DATA OF ELEMENTS

Messrs. :
Project : Maranta Bosques
Reference : Calculo de cortocircuito trifasico simetrico File name : MarantaT4.ms2
Engineer : CAMCh Created date : 22-11-2023
Changed : Changed date :
Comments : Para vo.bo.

[Reference capacity and Frequency]


Reference capacity : 1000kVA, Frequency : 60Hz
[Source]
Resistance Reactance Impedance
Ref.No. Voltage Phase Capacity X/R
R X Z
0.09617%r 0.1923%r 0.2151%r
CJM53090-CJM25X23000V 3Phases 465MVA 2
508.8mohms 1018mohms 1138mohms
[High-voltage circuit breaker]
No data
[Transformer]
Phase / Short-circuit
Primary Secondary Rated Resistance Reactance Impedance Peak value of Damping time
Ref.No. Earthing Capacity X/R current
voltage voltage Current R X Z rush current constant
system I"k3direct
1.460%e 3.010%e 3.345%e
3Phases 13times 7cycles
T-T4 23000V 440V 225kVA 295.2A 2.061644 6.489%r 13.38%r 14.87%r -
TN-S 3838Arms 116.666667ms
12.56mohms 25.90mohms 28.79mohms
2.131%e 3.850%e 4.40%e
3Phases 14times 6cycles
T-SG4 440V 220V 112.5kVA 295.2A 1.806667 18.94%r 34.22%r 39.11%r -
TN-S 4133Arms 100ms
9.167mohms 16.56mohms 18.93mohms
3.317%e 3.754%e 5.010%e
3Phases 23times 5cycles
T-PTAR 440V 220V 30kVA 78.73A 1.131737 110.6%r 125.1%r 167.0%r -
TN-S 1811Arms 83.333333ms
53.52mohms 60.57mohms 80.83mohms
[Generator]
AC component Peak value of
Transient Sub-transient DC time Sub-transient Stator
Rated Phase / Rated of short-circuit short-circuit
Ref.No. Capacity reactance reactance constant time constant resistance
voltage Earthing Current current current
X'd X"d Tdc T"d Ra
system Iac load Iac
3Phases
G1 440V 312kVA 409.4A 28.00%e 17.00%e 0.04000s 0.02500s 1.127%e 2.349kA 5.780kA
TN-S
[Motor effect]
No data
[Zero conductor]
Operational Short-circuit
Ref.No. Phase
voltage current I"k3
Bpri 440V 3Phases 8.6993kA
Bsg4 220V 3Phases 4.8438kA
Bptar 220V 3Phases 1.4453kA
1
[Bus-duct]
No data
[Bus-bar]
No data
[Wire]
Load current Current-
Material / Installation / Core Centre-line Short-circuit
Operational Wire Core IB / carrying Resistance Reactance Impedance
Ref.No. Insulation / Number of Length size(mm²) distance current
voltage system constraction Voltage capacity R X Z
Ambient temp. circuit xNumber a I"k3 Force
drop Iz
1.120mohms/m 0.1044mohms/m 1.125mohms/m
3Phases 16x1 81.96A 8.000mm 0.000mohms 0.000mohms 0.000mohms
0.000%r 0.000%r 0.000%r

Cu 1.120mohms/m 0.1044mohms/m 1.125mohms/m


N Method F 0A 16x1 81.96A 8.000mm 0.000mohms 0.000mohms 0.000mohms
W1 440V PVC70deg. Single-Core 0m -
1 0.000% 0.000%r 0.000%r 0.000%r
30deg.

1.120mohms/m 0.1044mohms/m 1.125mohms/m


PE 16x1 81.96A 8.000mm 0.000mohms 0.000mohms 0.000mohms
0.000%r 0.000%r 0.000%r

[Low-voltage circuit breaker]


Rated
Short-
current Long- Short- ON
Operational Manu- Instan- circuit
Ref.No. Kind Type of breakers Pole or time time Ics Icu or Icn Icu-back Back up breaker or Selected by
voltage facturer taneous current
Current delay delay OFF
I"k3direct
setting
Not
CB1 440V 3 400A - - - - ON
selected
Not
CB0 440V 3 400A - - - - OFF -
selected
Not
CB2 440V 3 80A - - - - ON -
selected
Not
CB3 440V 3 20A - - - - ON -
selected
Not
CB4 440V 3 30A - - - - ON -
selected
Not
CB5 440V 3 40A - - - - ON -
selected
Not
CB6 440V 3 40A - - - - ON -
selected
Not
CB7 440V 3 40A - - - - ON -
selected
Not
CB8 440V 3 30A - - - - ON -
selected
Not
CB20 440V 3 40A - - - - ON -
selected
Not
CB9 440V 3 20A - - - - ON -
selected
2
Rated
Short-
current Long- Short- ON
Operational Manu- Instan- circuit
Ref.No. Kind Type of breakers Pole or time time Ics Icu or Icn Icu-back Back up breaker or Selected by
voltage facturer taneous current
Current delay delay OFF
I"k3direct
setting
Not
CB10 440V 3 200A - - - - ON -
selected
NF63-HW Fixed - Not
CB11 440V MCCB(Fix) 3 50A Fixed 5.000kA 10.00kA - - ON 8.6993kA
- - selected
Not
CB14 220V 3 400A - - - - ON -
selected
NF63-HW Fixed - Not
CB12 440V MCCB(Fix) 3 50A Fixed 5.000kA 10.00kA - - ON 8.6993kA
- - selected
Not
CB15 220V 3 125A - - - - ON -
selected
Not
CB16 220V 3 40A - - - - ON -
selected
Not
CB17 220V 3 100A - - - - ON -
selected
Not
CB18 220V 3 50A - - - - ON -
selected
NF125-CW Fixed - Not
CB13 220V MCCB(Fix) 3 100A A 15.00kA 30.00kA - - ON 1.4453kA
- - selected
[Contactor + Thermal relay]
No data
[Motor]
Operational Full load Power Phase of Starting Starting inrush
Ref.No. Phase Capacity Starting time
voltage current Im factor current current current
8 x Im 12 x Im
M1 440V 3Phases 22.38kW 34.55A 0.85 -31.79deg. 10s
276.4A 414.6A
8 x Im 12 x Im
M6 440V 3Phases 7.78kW 12.01A 0.85 -31.79deg. 10s
96.08A 144.1A
8 x Im 12 x Im
M12 440V 3Phases 14.92kW 23.03A 0.85 -31.79deg. 10s
184.3A 276.4A
8 x Im 12 x Im
M11 440V 3Phases 1.492kW 2.303A 0.85 -31.79deg. 10s
18.43A 27.64A
8 x Im 12 x Im
M3 220V 3Phases 12.3kW 37.98A 0.85 -31.79deg. 10s
303.8A 455.7A
8 x Im 12 x Im
M4 220V 3Phases 16.8kW 51.87A 0.85 -31.79deg. 10s
415.0A 622.4A
[General load]
Operational Load current Power Phase of Starting
Ref.No. Phase Starting time
voltage IL factor current current
1.7 x IL
FILTROS 440V 3Phases 1.63A 0.7 -45.57deg. 300s
2.771A
1.7 x IL
ELEVADOR 1 440V 3Phases 14.9A 0.85 -31.79deg. 300s
25.33A
1.7 x IL
ELEVADOR 2 440V 3Phases 14.9A 0.7 -45.57deg. 300s
25.33A
3
Operational Load current Power Phase of Starting
Ref.No. Phase Starting time
voltage IL factor current current
1.7 x IL
MONTACARGAS 440V 3Phases 19.6A 0.85 -31.79deg. 300s
33.32A
1.7 x IL
TRANSFER 440V 3Phases 11.2A 0.85 -31.79deg. 300s
19.04A
1.7 x IL
E1 220V 3Phases 81.3A 0.85 -31.79deg. 300s
138.2A
1.7 x IL
J4 220V 3Phases 5.1A 0.85 -31.79deg. 300s
8.670A
1.7 x IL
AA1 220V 3Phases 40.1A 0.85 -31.79deg. 300s
68.17A
1.7 x IL
AEX 220V 3Phases 3.9A 0.85 -31.79deg. 300s
6.630A
[Capacitor]
No data