Medium Voltage Products

SHS2
Gas-insulated switching and
isolating apparatus
Index

2 1. Description

7 2. Operating mechanisms

9 3. Accessories

14 4. Type available

20 5. Overall dimensions

22 6. Fuses

2 4 7. Electrical diagrams

34 8. Switchgear applications

1
1. Description

General Technical characteristics


The SHS2 switching and isolating apparatus consist of gas- The SHS2 switch-disconnectors and isolators are made up
insulated switch-disconnectors and isolators, suitable for use of a stainless steel cylindrical housing, a set of three top
in medium voltage metal-enclosed switchgear. insulators and a set of three bottom insulators made of epoxy
They are used in secondary distribution substations for resin, and a front operating mechanism.
supplying lines, power transformers and ring networks. The blade contacts for isolation, breaking, closing and
earthing are arranged inside the cylinder in SF6 gas at a
pressure of 125 kPa absolute.
The unit is the sealed for life type complying with the IEC
60694 Standards.
It is therefore free from any problems of gas tightness.
A gas exhaust valve is located in the rear part of the cylinder
for any over-pressure.
The contacts can take up three positions: CLOSED - OPEN -
EARTHED.
The position of the contacts can be verified from the front of
the operating mechanism by means of a reliable indication, in
compliance with IEC 62265-1 and CEI 17-4 and with the IEC
62271-102 and CEI EN 60129 Standards.
The three top insulators act as a support for the fixed
contacts and allow fixing of the main busbars.
The three bottom insulators act as a support for the moving
contacts and allow connection of the cables or of the
busbars.

2 4 2 2 2

1 3 5 6

1 Moving contact
operating shaft
2 Top insulator
3 Upper fixed contact
4 Gas exhaust valve
5 Stainless steel
housing
6 Operating mechanism
7 Bottom insulator
8 Moving contact
9 Earth contact

7 9 8 7 7 7

2
Closed Open Earthed

The stainless steel housing provides a metal earthed


segregation between the busbar compartment and the feeder
compartment of the unit the apparatus is installed in.
This characteristic ensures maximum personnel safety
during any intervention in the feeder compartment, such as
replacement of one or more fuses or cable maintenance, even
with the main busbars energised.

Furthermore, the metal segregation provided by the housing


considerably reduces the possibility of a short-circuit between
the phases and between the upper and lower contacts of the
same phase due to leakage currents.

3
1. Description

Compliance with Standards Electrical characteristics


• IEC 60694
• CEI EN 60694
Common requirements for high voltage switching
and control apparatus.
Isolator
• IEC 62271-102
• CEI 17.4
Isolators and earthing switches with alternating Rated voltage kV
current and voltage higher than 1000 V.
Rated Normal Current (40 °C) A
• IEC 60694
Frequency Hz
• CEI EN 60694
Rated making capacity on short-circuit
Common requirements for high voltage switching
and control apparatus. Without external earthing switch kAp
• IEC 60265-1
With external earthing switch ( )
1
kAp
Switch-disconnector • CEI 17-9/1
Rated short time withstand current - 1s (1) kA
Control circuit-breakers and switch-disconnectors
Rated breaking capacity
for high voltage.
Part 1: Control circuit-breakers and switch- Mainly resistive load service A
disconnectors for rated voltages higher than 1 kV
and lower than 52 kV. No-load transformer service A

• IEC 62271-105 No-load line service A


• CEI EN 60420 No-load cable service A
Switch-disconnectors combined with high voltage Ring circuit service A
fuses for alternating current.
The fuses must comply with DIN Standards. Operating Mechanism

• IEC 60694 Test parameters for making capacity, breaking capacity and
Switch-disconnector making capacity under short circuit - rms (IEC 60265-1)
combined with fuses • CEI EN 60694
Electrical life
Common requirements for high voltage switching
and control apparatus. Transfer current secondo IEC 62271-105 A
• IEC 60282.1 Maximum overtemperature test under normal load °C
• CEI EN 60282.1 Mechanical life
Fuses with voltage higher than 1000 V. Atmospheric impulse withstand voltage
Part 1: current-limiting fuses.
Phase-Phase towards earth kVp

Between open contacts kVp

Withstand voltage at industrial frequency

Phase-Phase towards earth kVrms/1 min


Degrees of protection Between open contacts kVrms/1 min
Stainless steel enclosure IP65
( 1) For different values contact ABB.
Operating mechanism IP3X ( 2) Up to 16 kA for V1 operating mechanism.

4
Switch-disconnector Isolator Earthing switch

IEC 60265-1 IEC 62271-102 IEC 62271-102


Earthing Switch Earthing Switch
Feeder Feeder (SHS2 ES)
Unit without fuses Unit with fuses Unit without fuses Unit with fuses

24 - - 24 - - -

400-630 - - 400-630 - - -

50/60 - - 50/60 - - -

31.5-40-50-62.5 31.5-40-50-62.5 N.O. - - N.O. N.O.

