DATA SHEET FOR TRANSFORMERS
Document No. : XXXXXX Rev : XX

Project No. :XXXXXX Page : 2 of 8

The table below is a brief summary of the most recent revisions to this document. Details of all revisions are held on
document by the issuing department.

Sr. No. Rev. No. Issue No. Date of issue Description of revision
1 A 1 DD-MM-YYYY Issued for EBOK
DATA SHEET FOR TRANSFORMERS
Document No. : XXXXXX Rev :X

Project No. :XXXXXX Page : 3 of 8

1. SCOPE
THIS DOCUMENT COVERS THE TECHNICAL AND DESIGN REQUIREMENTS IN A FORM OF DATASHEET FOR TRANSFORMERS
INSTALLED IN PROJECT FACILITIES OF FERRUKA-HARARE PIPELINE SERIES OPERATION.

2. GENERAL NOTES

1. VENDOR TO PROVIDE DETAILED DATASHEET FOR EACH TRANSFORMER.


2. TRANSFORMER DESIGN SHALL BE SUITABLE FOR PRIMARY INPUT VOLTAGE VARIATION OF +/-10% AND FREQUENCY
OF +/-5%.
3. THERMAL IMAGE WINDOWS SHALL BE PROVIDED AT PRIMARY, SECONDARY, AND NEUTRAL CABLE BOXES.
THE WINDOWS SHALL WITHSTAND THE PRESSURE CREATED DUE TO SHORT CIRCUIT INSIDE THE CABLE BOX.
IT SHALL BE TYPE TESTED WITH TRANSFORMER CABLE BOXES.
4. OIL AND WINDING TEMPERATURE RISE SHALL BE BASED ON THE AVERAGE YEARLY AMBIENT TEMPERATURE
OF 37 DEG C.
5. VENDOR SHALL SUBMIT APPROPRIATE CALCULATIONS TO PROVE THAT TRANSFORMER CABLE BOXES ARE CAPABLE
OF WITHSTANDING FAULT CONDITIONS.
6. TYPE TEST CERTIFICATE SHALL BE PROVIDED FOR SIMILAR TRANSFORMER.
7. PRE-COMMISSIONING AND COMMISSIONING OF THE EQUIPMENT SHALL BE DONE IN THE PRESENCE OF THE OEM.
8 FERUKA TRANSFORMER RATINGS ARE AS STATED. WILTON TRANSFOMER RATING SHALL BE RE-VERRIFIED BASED ON
VENDOR INPUTS BEFORE PO PLACEMENT AT A LATER STAGE
3 ABBREVIATIONS

IEC INTERNATIONAL ELECTROTECHNICAL COMMISSION


SLD SINGLE LINE DIAGRAM
TBA TO BE ADVISED
OLTC ON LOAD TAP CHANGER
ONAN OIL NATURAL AIR NATURAL
ONAF OIL NATURAL AIR FORCED
AN AIR NATURAL
CU COPPER
XLPE CROSS LINKED POLY ETHYLENE
PVC POLY VINYL CHLORIDE
SWA STEEL WIR ARMOUR
kV KILO VOLT
kVA KILO VOLT AMPERE
CT CURRENT TRANSFORMER
LV LOW VOLTAGE
MV MEDIUM VOLTAGE
IP INGRESS PROTECTION

3 REFERENCE STANDARDS

IEC 60076 POWER TRANSFORMERS - ALL PARTS


IEC 60214 TAP CHANGERS
IEC 61869 INSTRUMENT TRANSFORMERS- ALL PARTS
IEC 60296 FLUIDS FOR ELECTROTECHNICAL APPLICATIONS - UNUSED MINERAL INSULATING OILS
FOR TRANSFORMERS AND SWITCHGEAR
IEC 60156 INSULATING LIQUIDS-DETERMINATION OF THE BREAKDOWN VOLTAGE AT POWER
FREQUENCY - TEST METHOD
IEC 60085 ELECTRICAL INSULATION - THERMAL CLASSIFICATION
BS 5467 ELECTRICAL CABLES-THERMOSETTING INSULATED, ARMOURED CABLES FOR
VOLTAGES OF 600/1000V AND 1900/3300V.
BS 6121 MECHANICAL CABLE GLANDS
DATA SHEET FOR TRANSFORMERS
Document No. : XXXXXX Rev :X

