 = Terminal boxes for the switch-disconnector auxiliary
switch-disconnector circuits
BI51...53 = Position contacts open with switch-disconnector -XB2 = Terminal boxes for the circuits inside the switch-
BI411...412 = Position contacts of the switch-disconnector disconnector
BI413 = Earthing switch position contacts XB91...94 = Terminal boxes of the operating mechanism
applications
-XB93 = Terminal boxes of operating mechanism application
32
Graphic symbols for electrical diagrams (IEC 60617 and CEI 3-14 ... 3-26 Standards)
Rotary handle operating Socket and plug Closing position contact Control coil of a
mechanism (female and male) (limit switch) relay with delay on
attraction
M M
33
8. Switchgear applications
PR521and REF601
switchgear protection devices
These are provided on board
the HD4/R and VD4/R circuit-
breakers combined with current
sensors of dedicated type. The Circuit-breakers
REF601 CEI 0-16 version is
Both the HD4/R series SF6 gas
also available, specially made to
insulated medium voltage circuit-
comply with CEI 0-16 standards.
breaker and the VD4/R vacuum circuit-
For further information, please
breaker, with right lateral operating
contact us.
Fuses
Fuses according to DIN Standards
are available to be combined with
the SHS2 apparatus.
34
REF542plus micro- Voltage
processor-based unit transformers
The REF542plus unit carries The voltage
out integration of all the transformers
secondary functions relative are of the resin
to a switchgear unit. insulated type.
They comply with
the IEC 60044-2
Standards.
PR512 switchgear protection devices Their dimensions are normally according
The PR512 are devices of the self-supplied type and ensure complete protection of the installation to DIN 42600 Standards.
without an auxiliary power supply.
Current
transformers
The current
transformers
are of the resin
insulated type.
They comply with
the IEC 60044-1
Standards.
Their dimensions are normally according
to DIN 42600 Standards.
Toroidal cable
type transformers
are also available.
mechanism and
230 mm pole centre
distance, are available
to make units with a
circuit-breaker.
Combined voltage-
current sensors
A range of sensors
is available which
optimally covers the
characteristics of
new generations
of instruments and
Example of
of the REF542plus
unit with
unit in particular.
circuit-breaker.
The current sensors conform with the
IEC 60044-8 (CDV) Standard, the voltage
sensors with the IEC 60044-7 Standard.
Their dimensions are according to
DIN 42600 Standards.
35