- - 2.5 - - 2.5 kA 62.5 kA

12.5-16- 20-25 12.5-16- 20-25 1 12.5-16- 20-25 (2) 12.5-16- 20-25 ( 2) 1 12.5-16-20-25

400-630 - - - - - -
4...16 - - - - - -

25 - - - - - -

50 - - - - - -

400 - - - - - -
T1-T1M-T2-T2M T1-T1M-T2-T2M T2-T2M T3-V1 T3-V1 - T4
Test Duties
- - - - - -
1-2-3-4-5-6-7
E3 E1 E1 - E1 E1 E1
N.O. N.O. Ask ABB N.O. N.O. N.O. N.O.
IEC 60694 - - IEC 60694 - - -

M1 M1 M1
(BIL 1.2/50 µs) (BIL 1.2/50 µs) (BIL 1,2/50 µs)
125 125 125

145 145 145

50 50 50
60 60 60

5
1. Description

Quality System Health and Safety Management System


Complies with ISO 9001 Standards, certified by an Complies with ISO 18001 Standards, certified by an
independent organisation. independent organisation.

Environmental Management System Test Laboratory


Complies with ISO 14001 Standards, certified by an Complies with UNI CEI EN ISO/IEC 17025 Standards,
independent organisation. accredited by an independent organisation.

6
2. Operating mechanism

General T1-T1M Operating mechanism with independent


The switch-disconnectors use T1-T1M and T2-T2M type operation on exceeding dead centre
operating mechanisms with separate operating seats for the This allows rapid manual or motorized closing and opening of
isolation and earthing operations. the switch-disconnector with operating speed independent of
The isolators use T3 and V1 type operating mechanisms the operator, obtained by using a single spring.
with separate operating seats for the isolation and earthing Closing or opening takes place by charging the above-
operations and T4 with a single operating seat. mentioned spring (either manually of by means of a motor)
With the T1-T2-T3-T4 operating mechanisms, the opening until the dead centre is exceeded.
and closing operations are carried out manually locally by It also carries out rapid manual closing of the earthing switch
means of the operating lever provided. with operating speed independent of the operator.
For the T2 operating mechanism it is also possible to carry It is used in the SHS2/T1, SHS2/T1/N, SHS2/T1M and SHS2/
out the opening operation remotely by means of a special T1M/N type of switch-disconnectors.
shunt
opening release. T2-T2M Operating mechanism with independent stored
With the T1M and T2M motor operators, the closing and energy operation
opening operations are carried out remotely. However, in case Allows rapid manual closing of the switch-disconnector with
of emergency, they can also be carried out manually locally operation independent of the operator, obtained by means of
using the operating lever provided, or electrically by means of a charged spring up to exceeding dead centre.
the special pushbuttons.
The normal power supply voltages for the T1M and T2M
motor operators are:
– 24 (*) - 48 - 110-220 V DC;
– 48 - 110 - 220 V AC 50 - 60 Hz.

(*) Only T1M

1 Switch-disconnector operating seat

4 2 Earthing switch operating seat


3 Interlocking lever between switch-disconnector and earthing
switch
4 Mechanical position indicators of the mimic diagram
2
5 Voltage indicator lamps (on request)
6 Key locks on switch-disconnector operation (on request)
7 7 Key locks on earthing switch operation (on request)

SHS2/T1M switch-disconnector operating mechanism.

7
2. Operating mechanism

During the closing operation, a separate spring is charged T3-V1 Operating mechanisms with dependent operation
automatically which stores the energy for opening. These allow manual closing of the isolator and earthing switch
Switch-disconnector opening can be carried out by means of: with operation speed dependent on the operator.
– the operating lever Closing and opening are obtained by working on the
– a shunt opening release (applied onto the operating operating lever. The lever can only be removed after
mechanism itself) on request completion of the operation.
– the release system, activated by the striker fuse in the case The T3 type operating mechanism is used in the SHS2/I,
of even a single fuse blowing (only for SHS2/T2F SHS2/I/N, SHS2/IF and SHS2/IB type isolators.
- SHS2/T2F/N - SHS2/T2MF - SHS2/T2MF/N). The type V1 operating mechanism is used in the SHS2/A type
It also carries out rapid manual closing of the earthing switch isolator.
with operating speed independent of the operator.
It is used in the SHS2/T2, SHS2/T2/N, SHS2/T2F, SHS2/
T2F/N type switch-disconnectors and in the corresponding T4 Operating mechanisms with independent operation
SHS2/T2M - SHS2 T2M/N SHS2/T2MF - SHS2/T2MF/N
These allow manual closing of the earthing switch with
motorized versions.
operating speed independent of the operator.
With the T2M operating mechanism, the closing operation can
The opening and closing operations are carried out locally
be carried out from remote or by means of the operating lever.
manually by means of an operating lever provided. The lever
can only be removed after completion of the operation.
The type T4 operating mechanism is used in the SHS2/ES
type earthing switch.

1 Isolator and earthing switch operating seat

1
2 Key locks on isolator and earthing switch
operation (on request)

2
3 Key locks on earthing switch operation
(on request)

4 4 Key interlock between isolator and


circuit-breaker
5
5 Mechanical position indicators of the
3 mimic diagram

6 Voltage indicator lamps (on request)

SHS2/IB isolator operating mechanism (type T3).

8
3. Accessories

Optional accessories
Switch-disconnector-isolator

Microswitch for indication of

Cable-side voltage indicator

Insulator crosspiece with or


without capacitive dividers
Bus-side voltage indicator
Earthing switch key locks

Spaced earthing switch


Shunt opening release
Operating Type

Auxiliary contacts
mechanism of isolator

Fuse adapters
fuse blown

Retrofit Kit
Door lock
key locks

lamps

lamps
SHS2/T1 C C C C C C C
– – – – C
T1 SHS2/T1/N C C – – C C C C C – – C
SHS2/T1M C C – – C C C C C – – C
SHS2/T1M/N C C – – C C C C C – – C
SHS2/T2F C C C ABB C C C C C C
SHS2/T2F/N C C C ABB C C C C C C
T2
SHS2/T2 C C C – C C C C C – – C
SHS2/T2/N C C C – C C C C C – – C
SHS2/IF C C – – C C C C C C
SHS2/I C C – – C C C C C – – C
T1-T3-V1 SHS2/I/N C C – – C C C C C – – C
SHS2/IB C C – – C C C C C C – C
SHS2/A C C – – C C C C C C – C
SHS2/ES C C – – C C C C C – –
SHS2/T2M C C C – C C C C C – – C
T4 SHS2/T2M/N C C C – C C C C C – – C
SHS2/T2MF C C C ABB C C C C C C
SHS2/T2MF/N C C C ABB C C C C C C
C Assembly by the customer.
ABB Assembly by ABB.
Accessory always supplied.
– Not available.

9
3. Accessories

1 Key locks 2 Auxiliary contacts

These allow the apparatus to be locked in the closed or open These signal the position of the apparatus state.
position. These signal the position of the apparatus state.
It is possible to combine a maximum of four key locks for T1, It is possible to combine a maximum of two closing or
T2 and T3 operating mechanisms, and a maximum of two key opening contacts for each position (closed/open/earthed).
locks for T4 operating mechanisms.
If key locks are not requested, a pre-assembled extension
is supplied which allows the use of padlocks to lock the
operations.

SHS2 - T1, T2, T3 and V1 operating mechanism (*): 3 Shunt opening release (only T2-T2M operating mechanism)
Line-side isolator operation
1 free key IMS open
1 free key IMS closed
1 free key IMS open + 1 free key IMS closed
2 free keys IMS open
2 free keys IMS closed
Earthing switch operation
1 free key ST open
1 free key ST closed
1 free key ST open + free key ST closed
2 free keys ST open
2 free keys ST closed
SHS2/ES - (T4 operating mechanism)
1 free key earthing switch open
1 free key earthing switch open + 1 free key earthing switch closed
1 free key earthing switch closed
This is an electromechanical device which, following
2 free keys earthing switches closed
energisation of an electromagnet, activates the release lever
2 free keys earthing switches open
of the operating mechanism making the switch-disconnector
IMS Switch-disconnector. open.
ST Earthing switch.
(*) A key interlock, with the key free with the line-side isolator closed, is always sup- Power supply voltages:
plied as a compulsory application. – 24-48-110-220 V DC
– 24-48-110-220 V AC. 50-60 Hz.

10
4 Voltage indicator lamps 6 Door lock

These can be supplied with one or two sets of three lamps This is a mechanical device which does not allow the unit door to
integrated in the operating mechanism casing. be opened with the earthing switch open.
The device is prepared for verification of concordance of the
phase with fibre optics.
It can be combined with the crosspiece with capacitive
insulators.

5 Crosspiece with insulators 7 Earthing switch

This can be supplied to complete the switchgear in the This is fitted with:
versions with pole insulators or, alternatively, with pole – transmission;
capacitive insulators. – interlock;
Should voltage indicator lamps be requested on the cable – auxiliary contacts: two closing or opening contacts.
side, it is necessary to install a crosspiece with capacitive The spaced earthing switch is standard for: SHS2/T2F, SHS2/
insulators. T2MF, SHS2/T2MF/N, SHS2/IF, SHS2/ES.
The crosspiece is always present in the versions fitted with In the SHS2/IB isolator, the earthing switch with making
fuses. capacity (62.5 kAp) is available.

11
3. Accessories

8 Contact signalling fuse blown 10 Field diffusers

When a fuse blows, special kinematics activate a signalling The kit includes three field diffusers to be applied to the end of the
contact. busbars in correspondence with the switchgear closure sheet.
The kit is optional and assembly is by the customer.
The kit must be used, for insulation reasons, in 375 mm units
(should the switchgear manufacturer not provide alternative
solutions).
This solution is already used in ABB UniMix switchgear and
application of the kit requires a busbar cross-section similar to that
of the UniMix switchgear.

9 Adapters for fuses

DIN
e

The kit includes all the accessories needed to adapt and mount
three fuses according to DIN Standards with dimension “e” less
than 442 mm.
Different adapters are available for 292 mm and 192 mm fuses.

12
11 Retrofit Kit 13 Two-level pressure switch

The kit includes the lateral supports to be assembled on the The device allows the internal pressure of the SHS2 switch-
stainless steel structure to allow fixing in panels built for SHS2 disconnector to be monitored.
switch-disconnectors and isolators of the first series. There are two contacts in the device which allow the
With regard to the auxiliary electrical connections, it is operating pressure (contact 1) and the minimum pressure
necessary to carry out the panel retrofit according to the below which operation is not guaranteed (contact 2).
electric circuit diagrams, available on request.