Project No. :XXXXXX Page : 4 of 8

BS EN 10204 METALLIC PRODUCTS - TYPE OF INSPECTION DOCUMENTS


BS EN 60228 CONDUCTORS OF INSULATED CABLES
BS EN 60332 TESTS ON ELECTRIC AND OPTICAL FIBRE CABLES UNDER FIRE CONDITIONS
BS EN 62444 CABLE GLANDS FOR ELECTRICAL INSTALLATIONS
EN 60079 EXPLOSIVE ATMOSPHERES
EN 60529 SPECIFICATION FOR DEGREES OF PROTECTION PROVIDED BY ENCLOSURES (IP CODE)
EN 61000-6-4 ELECTROMAGNETIC COMPATIBILITY
EN 61508 FUNCTIONAL SAFETY OF ELECTRICAL/ELECTRONIC/PROGRAMMABLE ELECTRONIC
SAFETY-RELATED SYSTEMS
EUROPEAN
DIRECTIVE
89/366/EEC ELECTROMAGNETIC COMPATIBILITY DIRECTIVE
ISO-9001-2015 QUALITY MANAGEMENT AND QUALITY ASSURANCE STANDARDS

4 REFERENCE DOCUMENTS

19911-EL-SPC-CMN-002 SPECIFICATION FOR TRANSFORMERS


S/No DESCRIPTION DESIGN DATA SUPPLIER DATA
1) GENERAL

2) TAG NO.

3) MANUFACTURER ***

4) COUNTRY OF ORIGIN ***


5) GENERAL DATA

SPECIFICATION FOR DISTRIBUTION


7) GENERAL SPECIFICATION
TRANSFORMER (XXXXXX)

8) ENVIRONMENTAL CONDITIONS
PLACE OF INSTALLATION (INDOORS, OUTDOORS,
9) OUTDOOR
UNDER SHELTER)
10) ALTITUDE XXX M
11) MAXIMUM AMBIENT TEMPERATURE XXXOC
O
12) DESIGN AMBIENT TEMPERATURE XXX C
13) RELATIVE HUMIDITY UPTO XX%
14) DEGREE OF PROTECTION (IP) IP55
15) SPECIAL CONDITIONS (TROPICALISATION, ETC.) TROPICALISATION
16) GENERAL CHARACTERISTICS
17) RATED POWER ( SR ) XXXX kVA As Per Sizing
18) RATED PRIMARY VOLTAGE XX KV
19) RATED SECONDARY VOLTAGE AT NO LOAD XX kV
SECONDARY VOLTAGE AT RATED POWER AND P.F
20) XX kV
0.8
21) RATED FREQUENCY 50 HZ
22) CONNECTION SYMBOL AND VECTOR GROUP Dyn 11
MAXIMUM FLUX DENSITY AT 110 % OF OVER-
23) < 1.72 TESLA
VOLTAGE AND FREQUENCY
24) TYPE OF TRANSFORMER
25) WITH SEPARATE WINDINGS YES
26) AUTO-TRANSFORMER NO
27) INSULATION SYSTEMS
28) INSULATION CLASS CLASS A
29) UNIFORM INSULATION YES
30) NON-UNIFORM INSULATION NO
IF NON-UNIFORM,
31) N/A
POWER FREQUENCY WITHSTAND
32) POWER FREQUENCY WITHSTAND VOLTAGE:
33) • PRIMARY XX kV
34) • SECONDARY XX kV
35) IMPULSE WITHSTAND VOLTAGE:
36) • PRIMARY XX kV
37) • SECONDARY XX kV
38) OIL IMMERSED TRANSFORMER YES

39) OIL TYPE NON TOXIC SYNTHETIC MINERAL OIL

40) SEALED TYPE CONSERVATOR TYPE


41) COMPLETELY FILLED ***
42) WITH GAS CUSHION ***
ONAN (WITH PROVISION OF 125% ON ONAF)
43) TYPE OF COOLING (ONAN, ONAF, AN)
(ADDITION OF FANS IN FUTURE)
44) MODE OF OPERATION
45) INDIVIDUAL -
46) PARALLEL PARALLELED FOR SHORT DURATION
47) PRIMARY WINDING
48) HIGHEST VOLTAGE ( UM ) XXXX V
49) COPPER YES
50) ALUMINIUM NO
51) MAXIMUM CURRENT DENSITY IN THE WINDING ***
52) RATED PRIMARY CURRENT ***

Datasheet for Transformer 5 of 8


S/No DESCRIPTION DESIGN DATA SUPPLIER DATA
53) SECONDARY WINDING
54) HIGHEST VOLTAGE ( UM ) XXX V
55) COPPER YES
56) ALUMINIUM NO
ADDITIONAL NEUTRAL BROUGHT OUT IN A
57) YES
SEPARATE BOX
58) EARTHING SYSTEM SOLID
59) MAXIMUM CURRENT DENSITY IN THE WINDING ***
60) RATED SECONDARY CURRENT ***
61) ELECTRICAL AND MECHANICAL CHARACTERISTICS
62) NO-LOAD CURRENT (PRIMARY) ***
MIN. 1.8 TIMES OF TRANSFORMER RATED
63) MAGNETIZING INRUSH CURRENT
CURRENT
64) DURATION OF MAGNETIZING INRUSH CURRENT ***
65) SHORT CIRCUIT IMPEDANCE AT 75°C MINIMUM 6% AS PER IEC 60076-5
66) ZERO SEQUENCE IMPEDANCE ***
67) POSITIVE SEQUENCE X/R RATIO ***
68) NEGATIVE SEQUENCE X/R RATIO ***
69) PRIM. SYSTEM APPARENT SHORT CIRCUIT RATING AS PER SLD DWG
70) MAX. SHORT CIRCUIT DURATION AS PER SLD DWG
71) TOP OIL TEMPERATURE RISE 63°C
72) AVERAGE WINDING TEMPERATURE RISE 68°C
73) HOT SPOT TEMPERATURE ***
74) NO-LOAD LOSSES ***
75) LOAD LOSSES ***
76) TOTAL LOSSES ***
77) EFFICIENCY IN % AT 4/4, 3/4, 1/2 & FULL LOAD *** / *** / *** / ***
78) TAP CHANGERS
79) OFF-CIRCUIT (Y / N) YES
80) NO. OF TAPPINGS AS PER SLD
81) TAPPING STEP 2.5
82) TAPPING RANGE - 5 % TO + 5 %
83) TANK
84) TANK MATERIAL ***
85) FABRICATED UNDER BASE YES (THICKNESS MINIMUM 10 MM)
86) THICKNESS OF TANK (6 MM MINIMUM)
87) • SIDES ***
88) • BOTTOM ***
89) • TOP ***
90) TYPE OFTANK(SEALED/CONSERVATOR) CONSERVATOR TYPE
91) TANK COVER TYPE
92) BOLTED NO
93) WELDED YES
94) BELL TYPE NO
95) THICKNESS ***mm
96) DIMENSIONS
97) OVERALL, WITH ACCESSORIES ***mm
(HEIGHT / WIDTH / DEPTH)
98) BETWEEN AXIS ***mm
99) ROLLER TYPE NOT APPLICABLE
100) WEIGHTS
101) TOTAL ***kg
102) OIL ***kg
103) UNTANKING ***kg
104) VOLUME OF OIL ***liters
105) MAKE OF OIL ***
106) NOISE LEVEL
107) WITHOUT COOLING < 80 db(A) at 1 m
108) WITH COOLING N/A
109) CONNECTIONS
110) PRIMARY VOLTAGE SIDE
111) CABLE CONNECTION YES
112) CABLE TYPE CU/XLPE/PVC/SWA/PVC

Datasheet for Transformer 6 of 8


S/No DESCRIPTION DESIGN DATA SUPPLIER DATA
AS PER CABLE SCHEDULE (SHALL BE SHARED
113) PARALLEL CABLE
WITH VENDOR )
AS PER CABLE SCHEDULE (SHALL BE SHARED
114) SECTION OF CABLE
WITH VENDOR )
115) TYPE OF BUSHING AND RATING (KV/A) ***
116) SPACE FOR CURRENT TRANSFORMER ***
117) PLUG IN TERMINAL NO
118) CABLE BOX WITH OIL NO
119) SF6 CONNECTION NO
PROTECTIVE ENCLOSURE COMPLETE WITH
120) AIR INSULATED CABLE BOX WITH GLANDS
CABLE GLANDS
THERMAL IMAGE WINDOW FOR CABLE
121) REQUIRED
INVESTIGATION
122) PRESSURE RELIEF DIAPHRAGM REQUIRED
123) DISCONNECTING CHAMBER / LINKS REQUIRED
124) SECONDARY VOLTAGE SIDE
BUS DUCT (OPTIONAL FOR TRANSFORMERS
125) NA
>1600KVA)
126) CABLE CONNECTION YES
127) CABLE TYPE CU/XLPE/PVC/SWA/PVC
128) PARALLEL CABLE HOLD
129) SECTION OF CABLE HOLD
130) TYPE OF BUSHING AND RATING (KV/A) ***
PROTECTIVE ENCLOSURE COMPLETE WITH
131) AIR INSULATED CABLE BOX WITH GLANDS
CABLE GLANDS
THERMAL IMAGE WINDOW FOR CABLE
132) REQUIRED
INVESTIGATION
133) PRESSURE RELIEF DIAPHRAGM REQUIRED
134) DISCONNECTING CHAMBER / LINKS REQUIRED
135) NEUTRAL SIDE
NEUTRAL TERMINAL IN A SEPARATE NEUTRAL
136) YES
TERMINAL BOX
THERMAL IMAGE WINDOW FOR CABLE
137) REQUIRED
INVESTIGATION
138) PRESSURE RELIEF DIAPHRAGM REQUIRED
139) COOLING SYSTEM
COOLING SYSTEM AND ASSOCIATED PROVISION TO BE MADE FOR ADDITION OF
140)
CONTACTORS FUTURE FANS
141) TOTAL NO OF RADIATORS ***
142) TOTAL NUMBER OF FANS ***
143) RATED POWER N/A
144) SUPPLY VOLTAGE / FREQUENCY N/A
145) CONTROL AND PROTECTION DEVICES
OVER TEMP. / LOW LEVEL / OVER PRESS. RELAY
146) YES
(TYPE DGPT2)
BUCHHOLZ RELAY WITH 2 CONTACTS (ALARM /
147) N/A
TRIP)
THERMAL IMAGE TYPE WINDING TEMPERATURE
148) YES
WITH 4 CONTACTS (ALARM/TRIP)
TOP OIL THERMOMETER WITH 4 CONTACTS
149) YES
(ALARM / TRIP)
DIAL THERMOMETER WITH 4 CONTACTS
150) YES
(ALARM/TRIP)
151) THERMOWELL YES
152) THERMOSTAT ***
LIQUID LEVEL GAUGE WITH 2 CONTACTS
153) YES
(ALARM/TRIP)
PRESSURE RELIEF VALVE WITH OPERATING 4
154) YES
SIGNAL CONTACTS
PRESSURE VACUUM GAUGE WITH OPERATING 4
155) YES
CONTACTS (ALARM/TRIP)
156) DISSOLVED GAS (DGA) MONITORS NO
YES
NEUTRAL CT IN SEPARATE NEUTRAL
157) CLASS 5P20 FOR 51G
TERMINAL BOX (Y / N)
RATING: *** (AS REQUIRED)

Datasheet for Transformer 7 of 8


S/No DESCRIPTION DESIGN DATA SUPPLIER DATA
158) ACCESSORIES
159) PRIMARY SURGE ARRESTER YES
160) LV NEUTRAL SURGE ARRESTER NO
161) AIR DRYER N/A
162) LIFTING EYES & JACKING LUGS YES
PULLING EYES FOR MOVING TRANSFORMER IN
163) YES
ALL DIRECTIONS
164) FILLER PLUG YES
TRAVELLING WHEELS (FIXED / ORIENTABLE) OR WHEELS WITH LOCK MECHANISM ALONG
165)
LIFTING PADS/LUGS WITH LIFTING PADS/LUGS
166) EARTH TERMINAL YES,2
167) AUXILIARIES TERMINAL BOX YES
168) FILLING VALVE ON TANK AND RADIATORS YES
169) TANK ACCESS LADDER YES
FLANGE BLINDED ISOLATION VALVE ON
170) REQUIRED
RADIATORS (TOP AND BOTTOM)
171) FLANGE BLINDED SAMPLING VALVE REQUIRED
FLANGE BLINDED DRAIN VALVE ON TANK
172) REQUIRED
(BOTTOM)
173) INSPECTION & TESTING
174) INSPECTION & TESTS AS PER SPECIFICATION
175) ROUTINE TESTS YES/ON ALL TRANSFORMERS
TYPE TESTS (IF NOT AVAILABLE FOR SIMILAR
176) YES/ ONE OF EACH RATING
TRANSFORMER)
SPECIAL TESTS (IF NOT AVAILABLE FOR SIMILAR
177) YES/ ONE OF EACH RATING
TRANSFORMER)
178) PAINTING
179) • COLOR RAL 7032
180) • PAINTING THICKNESS TANK ***
181) • PAINTING THICKNESS RADIATOR ***
182) GALVANISATION THICKNESS TANK ***
183) GALVANISATION THICKNESS RADIATOR ***