Test report

Test system SCHLEICH MTC2-40kV | 13564


Test plan 0571190297 AISLACION - SIERRA GORDA
S/N 0571190297 AISLACION
Test date 3/29/2021 4:02:35 PM
Customer SIERRA GORDA

Summary
Resistance 1-2 ----- not
tested
Resistance 2-3 ----- not
tested
Resistance 3-1 ----- not
tested
Deviation ----- not
tested
Surge 1-2 ----- not
tested
Surge 2-3 ----- not
tested
Surge 3-1 ----- not
tested
Compare ----- not
tested
Insulation test 519.4V, 24.808 GOhm, Imax1=5.698µA, Tested
Imax2=3.060µA, DAR out of range, PI= -

0571190297 AISLACION / 3/29/2021 4:02:35 PM 1/2


Resistance test
Test step Set value(s) Real value(s)
Resistance 1-2 --- ----- not
tested
Resistance 2-3 --- ----- not
tested
Resistance 3-1 --- ----- not
tested
Deviation --- ----- not
tested

Surge test
Test step Set value(s) Real value(s)
Surge 1-2 --- ----- not
tested
Surge 2-3 --- ----- not
tested
Surge 3-1 --- ----- not
tested
Compare --- ----- not
tested

Insulation test DC
Test step Set value(s) Real value(s)
Insulation test --- 519.4V, 24.808 GOhm, Tested
Imax1=5.698µA, Imax2=3.060µA,
DAR out of range, PI= -

Voltage in V Insulation test Current in µA


6 0 0 .0 1 0 .0 0

1.00
5 0 0 .0

0.10
4 0 0 .0

0.01
Legend
3 0 0 .0 Voltage
Current
0.00 1

2 0 0 .0
0.00 01

1 0 0 .0
0.00 00

0 .0 0.00 00
0 .0 s 1 0 .0 s 2 0 .0 s 3 0 .0 s 4 0 .0 s 5 0 .0 s 6 0 .0 s

Insulation test explanations:


Imax1: maximum current during the ramp up
Imax2: maximum current after the test voltage has been reached
DAR and PI: Resistance > 5GOhm => Values are ambiguous and will be disregarded (IEEE Std 43-2000)

Surge test explanations:


Cor.: (Correlation) Being a mathematical procedure to the inquiry of the resemblance of two signals.
EAR.: (Difference surface) determines the originating surface between two curves and compares this.
AREA: the surface is calculated between signal and the zero line and is compared to the reference.
Zero Crossing: with the help of the zero passageways the frequency is determined and compared
Attenuate: Damping of the curve oscillation
PDIV: PD start voltage
PDEV: PD stop voltage

0571190297 AISLACION / 3/29/2021 4:02:35 PM 2/2