12 Gas topping up valve

The SHS2 switch-disconnector is sealed and has a life of 30


years.
In the case of extraordinary maintenance, topping up of the
SF6 gas is done through the front valve.

13
4. Types Available

Switch-disconnectors

• SHS2/T1, SHS2/T1/N: three-position switch-disconnector


with manual operating mechanism on exceeding dead
centre.
It is normally used for incoming/outgoing units. (Fig. 1).

• SHS2/T2, SHS2/T2/N: three-position switch-disconnector


with manual stored energy operating mechanism. It is
normally used for incoming/outgoing units and can be fitted
with a shunt opening release. (Fig. 1).

• SHS2/T2F, SHS2/T2F/N: three position switch-


disconnector with manual stored energy operating
mechanism, fuse-holder frame, release device for fuse
blown, and earthing switch on the load side of the fuse-
holder frame.
It is normally used to make transformer protection units and
can be fitted with a shunt opening release (Fig. 2).

• SHS2/T1M, SHS2/T1M/N: three-position switch-


disconnector with motor operator.
It is normally used to make incoming/outgoing units (Fig. 1).

• SHS2/T2M, SHS2/T2M/N: switch-disconnector with three


positions with stored energy motor operator.
It is normally used to make incoming/outgoing units and
SHS2/T1
can be fitted with a shunt opening release (Fig. 1).
SHS2/T2
SHS2/T1/N
• SHS2/T2MF, SHS2/T2MF/N: switch-disconnector with SHS2/T2/N
three positions with stored energy motor operator, fuse- SHS2/T1M
SHS2/T1M/N
holder frame, release device for fuse blowing and earthing
SHS2/T2M SHS2/
switch on the load side of the fuse-holder frame. T2M/N
It is normally used to make transformer protection units and
can be fitted with a shunt opening release (Fig. 2).

Fig. 1 - UniMix P3

14
Isolators

• SHS2/I, SHS2/I/N: three-position line-side isolator with


manual operating mechanism with dependent operation.
It is normally used for incoming/outgoing units (Fig. 3).

• SHS2/IF: three-position line-side isolator with fuse-holder


frame and earthing switch on the load side of the fuse-
holder frame, both with manual operating mechanism with
dependent operation.
It is normally used for measurement units (Fig. 4).

• SHS2/IB: three-position line-side isolator and spaced


earthing switch, interlocked, with manual operating
mechanism with dependent operation.
It is normally used for incoming/outgoing units with fixed
circuit-breakers (Fig. 5).
The spaced earthing switch can be assembled to allow the
use of fixed circuit-breakers with current sensors on board
(standard version), or can be assembled for use of current
transformers according to DIN Standards, installed in
switchgear.

• SHS2/A: earthing switch upended with three positions and


spaced earthing switch, interlocked with manual operating
mechanism with dependent operation. It is normally used to
make an incoming unit with fixed circuit-breaker (Fig. 6).
SHS2/T2F SHS2/I
SHS2/T2F/N SHS2/I/N
SHS2/T2F
SHS2/T2MF/N
Earthing switches

• SHS2/ES: earthing switch with manual operating mechanism
with independent operation. It is normally used for incoming/
outgoing units (Fig. 7). It has making capacity up to 62.5 kAp.

Fig. 2 - UniMix P2 Fig. 3 - UniMix ASR

15
4. Types Available

SHS2/IF SHS2/IB

HD4/UniMix-F
VD4/UniMix-F

SHS2/A

Fig. 4 - UniMix M Fig. 5 - UniMix P1F Fig. 6 - UniMix P1A Fig. 7 - UniMix A

16
Icw [kA] Width Unit
Type Dimensions U [kV] In [A]
Unit UniMix UniMix
SHS2/T1 24.04.12 1vcd003305 24 400 12,5 500 P3
SHS2/T1 24.04.16 1vcd003305 24 400 16 500 P3
SHS2/T1 24.06.16 1vcd003305 24 630 16 500 P3
SHS2/T1 24.06.20 1vcd003305 24 630 20 500 P3
SHS2/T1 24.06.25 1vcd003305 24 630 25 500 P3
SHS2/T1/N 24.04.12 1vcd003307 24 400 12,5 375 P3
SHS2/T1/N 24.04.16 1vcd003307 24 400 16 375 P3
SHS2/T1/N 24.06.16 1vcd003307 24 630 16 375 P3
SHS2/T1/N 24.06.20 1vcd003307 24 630 20 375 P3
SHS2/T1/N 24.06.25 1vcd003307 24 630 25 375 P3
SHS2/T2 24.04.12 1vcd003309 24 400 12,5 500 P3
SHS2/T2 24.04.16 1vcd003309 24 400 16 500 P3
SHS2/T2 24.06.16 1vcd003309 24 630 16 500 P3
SHS2/T2 24.06.20 1vcd003309 24 630 20 500 P3
SHS2/T2 24.06.25 1vcd003309 24 630 25 500 P3
SHS2/T2/N 24.04.12 1vcd003311 24 400 12,5 375 P3
SHS2/T2/N 24.04.16 1vcd003311 24 400 16 375 P3
SHS2/T2/N 24.06.16 1vcd003311 24 630 16 375 P3
SHS2/T2/N 24.06.20 1vcd003311 24 630 20 375 P3
SHS2/T2/N 24.06.25 1vcd003311 24 630 25 375 P3
SHS2/T2F 24.04.12 1vcd003313 24 400 12,5 500 P2
SHS2/T2F 24.04.16 1vcd003313 24 400 16 500 P2
SHS2/T2F 24.06.16 1vcd003313 24 630 16 500 P2
SHS2/T2F 24.06.20 1vcd003313 24 630 20 500 P2
SHS2/T2F 24.06.25 1vcd003313 24 630 25 500 P2
SHS2/T2F/N 24.04.12 1vcd003315 24 400 12,5 375 P2
SHS2/T2F/N 24.04.16 1vcd003315 24 400 16 375 P2
SHS2/T2F/N 24.06.16 1vcd003315 24 630 16 375 P2
SHS2/T2F/N 24.06.20 1vcd003315 24 630 20 375 P2
SHS2/T2F/N 24.06.25 1vcd003315 24 630 25 375 P2
SHS2/T1M 24.04.12 1vcd003306 24 400 12,5 500 P3
SHS2/T1M 24.04.16 1vcd003306 24 400 16 500 P3
SHS2/T1M 24.06.16 1vcd003306 24 630 16 500 P3
SHS2/T1M 24.06.20 1vcd003306 24 630 20 500 P3
SHS2/T1M 24.06.25 1vcd003306 24 630 25 500 P3
SHS2/T1M/N 24.04.12 1vcd003308 24 400 12,5 375 P3
SHS2/T1M/N 24.04.16 1vcd003308 24 630 16 375 P3
SHS2/T1M/N 24.06.16 1vcd003308 24 630 16 375 P3
SHS2/T1M/N 24.06.20 1vcd003308 24 630 20 375 P3
SHS2/T1M/N 24.06.25 1vcd003308 24 630 25 375 P3
SHS2/I 24.04.12 1vcd003318 24 400 12,5 500 ASR
SHS2/I 24.04.16 1vcd003318 24 400 16 500 ASR
SHS2/I 24.06.16 1vcd003318 24 630 16 500 ASR
SHS2/I 24.06.20 1vcd003318 24 630 20 500 ASR
SHS2/I 24.06.25 1vcd003318 24 630 25 500 ASR
SHS2/I/N 24.04.12 1vcd003319 24 400 12,5 500 ASR
SHS2/I/N 24.04.16 1vcd003319 24 400 16 500 ASR
SHS2/I/N 24.06.16 1vcd003319 24 630 16 500 ASR
SHS2/I/N 24.06.20 1vcd003319 24 630 20 500 ASR
SHS2/I/N 24.06.25 1vcd003319 24 630 25 500 ASR

17
4. Types Available

Icw [kA] Width Unit


Type Dimensions U [kV] In [A]
Unit UniMix UniMix
SHS2/IF 24.04.12 1vcd003317 24 400 12,5 500 M
SHS2/IF 24.04.16 1vcd003317 24 400 16 500 M
SHS2/IF 24.06.16 1vcd003317 24 630 16 500 M
SHS2/IF 24.06.20 1vcd003317 24 630 20 500 M
SHS2/IF 24.06.25 1vcd003317 24 630 25 500 M
SHS2/T2M 24.04.12 1VCD003310 24 400 12,5 500 P3
SHS2/T2M 24.04.16 1VCD003310 24 400 16 500 P3
SHS2/T2M 24.06.16 1VCD003310 24 630 16 500 P3
SHS2/T2M 24.06.20 1VCD003310 24 630 20 500 P3
SHS2/T2M 24.06.25 1VCD003310 24 630 25 500 P3
SHS2/T2M/N 24.04.12 1VCD003312 24 400 12,5 375 P3
SHS2/T2M/N 24.04.16 1VCD003312 24 400 16 375 P3
SHS2/T2M/N 24.06.16 1VCD003312 24 630 16 375 P3
SHS2/T2M/N 24.06.20 1VCD003312 24 630 20 375 P3
SHS2/T2M/N 24.06.25 1VCD003312 24 630 25 375 P3
SHS2/T2M/F 24.04.12 1VCD003314 24 400 12,5 500 P3
SHS2/T2M/F 24.04.16 1VCD003314 24 400 16 500 P3
SHS2/T2M/F 24.06.16 1VCD003314 24 630 16 500 P3
SHS2/T2M/F 24.06.20 1VCD003314 24 630 20 500 P3
SHS2/T2M/F 24.06.25 1VCD003314 24 630 25 500 P3
SHS2/T2MF/N 24.04.12 1VCD003316 24 400 12,5 375 P2
SHS2/T2MF/N 24.04.16 1VCD003316 24 400 16 375 P2
SHS2/T2MF/N 24.06.16 1VCD003316 24 630 16 375 P2
SHS2/T2MF/N 24.06.20 1VCD003316 24 630 20 375 P2
SHS2/T2MF/N 24.06.25 1VCD003316 24 630 25 375 P2
SHS2/IB 24.04.12 1VCD003320 24 400 12,5 750 P1F
SHS2/IB 24.04.16 1VCD003320 24 400 16 750 P1F
SHS2/IB 24.06.16 1VCD003320 24 630 16 750 P1F
SHS2/IB 24.06.20 1VCD003320 24 630 20 750 P1F
SHS2/IB 24.06.25 1VCD003320 24 630 25 750 P1F
SHS2/IB 24.04.12+kit 2CT 1VCD003320 24 400 12,5 750 P1F
SHS2/IB 24.04.16+kit 2CT 1VCD003320 24 400 16 750 P1F
SHS2/IB 24.06.16+kit 2CT 1VCD003320 24 630 16 750 P1F
SHS2/IB 24.06.20+kit 2CT 1VCD003320 24 630 20 750 P1F
SHS2/IB 24.06.25+kit 2CT 1VCD003320 24 630 25 750 P1F
SHS2/IB 24.04.12+kit 3CT 1VCD003320 24 400 12,5 750 P1F
SHS2/IB 24.04.16+kit 3CT 1VCD003320 24 400 16 750 P1F
SHS2/IB 24.06.16+kit 3CT 1VCD003320 24 630 16 750 P1F
SHS2/IB 24.06.20+kit 3CT 1VCD003320 24 630 20 750 P1F
SHS2/IB 24.06.25+kit 3CT 1VCD003320 24 630 25 750 P1F
SHS2/ES 24.12 1VCD003321 24 — 12,5 500 A
SHS2/ES 24.16 1VCD003321 24 — 16 500 A
SHS2/ES 24.20 1VCD003321 24 — 20 500 A
SHS2/ES 24.25 1VCD003321 <24 — 25 500 A
SHS2/A 24.04.12 1VCD003322 24 400 12,5 750 P1A
SHS2/A 24.04.16 1VCD003322 24 400 16 750 P1A
SHS2/A 24.06.16 1VCD003322 24 630 16 750 P1A

18
Switch-disconnectors approved by Enel spaced earthing switch, both with operation independent of
Can only be ordered together with a complete UniMix unit the operator.
in the fixed configuration and with the accessories indicated It is normally used to make 1UT type units according to
below. DY803/3 and DY 803/316.

• Mix-L: three-position switch-disconnector with manual • Mix-LM: three-position switch-disconnector with motor
operating mechanism on exceeding dead centre, with operator (24 V DC auxiliary voltage) on exceeding dead
operation independent of the operator . centre.
It is normally used to make 1L type units according to It is normally used to make 1LE type units according to
DY803/1 and DY 803/116. DY803/4 and DY 803/416.

• Mix-T: three-position switch-disconnector with manual Type


Standardised
U [kV] In [A] Icw [kA]
unit table
stored energy operating mechanism, with operation
Mix-L 24.04.12 DY 803/1 24 400 12,5
independent of the operator, fuse-holder frame, release
Mix-L 24.04.16 DY 803/116 24 400 16
device for fuse blown, earthing switch on the load side of
Mix-T 24.04.12 DY 803/2 24 400 12,5
the fuse-holder frame.
Mix-T 24.04.16 DY 803/216 24 400 16
It is normally used to make 1T type units according to
Mix-U 24.04.12 DY 803/3 24 400 12,5
DY803/2 and DY 803/216.
Mix-U 24.04.16 DY 803/316 24 400 16
Mix-Lm 24.04.12 DY 803/4 24 400 12,5
• Mix-U: three-position switch-disconnector with manual
Mix-Lm 24.04.16 DY 803/416 24 400 16
operating mechanism on exceeding dead centre and

IMS-ST1 IMS-ST1
IMS-ST

ST2 ST2

MIX - L MIX - T MIX - U MIX - LM

19
5. Overall dimensions

The SHS2 switch-disconnectors and isolators have been The overall dimensions of the different apparatus are available on
designed with a 230 mm pole centre distance. request. For detailed information and other types of apparatus,
As an example, the figure shows the dimensions of the SHS2/T1 please contact us.
type of switch-disconnector.

SHS2/.../N for units 375 mm wide

20
SHS2 for units 500 mm wide

21
6. Fuses

Three fuses for transformer protection can be connected in Transformer protection and selection of fuses
series with the SHS2 switch-disconnector, with dimensional When the isolators are used to control and protect
characteristics complying with DIN 43625 Standards. transformers, they are fitted with a particular type of current-
The fuse striker must have the force and run shown in the limiting fuses which guarantee selectivity with other protection
diagram. devices and can take the high transformer connection
Selection of the fuse according to the voltage and power of currents without deteriorating.
the transformer must be made in conformity with the data In this case, protection against overcurrents on the medium
indicated in the table. voltage side of the transformer is not indispensable since
this task is carried out by the protection provided on the low
voltage side.
The protection on the medium voltage side can be entrusted
F (N) just to the fuse, which must be selected taking into account
the no-load connection current, which can take on values
60 equal to or higher than 10 times the rated current according
to the power of the transformer and to the type of laminations
50
used (hot laminated or with orientated crystals).
40 There is the maximum connection current when circuit-
breaker closing takes place corresponding to the voltage
30 passing through zero.
20 A further result to be guaranteed is protection against faults in
the low voltage winding and in the stretch of the connection
10 from this to the circuit-breaker positioned on the secondary,
avoiding the use of fuses with rated current which is too high,
in order to ensure tripping within a short time even under
10 20 30 40 S (mm)
F = Striker force.
these fault conditions.
S = Striker run.

22
A rapid check of the short-circuit current at the secondary The usage table given below takes both the required
terminals of the transformer and on the supply side of the conditions into account, i.e. sufficiently high rated current to
circuit-breaker on the secondary - if placed at a significant avoid untimely fuse blowing during the no-load connection
distance, allows the trip time to be verified on the fuse stage and, in any case, of a value which guarantees protection
blowing curve. of the machine against faults on the low voltage side.

Table for selecting fuses for transformer protection (*)


Un Rated power of the transformer (kVA)
network 25 40 50 63 80 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000
(kV) Rated normal current of the fuse IN (A)
3 10 16 25 25 40 40 40 63 63 63 80 100 100 – – – – – –
5 6 10 16 16 25 25 25 40 40 63 63 63 80 100 100 – – – –
6 6 6 16 10 16 25 25 40 40 40 63 63 63 80 100 100 – – –
10 6 6 10 10 16 16 16 25 25 25 40 40 63 63 63 80 100 100 –
12 6 6 10 10 10 16 16 16 25 25 25 40 40 63 63 63 80 100 –
15 6 6 10 10 10 16 16 16 16 25 25 25 40 40 63 63 63 80 80
20 6 6 10 6 6 10 16 16 16 16 25 25 25 40 40 63 63 63 63
24 6 6 10 6 6 10 10 16 16 16 16 25 25 25 40 40 63 63 63
(*) ABB CEF type fuses. Increases in the rated normal current of the fuses must be foreseen in the case of transformer overload or in the case of ambient temperature higher than
40 °C.

23
7. Electric circuit diagram

SHS2/T1 electric circuit diagram


Control circuit of the switch-disconnector (24 V DC)

Control circuit of the switch-disconnector (48-110 V DC – 110 V AC)

Continues on page 25

24
SHS2/T1 electric circuit diagram
Control circuit of the switch-disconnector (48-110 V DC – 110 V AC)

Control circuit of the switch-disconnector (220 V DC / V ac)

Continues on page 26

25
7. Electric circuit diagram

SHS2/T1 electric circuit diagram


Control circuit of the switch-disconnector (220 V DC – 220 V AC)

Circuit of the shunt opening release (see note C)

26
SHS2/T2 electric circuit diagram
Circuit of the closing motor

Circuit of the shunt opening release

27
7. Electric circuit diagram

SHS2/T1 - SHS2/T1M - SHS2/N-T1 - SHS2/N-T1M electric circuit diagram


Control circuit of the switch-disconnector

Switch-disconnector and earthing switch auxiliary contacts

28
Circuit for indication of voltage present busbars and line

SHS2/T4 electric circuit diagram


Auxiliary contacts of the earthing switch

29
7. Electric circuit diagram

Auxiliary contacts of the isolator (see note C), for the SHS2/T1, SHS2/T2 and SHS2/T3 type isolators.

Circuit for indicating voltage present on the line for the


SHS2/T1, SHS2/T2, SHS2/T3 and SHS2/T4 isolators

30
Circuit for signalling voltage present on the earth for the
SHS2/T1 and SHS2/T3 isolators

Circuit for signalling fuse blown for the SHS2/T1 and SHS2/
T2 isolators

31
7. Electric circuit diagram

Note: To take development of the product into account it is, in BI421...422 = L ine earth-open position contacts
any case, always useful to refer to the electric circuit diagram BI431...432 = E arthing switch-QE position contacts
provided with each circuit-breaker. -BK = C ontact activated by the key lock
-BU1...3 = C apacitive dividers located on phases L1, L2, L3 of
the line
State of operation shown
-BU1...6 = C apacitive dividers located on phases L1, L2, L3
The diagram is shown under the following conditions:
-BU4...6 = C apacitive dividers located on phases L1, L2, L3 of
– switch-disconnector open the busbars
-C1/L1...L3 = C apacitive dividers located on phases L1, L2, L3 of
the line
– earthing switch open
-C2/L1...L3 = C apacitive dividers located on phases L1, L2, L3 of
the busbars
– circuits de-energised.
-F1…-F3 = M edium voltage fuses
-FF1…3 = M edium voltage fuses
-KC = A uxiliary relay for closing the switch-disconnector
-KO = A uxiliary relay for opening the switch-disconnector
Caption
-KD = A uxiliary relay for with two contacts delayed at
= Number of diagram figure
attraction and two instantaneous contacts
* = See the note indicated by the letter
-MI4 = M otor for operating the switch-disconnector
A1 = Switch-disconnector operating mechanism
-MM = M otor for operating the switch-disconnector
applications
-MO = S hunt opening release (see note C)
A4 = Switchgear applications (indicative apparatus and
connections for operating mechanism and signals) -MS = M otor for operating the switch-disconnector
AK = Switch-disconnector auxiliary circuit diagram -PGN = L amp for signalling switch-disconnector open
-B80/1…2 = Earthing switch position contact -PRD = L amp for signalling switch-disconnector closed
-B80/L = Position contact open during manual operation of -PU1...2 = Voltage indicator located on phases L1, L2, L3 of the
earthing switch -Q80 line/busbars
-B80-90/1…2 = Position contact open during manual operation of -PUD1 = Voltage indicator located on the line
earthing switch -Q80 and during manual operation of -PUD2 = Voltage indicator located on the busbars
the switch-disconnector -Q80 = E arthing switch
-B90/1…3 = Switch-disconnector position contacts -Q90 = S witch-disconnector
-B90/C = Position contact open with switch-disconnector -QE = E arthing switch
closed
-QI4 = S witch-disconnector
-B90/E = Contact activated by the key lock
-RR1…2 = S uppressors of transients
-B90/L = Position contact open during manual operation of
-S75F = C ontact signalling medium voltage fuse blown
switch-disconnector Q90
-SC = P ushbutton for local switch-disconnector closing
-B90/O = Position contact open with the switch-disconnector
open -SO = P ushbutton for local switch-disconnector opening
-BE7 = Position contact open during manual operation of the -SS = L ocal/remote selector
earthing switch -TR = Converter
-BF = Contact signalling medium voltage fuse blown -TR1…2 = R ectifier
-BI1...4 = Position contact open with switch-disconnector -X = Interface connector with the feeder (outside the unit)
closed
-X1…-X3 = Terminal boxes of the operating mechanism
-BI2...5 = Position contact open with switch-disconnector open applications
-BI7 = Position contact open during manual operation of the -XB1 = Terminal boxes for the switch-disconnector auxiliary
switch-disconnector circuits
BI51...53 = Position contacts open with switch-disconnector -XB2 = Terminal boxes for the circuits inside the switch-
BI411...412 = Position contacts of the switch-disconnector disconnector
BI413 = Earthing switch position contacts XB91...94 = Terminal boxes of the operating mechanism
applications
-XB93 = Terminal boxes of operating mechanism application

