Ø168 Table.

1 Technical Parameters

Inner terminal for cable Rated voltage(50/60Hz): 245kV


Ø40 Top Terminal ,
Rated phase-to-earth voltage: 142kV
Brass Tin plated M10
M10

125
Ø8 One minute power frequency withstand
505kV
voltage(dry):
Ø8.5
Anti-corona head,
Rated current: 1600A
Aluminum alloy

35
Partial discharge level at 245kV: ≤10pC
Ø42
Ø48 Tanδ of bushings: ≤0.4%
2240±10 (Arcing distance)

Lightning impulse withstand voltage(dry): 1050kV


Test tap voltage withstand level: 2kVrms

Test Tap Creepage distance: ≥7812mm


Rated thermal short-time current, 2sec(Ith): 40kA
Flange
Rated dynamic current(Id): 100kA
Insulating layer
Silicone rubber Ambient temperature: -10°C to+60°C
sheds
L±20

Altitude above mean sea level: ≤1000m


Ø490
Installation angle: 0-90°
Grounding Cap
Cantilever test load: 4000N
Type of conductor: Draw lead
A A Test tap A-A
25 30° Internal insulation: RIP
170

2-Lifting lugs 15°


2-M12 For Earthing External insulation/Colour: Silicone rubber / Gray
L2 (CT Length)

Comply with standard: IEC 60137


Flange,Aluminum alloy Test tap
Transformer
Ø300(sealing area:min.diameter) air vent
**Please confirm the dimensions of the bushing.
L1±5

Ø260
12-Ø20
Ø400
Ø450
B
30

Table.2 Main Dimensions


65

Ø245 Ø40 Main Dimensions(mm)


Ø48 Net weight
Bushing Type
kgs
View B L L1 L2
Ø50
FBRGL-245/1600 3995 1350 500 480

End shield,Surface ALL DIMENSIONS ARE IN MILLIMETERS


coated with Epoxy Drawing No.: 0CX.302.080.04-2 Rev.0: 30/11/2023
UNLESS OTHERWISE STATED
65

Designer

10 Ø40 30 R32.5 Nanjing Rainbow Electric Co.,Ltd


Ø130 Approver
Ø245