Professional Documents
Culture Documents
Flat Slab V02
Flat Slab V02
1. introduction:
Flat slab is a beamless reinforced concrete slab in which the load is directly transmitted to the
supporting columns.
Flat slab is a preferred for heavy live loads (500kg/m2 or more) and for long spans up to 10 meters
and for big clear height between the successive floors.
The connection between the slab and the supporting columns is discussed as shown the following
figures.
1-flat slab without drop and without column head is suitable for L. L. about 200: 300 kg/m2.
2-Flat slab with column head and without drops is suitable for L. L. about 500 kg/m2.
3-Flat slab with column head and with drop for heavy live loads about 1000kg/m2.
Fig.[Critical shear
perimeter in flat slab
2 Notations:
L1 : length of the panel in the direction of the span.
L2 : Width of the panel in the perpendicular direction.
L1 & L2 are measured from the centers of the
columns.
D : Diameter of the column or column head, or the
largest circle drawn inside its sec.
w : Total load per unite area of the panel.
t = total thickness of slab.
D : Effective depth.
3- Minimum dimensions
a) Minimum flat slab thickness is 15 cm and should not
be less than :
External Internal panel
Panel
Without drop L/32 L/36
With drop L/36 L/40
The diameter of a column (if circular), or the side length of a rectangular column should in no case
be less than the greatest of the following values:
*D min = 30 cm 30 cm
*1/20 of the panel length in the same direction L/20
* 1/15 of the height of the floor (H) H/15
Dimensions of column head and drop panels:
L : is short length
Panels are assumed to be divided into the following strips.
W∗(L3)2 W∗(L3)2
M5 = + M6 = -
12 12
Distribution factors (D.F.)
At Jt 2 (D.F.)
(D.F.2) (D.F.3)
Is1 ΤL 1 Ic2 L ΤHL Ic2 up ΤHup Is2 ΤL2
Is1 Ic2L Ic2 up Is2
: σk
: σk
∶ σk
σ k= + + H + L
L1 H L up 2
At Jt 3 (D.F.)
(D.F.4) (D.F.5)
Is2 ΤL 2 Ic3 L ΤH𝐿 Ic3 up ΤH𝑢𝑝 Is3 ΤL3
I I Ic3 up Is3 : σ𝑘
: σ𝑘
∶ σ𝑘
σ 𝑘= s2 + c3L + + L
L2 H 𝐿 H𝑢𝑝 3
At Jt 4 (D.F.)
c) The drops, if any, must have a length in each direction of not less than 1/3 long length of the panel and should not exceed
1/2 short length of the panel. For exterior panels the width of the drop at right angles to the edge, and measured from the
center line of the column, should be equal to 1/2 the width of the drop in interior panels. Depth of drop should not less than
1/4 the slab thickness.
d) When the column strip is taken equal to the width of the drop, the width of field strip is increase to a value greater than
1/2 of the breadth of the panel. The B.M. in the field strip should be increased by the same ratio and the B.M. in the
column strip is to be decreased. Anyhow the sum of both B.M. in column and field strip should not be less than the sum
of B.M. (+ve & -ve) which is resisted by both the column and field strip together.
e) The effective width is taken equal to the total width of the slab (distance between axis of columns) for calculating the
rigidity of slab under vertical loads while under transverse loads it is taken equal to the width of column plus three times the
slab thickness from each side of column under the condition that it should not be greater than 1/3 distance between axis of
columns.
4.2- Empirical Method
* This method needs more applied conditions than frame method as:-
1- The slabs should comprise a series of rectangular panels of approximately constant thickness arranged in at least three
rows in two directions at right angles, and the ratio of the length of a panel to its width should not exceed 4:3 ( i.e. min. 3
span , L1/L2 < 4:3)
2- The drops, if any, must have a length in each direction of not less than 1/3 long length of the panel and should not exceed
1/2 short length of the panel . For exterior panels the width of the drop at right angles to the edge, and measured from the
center line of the column, should be equal to 1/2 the width of the drop in interior panels. Depth of drop should not less than
1/4 the slab thickness.
3- The length or width of any two adjacent panels in a series should not differ by more than 10 % of the greater length or
width, and any two spans should not differ by more than 20 %. End spans may be shorter, but not longer than interior spans.
Where adjacent spans differ, the length should always be taken as that of the longer span in calculating the bending
moments.
Critical sections for B.M. in flat slabs:
Mo = wL2 / 8 [ L1 – (2D/3)]2 Where: L1= length of panel in the direction considered L2= length of panel in the
perpendicular direction.