32
Graphic symbols for electrical diagrams (IEC 60617 and CEI 3-14 ... 3-26 Standards)

Delayed movement Three conductors Make contact Interruttore di


manovra-sezionatore
a doppia interruzione

Mechanical interlock Connection of Break contact Control coil


between two pieces of conductors (general symbol)
apparatus

Rotary handle operating Socket and plug Closing position contact Control coil of a
mechanism (female and male) (limit switch) relay with delay on
attraction

Pushbutton operating Resistor depending on Opening position Lamp (general symbol)


mechanism the voltage, varistor contact
(limit switch)
U

Electric motor operator Motor (general symbol) Isolator Capacitive divider

M M

Earth (general symbol) Rectifier with two Switch-disconnector


half-waves (with bridge)

33
8. Switchgear applications

The SHS2 switch-disconnectors and isolators have mechanical,


SHS2 switch-disconnector.
electrical and layout characteristics ideal for constructing
Complete with fuse-holder
medium voltage metal-enclosed type switchgear for secondary frame and earthing switch
distribution substations. on load side of the fuses.

They can be used in standard or arc-proof version units. ABB


SHS2 isolator.
is able to offer all the apparatus and components needed to
Complete with earthing
complete the switchgear units. switch on load side of
the circuit-breaker.
Please contact us for further detailed information.

Example of unit with


switch-disconnector
and fuses

PR521and REF601
switchgear protection devices
These are provided on board
the HD4/R and VD4/R circuit-
breakers combined with current
sensors of dedicated type. The Circuit-breakers
REF601 CEI 0-16 version is
Both the HD4/R series SF6 gas
also available, specially made to
insulated medium voltage circuit-
comply with CEI 0-16 standards.
breaker and the VD4/R vacuum circuit-
For further information, please
breaker, with right lateral operating
contact us.

Fuses
Fuses according to DIN Standards
are available to be combined with
the SHS2 apparatus.

34
REF542plus micro- Voltage
processor-based unit transformers
The REF542plus unit carries The voltage
out integration of all the transformers
secondary functions relative are of the resin
to a switchgear unit. insulated type.
They comply with
the IEC 60044-2
Standards.
PR512 switchgear protection devices Their dimensions are normally according
The PR512 are devices of the self-supplied type and ensure complete protection of the installation to DIN 42600 Standards.
without an auxiliary power supply.

Current
transformers
The current
transformers
are of the resin
insulated type.
They comply with
the IEC 60044-1
Standards.
Their dimensions are normally according
to DIN 42600 Standards.

Toroidal cable
type transformers
are also available.

mechanism and
230 mm pole centre
distance, are available
to make units with a
circuit-breaker.
Combined voltage-
current sensors
A range of sensors
is available which
optimally covers the
characteristics of
new generations
of instruments and
Example of
of the REF542plus
unit with
unit in particular.
circuit-breaker.
The current sensors conform with the
IEC 60044-8 (CDV) Standard, the voltage
sensors with the IEC 60044-7 Standard.
Their dimensions are according to
DIN 42600 Standards.

35
Notes

36
Contact us

ABB S.p.A. The data and illustrations are not binding. We reserve the

1VCP000046 - Rev. F, en - Technical catalogue - 2010.08 - (SHS2) (gs) a


right to make changes without notice in the course of
Power Products Division technical development of the product.
Unità Operativa Sace-MV
Via Friuli, 4 Copyright 2010 ABB.
All rights reserved.
I-24044 Dalmine
Tel.: +39 035 6952 111
Fax: +39 035 6952 874
e-mail: sacetms.tipm@it.abb.com

www.abb.com