This moment should be divided between the column and field strips as shown in table (3-2)
1- The internal and external columns should be designed to resist bending moments equal to 50 %& 90% of the –ve
bending moments in column strip respectively, according to table(3-2). These moments are divided between the upper
and lower columns according to their stiffness.
In this case, the direct load on the internal column, can be reduced considering that only one side of the panel is
loaded with live loads.
2-If the external columns carry parts of the slabs and walls as cantilevers, the bending moment in these columns, can
be reduced by the value of the bending moment due to the dead load of the cantilever.
End
Exterior Panel Interior Panel
Table 3-2 Support
Strip type -ve -ve Int. +ve M -ve M +ve M
A = No beams Ext. M M
B = beams with total depth equal to or more than 3 times the
slab thickness. Colum A 25 50
n Strip 30 45 25
B 20
Field A 5 20
20 15 15
Strip B 10
4-3 Bending moment in panels with& without marginal beams:
a) For Marginal beam of total depth equals to or more than 3 times slab thickness, then:
1- The total load to be carried by the beam should be equal to the direct loads on the beam plus a uniformly
distributed load equal 1/4 the total load on the panel.
2- The bending moment in the half column strip adjacent to the beam will be 1/4 the values given in tables
(3-1 & 3-2)
b) Case of no marginal beam: The B.M. in edge column strip will be half the values given in tables (3-1 & 3-
2)
* Transfer of –ve moments from flat slab to columns.
- The unbalanced –ve moments of the column strips are transferred to columns by flexural and torsional moment as follows:
In external spans all the –ve moments are transferred to columns (fig. 3-8-a), while in internal spans the difference of –ve
moments are transferred to columns (fig. 3-8-b) according to the following distribution:
where:
f = Coefficient of moments transferred by flexure b1= dimension of punching critical section length measured in the
direction of B.M
b2= dimension of punching critical section width measured in the perpendicular direction.
(a)
(b)
Fig.[3-8] Transfer of moment from column strip to columns
Where:
where q = 1-f
This transfer of torsional moments produces additional punching shear stresses on the critical sections shown in fig.(3-11).
These stresses can be calculated in both directions according to the following equations:
qup= Qup /(bod) In These stresses are added to punching shear stresses resulting from vertical load according to
Column heads are to be reinforced by Rft. (1 & 2) which are anchored by stirrups (3) .which must be
sufficient to resist the B. M. From the worst position and the B. M.
Minimum reinforcement is:
1) For rectangular column head 1/25 of area of negative reinforcing / m of column strip in direction
considered multiplied by length of perpendicular panel to this reinforcement.
2) For circular column head the sum of Rft. 1 & 2 obtained as above are to be distributed along the
perimeter of the column head.
Reinforcement of columns head
4.3 Openings in flat slab:
a) It is not allowable to openings at regions of column head.
b) It is allowable to make openings at the sharing areas between field strips under the following conditions.
1-The max. dimension of the opening should not be more than 0.4 L in the direction parallel to the axis.
2-The + ve & - ve flexure design moments should be redistributed on the residual parts of the structure to be compatible
. with the variation occurred due to existence of the opening.
c) It is allowable to make openings at the sharing areas between field strips and column strips under the following conditions.
1-The max. Dimension of the opening should not be more than 0.25 width of column strip.
2-The sections of the two strips at region of the opening can resist the flexure design moments.
d) It is allowable to make openings at the sharing areas between two columns strips under the following condition:
1-the maximum dimension of the opening should not be more than (1/10) width of the smaller columns strip.
2-The sections of the two strips at region of the opening can resist flexure design moments.
3-the value of live load used to calculate shear stress could be reduced by a value equal to the effect of the opening . .
. which intersects the mentioned perimeter fig (3-14-a).
e) In case of exceeding the dimensions of openings more than the proportions mentioned before a, b, c, d an accurate structural
calculations which achieve resistance requirements and cases of working limits should be made.
(a) Shapes of openings in flat slab
(b) Max. dimension of openings in flat slab
Fig.[3-14] Shapes of openings & its max. dimensions in flat slab
APPendix:
*Shear of punching capacity according to Egyptian Code
Egyptian building Code recommends that the critical section of shear of punching at flat slab is at a space "d/2" from the
circumference of the face of the column
Punishing is resist by concrete up to 25 cm, if slab thickness exceed or equal 25 cm it is preferred to use stirrups to resist
punishing.
Steel stirrups for resisting punching shear is calculated from the following relation: